P08D09M PANDUIT | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 9
Technical content
www.panduit.com overview The Panduit® SmartZone™ G5 iPDU is more than a power distribution unit and energy meter. These iPDUs monitor the data center power and environment (at the rack or cabinet level), by continuously scanning for electrical circuit overloads, and physical environmental conditions that place critical IT equipment at risk. Panduit’s iPDUs provide comprehensive, accurate, energy measurement data to efficiently use power resources, make informed capacity planning decisions, improve uptime, measure PUE (power usage effectiveness), and drive green data center initiatives to save energy and money. Making the right choice in IT equipment is essential for a safe, efficient data center operation. Our full range of iPDUs, environmental sensors, and dual locking power cords are the key to fulfilling mission‐critical data center needs. SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) SPECIFICATION SHEET technical information Dimensions: Height Inch (mm) Width Inch (mm) Depth Inch (mm) 1U: 1U: 1U: 2U: 0U HALF: 0U HALF (2 sided): 0U MID: 0U FULL: 0U FULL (2 sided): 1.6 (40.6) 1.7 (43.2) 1.7 (43.2) 3.4 (86.4) 32.2 (817.9) 36 (914.4) 58.7 (1491) 68.9 (1750.1) 71.7 (1821.2) 17.5 (444.5) 17.5 (444.5) 17.5 (444.5) 17.5 (444.5) 2.0 (50.8) 2.0 (50.8) 2.0 (50.8) 2.0 (50.8) 2.0 (50.8) 2.0 (50.8) 7.8 (198.1) 10.6 (269.2) 7.8 (198.1) 2.1 (53.3) 4.4 (111.8) 2.1 (53.3) 2.1 (53.3) 4.4 (111.8) 0U Full +: 0U Full Wide: 0U Full Wide +: 74.6 (1896) 68.9 (1750.1) 74.0 (1880) 2.0 (50.8) 3.3 (83.8) 3.3 (83.8) 2.1 (53.3) 2.1 (53.3) 2.1 (53.3) Mounting: Vertical units provide up to 48 outlets and without encroaching on the EIA space. Horizontal units provide up to 16 outlets and mount in standard (1U or 2U) TIA/EIA rack space. key features and benefits HotSwappable Controller: Replace the controller and display module without having to power down the rack Redundant Network Access: Specifically designed for Landlord/Tenant (Co-Lo’s) allowing for remote access of real-time, vital statistics and operating information on two separate, secure networks. Hardened Security: Not only Physical but hardened Digital Security; layers within the firmware LDAP, SNMP v3, TLS, Encrypted Security; allows for Panduit PDUs to pass standard certified security scans. 1GB Ethernet: The 1G controller is compatible with the new Data Center Network switches being deployed - reducing special network configurations/resources required to support the iPDU. Plug & Play Sensors: Digital sensors not only allow for multiple sensors on the same bus; but also identify themselves to the controller to simplify setup & commissioning. Multi-Color PDUs: Different color PDUs simplify power feed identification & management. The new Panduit Intelligent PDUs are available in Black, White, Red, Blue, Yellow or Green. Mobile & Desktop Friendly Web GUI: The intelligent PDUs feature an enhanced designed web interface which detects the type of device that you are on; and automatically adjusts the screen for an optimal experience. Outlet Density: Meets demands of densely packed IT equipment in rack or cabinet space Form Factor: Optimal form factor enables efficient rack space utilization Operating Temperature: 60°C ambient at full load for operational reliability in high temperature areas (continued pg. 2)
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) electrical specifications Input Voltage North America
- Single-Phase 120V
- Single-Phase 208V
- Three-Phase Delta 208V
- Three-Phase Wye 120/208V
- Three-Phase Wye 415V International models
- Single-Phase 240V
- Three-Phase Wye 240/415V Input Current (per phase) North America
- 15A, 20A, 30A, 50A, 60A International models
- 16A, 32A Input Power North America
- 1.4 – 17.3 (kVA) International models
- 3.7 – 22 (kVA) Input Frequency 50/60 Hz Output Voltage 120 - 240 VAC Maximum output current (outlet) IEC C13: 10A IEC C19: 16A NEMA 5-20R: 16A Overload protection (where applicable) Circuit Breakers, hydraulic magnetic 10 kAIC Circuit Breakers for all 415V models for North America key features and benefits (continued) Cable Retention: Innovative cable tie accepting outlets allow for secure cord retention (C13 & C19 only) using a cable tie for added safety and security. (Panduit part number: PLT2I-C0) Circuit Breakers: Protects data center equipment for increased reliability by interrupting potentially hazardous circuit over-current conditions* Color Coded Circuits*: Easily identify phase to outlet banks to aid in fault isolation or load balancing External Chassis Ground: Meets NEC requirements and installation guidelines for IT equipment Load Balancing: Monitored through visual display on oLED (for 3 phase units only) Multiple Input Plug Options: A full breadth offering to seamlessly interoperate with existing building power wiring schemes Multiple Mounting Options: Enables simple out of the box commissioning and flexibility with Panduit cabinets and industry standard mounting features enabling installation into third party cabinets Mounting Buttons: Allows tool-less mounting of rack PDUs for faster installations on vertical 0U units Supported Metering: Frequency, VA, PF, plus aggregate and per phase Amperage, Voltage, Wattage, and Kilowatts per hour * Applies to products outfitted with circuit breakers iPDU product families MI Series: Rack PDUs that have the ability for aggregate power monitoring to quickly identify potential power issues, and reclaim available or under-utilized power capacity. MS Series: Rack PDUs that have the ability for aggregate power monitoring and outlet level switching capabilities for individual outlets or a group of outlets. Enabling power sequencing, rebooting equipment or restrict unauthorized use of individual outlets. MPO Series: Rack PDUs that have the ability for outlet level (and aggregate) power monitoring to quickly identify potential power issues, and reclaim available or under-utilized power capacity at the outlet level enabling the redeployment or decommissioning of individual servers to reclaim available or under-utilized power capacity. MSPO Series: Rack PDUs that have the ability for outlet level (and aggregate) power monitoring and outlet level switching capabilities for individual outlets or a group of outlets. Power monitoring at the individual outlet level provides actionable management data on the power consumption of each connected IT device enabling the redeployment or decommissioning of individual servers to reclaim available or under-utilized power capacity. Ideal for remote power reset, and cabinet power on sequencing and restrict unauthorized use of individual outlets.
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) cabinet compatibility Panduit iPDUs can be easily installed into Panduit (or third party cabinets) by utilizing the installed mounting buttons (18.4 mm diameter). Where necessary, a Small Diameter (14.5 mm) mounting button is available (sold separately, p/n: MA018). Panduit PDUs feature threaded inserts on the back and both sides for the ultimate in mounting flexibility. They safely and efficiently manage and distribute power to multiple devices through a single input power connector, per PDU, to enhance scalability of network build outs. general specifications Temperature: Operating 50° to 140° F (10° to 60° C) Temperature: Storage -4° to 140° F (-20° to 60° C) Relative Humidity: Operating 10% to 90% non-condensing Relative Humidity: Non-Operating 5 to 95% RH Relative Humidity: Storage 5% to 95% Elevation: Operating 0 to 10,000 ft. (0 to 3000 m) Elevation: Storage 0 to 30,000 ft. (0 to 9144 m) Conformance Standards North America - UL, CB Test Approved International - CE Approved, EAC Russia Approval Environmental Compliances RoHS & REACH
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) Monitored Input - MI Series Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 100-240VAC, 1-phase NA 15 1U 5-15P 0 1.4 8 (8)5-20R 1.7 17.5 10.6 P08D09M INTL 16 1U IEC 60309-316P6 0 3.7 12 (12)C13 1.7 17.5 10.6 P12D36M NA 20 1U 5-20P 0 1.9 8 (8)5-20R 1.7 17.5 10.6 P08D10M NA 20 1U L5-20P 0 1.9 8 (8)5-20R 1.7 17.5 10.6 P08D11M NA 20 1U L6-20P 0 3.3 12 (12)C13 1.7 17.5 10.6 P12D13M NA 50 1U CS8265C 3 8.3 6 (6)C19 1.7 17.5 10.6 P06D15M NA 30 2U L5-30P 2 2.9 16 (16)5-20R 3.4 17.5 10.6 P16D12M NA 30 2U L6-30P 2 5.0 16 (12)C13, (4)C19 3.4 17.5 10.6 P16D14M INTL 32 2U IEC 60309-332P6 2 7.4 16 (12)C13, (4)C19 3.4 17.5 10.6 P16D37M NA 15 0U HALF 5-15P 0 1.4 16 (16)5-20R 32.2 2.0 2.1 P16D20M NA 20 0U HALF 5-20P 0 1.9 16 (16)5-20R 32.2 2.0 2.1 P16D21M NA 20 0U HALF L5-20P 0 1.9 16 (16)5-20R 32.2 2.0 2.1 P16D22M INTL 16 0U MID IEC 60309-316P6 0 3.7 24 (20)C13, (4)C19 58.7 2.0 2.1 P24D40M NA 20 0U MID L6-20P 0 3.3 24 (20)C13, (4)C19 58.7 2.0 2.1 P24D24M NA 30 0U MID L5-30P 2 2.9 24 (24)5-20R 58.7 2.0 2.1 P24D23M NA 30 0U MID L6-30P 2 5.0 24 (20)C13, (4)C19 58.7 2.0 2.1 P24D07M INTL 32 0U Mid IEC 60309-332P6 2 7.4 24 (20)C13, (4)C19 58.7 2.0 2.1 P24D03M NA 30 0U FULL L6-30P 2 5.0 38 (32)C13, (6)C19 68.9 2.0 2.1 P38D25M INTL 32 0U FULL IEC 60309-332P6 2 7.4 34 (28)C13, (6)C19 68.9 2.0 2.1 P34D41M INTL 32 0U FULL IEC 60309-332P6 2 7.4 42 (36)C13, (6)C19 68.9 2.0 2.1 P42D06M NA 50 0U FULL CS8265C 3 8.3 36 (30)C13, (6)C19 68.9 2.0 2.1 P36D26M 208VAC, 3-Phase NA 30 1U L15-30P 3 8.6 6 (6)C19 1.7 17.5 10.6 P06D16M NA 30 1U L21-30P 3 8.6 6 (6)C19 1.7 17.5 10.6 P06D17M NA 50 1U CS8365C 6 14.4 6 (6)C19 1.7 17.5 10.6 P06D18M NA 60 1U IEC 60309-460P9 6 17.3 6 (6)C19 1.7 17.5 10.6 P06D19M NA 30 0U MID L15-30P 3 8.6 24 (18)C13, (6)C19 58.7 2.0 2.1 P24D27M NA 30 0U MID L21-30P 3 8.6 24 (18)C13, (6)C19 58.7 2.0 2.1 P24D01M NA 30 0U FULL L21-30P 3 8.6 30 (18)C13, (6)C19, (6)5-20R 68.9 2.0 2.1 P30D02M NA 30 0U FULL L15-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36D08M NA 30 0U FULL L21-30P 3 8.6 38 (30)C13, (6)C19, (2)5-20R 68.9 2.0 2.1 P38D28M NA 50 0U FULL CS8365C 3 10.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36D29M NA 50 0U FULL CS8365C 6 14.4 24 (12)C13, (12)C19 68.9 2.0 2.1 P24D31M NA 60 0U FULL IEC 60309-460P9 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24D34M NA 50 0U HALF - 2 sided CS8365C 6 14.4 24 (18)C13, (6)C19 36.0 2.0 4.4 P24D30M NA 60 0U HALF - 2 sided IEC 60309-460P9 6 17.3 24 (18)C13, (6)C19 36.0 2.0 4.4 P24D33M NA 50 0U FULL - 2 sided CS8365C 6 14.4 48 (36)C13, (12)C19 71.7 2.0 4.4 P48D32M NA 60 0U FULL - 2 sided IEC 60309-460P9 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48D35M 230/415VAC, 3-Phase INTL 16 1U IEC 60309-516P6 0 11.0 6 (6)C19 1.7 17.5 10.6 P06D38M INTL 32 1U IEC 60309-532P6 6 22.0 6 (6)C19 1.7 17.5 10.6 P06D39M INTL 16 0U MID IEC 60309-516P6 0 11.0 30 (24)C13, (6)C19 58.7 2.0 2.1 P30D05M INTL 16 0U FULL IEC 60309-516P6 0 11.0 42 (36)C13, (6)C19 68.9 2.0 2.1 P42D42M INTL 32 0U FULL IEC 60309-532P6 6 22.0 24 (12)C13, (12)C19 68.9 2.0 2.1 P24D43M INTL 32 0U FULL IEC 60309-532P6 6 22.0 42 (30)C13, (12)C19 68.9 2.2 2.1 P42D04M INTL 32 0U FULL - 2 sided IEC 60309-532P6 6 22.0 48 (36)C13, (12)C19 71.7 2.0 4.4 P48D44M (continued pg. 5)
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) Monitored Input - MI Series (continued) Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 415VAC, 3-Phase NA 30 1U IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 6 (6)C19 1.7 17.5 10.6 P06D01M NA 30 1U IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 6 (6)C19 1.7 17.5 10.6 P06D03M NA 30 1U NEMA L22-30P 6 17.3 6 (6)C19 1.7 17.5 10.6 P06D02M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24D02M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24D05M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24D04M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (24)C13, (12)C19 68.9 2.0 2.1 P36D01M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (24)C13, (12)C19 68.9 2.0 2.1 P36D03M NA 30 0U FULL NEMA L22-30P 6 17.3 36 (24)C13, (12)C19 68.9 2.0 2.1 P36D02M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48D01M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48D07M NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48D02M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 48 (48)C13 68.9 3.3 2.1 P48D03M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 68.9 3.3 2.1 P48D04M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 68.9 3.3 2.1 P48D08M NA 30 0U FULL + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 42 (36)C13, (6)C19 74.6 2.0 2.1 P42D05M NA 30 0U FULL + NEMA L22-30P 6 17.3 42 (36)C13, (6)C19 74.6 2.0 2.1 P42D07M NA 30 0U FULL + IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 42 (36)C13, (6)C19 74.6 2.0 2.1 P42D08M Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America include 10 kAIC circuit breakers. Monitored Switched - MS Series Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 100-240VAC, 1-phase NA 15 1U 5-15P 0 1.4 8 (8)5-20R 1.7 17.5 10.6 P08E14M INTL 16 1U IEC 60309-316P6 0 3.7 8 (8)C13 1.7 17.5 10.6 P08E25M NA 20 1U 5-20P 0 1.9 8 (8)5-20R 1.7 17.5 10.6 P08E15M NA 20 1U L5-20P 0 1.9 8 (8)5-20R 1.7 17.5 10.6 P08E16M NA 20 1U L6-20P 0 3.3 8 (8)C13 1.7 17.5 10.6 P08E18M INTL 32 1U IEC 60309-332P6 2 7.4 8 (8)C13 1.7 17.5 10.6 P08E05M NA 30 2U L5-30P 2 2.9 16 (16)5-20R 3.4 17.5 10.6 P16E17M NA 30 2U L6-30P 2 5.0 16 (12)C13, (4)C19 3.4 17.5 10.6 P16E19M INTL 32 2U IEC 60309-332P6 2 7.4 16 (12)C13, (4)C19 3.4 17.5 10.6 P16E26M NA 15 0U HALF 5-15P 0 1.4 12 (12)5-20R 36.1 2.0 2.1 P12E20M INTL 16 0U HALF IEC 60309-316P6 0 3.7 16 (12)C13, (4)C19 36.1 2.0 2.1 P16E27M NA 20 0U HALF 5-20P 0 1.9 12 (12)5-20R 36.1 2.0 2.1 P12E21M NA 20 0U HALF L5-20P 0 1.9 12 (12)5-20R 36.1 2.0 2.1 P12E22M NA 20 0U HALF L6-20P 0 3.3 16 (12)C13, (4)C19 36.1 2.0 2.1 P16E24M INTL 16 0U MID IEC 60309-316P6 0 3.7 24 (20)C13, (4)C19 58.7 2.0 2.1 P24E04M NA 30 0U MID L5-30P 2 2.9 18 (18)5-20R 58.7 2.0 2.1 P18E23M NA 30 0U FULL L6-30P 2 5.0 24 (20)C13, (4)C19 68.9 2.0 2.1 P24E28M NA 30 0U FULL L6-30P 2 5.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36E33M INTL 32 0U FULL IEC 60309-332P6 2 7.4 24 (20)C13, (4)C19 68.9 2.0 2.1 P24E01M INTL 32 0U FULL IEC 60309-332P6 2 7.4 32 (24)C13, (8)C19 68.9 2.0 2.1 P32E06M INTL 32 0U FULL - wide IEC 60309-332P6 2 7.4 44 (38)C13, (6)C19 68.9 3.3 2.1 P44E07M
Monitored Switched - MS Series Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 208VAC, 3-Phase NA 30 0U FULL L15-30P 3 8.6 24 (18)C13, (6)C19 68.9 2.0 2.1 P24E29M NA 30 0U FULL L21-30P 3 8.6 24 (18)C13, (6)C19 68.9 2.0 2.1 P24E30M NA 30 0U FULL L15-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36E34M NA 30 0U FULL L21-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36E35M NA 50 0U FULL CS8365C 6 14.4 24 (12)C13, (12)C19 68.9 2.0 2.1 P24E31M NA 50 0U FULL CS8365C 3 10.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36E12M NA 60 0U FULL IEC 60309-460P9 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24E32M NA 60 0U FULL - 2 sided IEC 60309-460P9 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48E13M 230/415VAC, 3-Phase INTL 16 0U FULL IEC 60309-516P6 0 11.0 24 (18)C13, (6)C19 68.9 2.0 2.1 P24E02M INTL 16 0U FULL IEC 60309-516P6 0 11.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36E08M INTL 32 0U FULL IEC 60309-532P6 6 22.0 24 (12)C13, (12)C19 68.9 2.0 2.1 P24E03M INTL 32 0U FULL - wide IEC 60309-532P6 6 22.0 36 (24)C13, (12)C19 68.9 3.3 2.1 P36E09M INTL 32 0U FULL - 2 sided IEC 60309-532P6 6 22.0 48 (36)C13, (12)C19 71.7 2.0 4.4 P48E10M 415VAC, 3-Phase NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24E05M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24E07M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (24)C13 68.9 2.0 2.1 P24E08M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24E09M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24E10M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (24)C13 68.9 2.0 2.1 P24E11M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24E06M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24E12M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (24)C13 68.9 2.0 2.1 P24E13M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36E01M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36E03M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36E04M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36E05M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36E02M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36E06M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48E01M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 71.7 2.0 4.4 P48E07M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48E08M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 71.7 2.0 4.4 P48E09M NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48E02M NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (48)C13 71.7 2.0 4.4 P48E14M NA 30 0U FULL - Wide + NEMA L22-30P 6 17.3 48 (48)C13 74.0 3.3 2.1 P48E04M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 74.0 3.3 2.1 P48E03M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 74.0 3.3 2.1 P48E11M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48E05M NA 30 0U FULL - Wide + NEMA L22-30P 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48E06M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48E12M Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America feature 10 kAIC circuit breakers. SmartZone™ G5 Intelligent Power Distribution Units (iPDUs)
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) Monitored Per Outlet - MPO Series Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 100-240VAC, 1-phase NA 30 0U FULL NEMA L6-30P 2 5.0 24 (20)C13, (4)C19 68.9 2.0 2.1 P24F01M NA 30 0U FULL NEMA L6-30P 2 5.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36F15M INTL 32 0U FULL IEC 60309-332P6 2 7.4 24 (20)C13, (4)C19 68.9 2.0 2.1 P24F06M INTL 32 0U FULL IEC 60309-332P6 2 7.4 32 (24)C13, (8)C19 68.9 2.0 2.1 P32F10M INTL 32 0U FULL - wide IEC 60309-332P6 2 7.4 44 (38)C13, (6)C19 68.9 3.3 2.1 P44F11M 208VAC, 3-Phase NA 30 0U FULL NEMA L15-30P 3 8.6 24 (18)C13, (6)C19 68.9 2.0 2.1 P24F02M NA 30 0U FULL NEMA L21-30P 3 8.6 24 (18)C13, (6)C19 68.9 2.0 2.1 P24F03M NA 30 0U FULL NEMA L15-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36F16M NA 30 0U FULL NEMA L21-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36F17M NA 50 0U FULL Hubbell CS8365C 6 14.4 24 (12)C13, (12)C19 68.9 2.0 2.1 P24F04M NA 50 0U FULL Hubbell CS8365C 3 10.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36F18M NA 60 0U FULL IEC 60309-460P9 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24F05M NA 60 0U FULL - 2 sided IEC 60309-460P9 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48F19M 230/415VAC, 3-Phase INTL 16 0U FULL IEC 60309-516P6 0 11.0 24 (18)C13, (6)C19 68.9 2.0 2.1 P24F07M INTL 16 0U FULL IEC 60309-516P6 0 11.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36F12M INTL 32 0U FULL IEC 60309-532P6 6 22.0 24 (12)C13, (12)C19 68.9 2.0 2.1 P24F08M INTL 32 0U FULL - wide IEC 60309-532P6 6 22.0 36 (24)C13, (12)C19 68.9 3.3 2.1 P36F13M INTL 32 0U FULL - 2 sided IEC 60309-532P6 6 22.0 48 (36)C13, (12)C19 71.7 2.0 4.4 P48F09M 415VAC, 3-Phase NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24F09M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24F11M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (24)C13 68.9 2.0 2.1 P24F12M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24F13M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24F14M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 24 (24)C13 68.9 2.0 2.1 P24F15M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24F10M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24F16M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (24)C13 68.9 2.0 2.1 P24F17M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36F01M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36F03M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36F04M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36F05M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36F02M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36F06M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48F01M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 71.7 2.0 4.4 P48F07M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48F08M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 71.7 2.0 4.4 P48F13M NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48F02M NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (48)C13 71.7 2.0 4.4 P48F10M NA 30 0U FULL - Wide + NEMA L22-30P 6 17.3 48 (48)C13 74.0 3.3 2.1 P48F04M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 74.0 3.3 2.1 P48F03M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 74.0 3.3 2.1 P48F11M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48F05M NA 30 0U FULL - Wide + NEMA L22-30P 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48F06M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48F12M Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America feature 10 kAIC circuit breakers.
SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) Monitored Switched Per Outlet - MSPO Series Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 100-240VAC, 1-phase INTL 16 1U IEC 60309-316P6 0 3.7 8 (8)C13 1.7 17.5 10.6 P08G10M INTL 32 1U IEC 60309-332P6 2 7.4 8 (8)C13 1.7 17.5 10.6 P08G12M INTL 16 0U Mid IEC 60309-316P6 0 3.7 24 (20)C13, (4)C19 58.7 2.0 2.1 P24G11M NA 30 0U FULL L6-30P 2 5.0 24 (20)C13, (4)C19 68.9 2.0 2.1 P24G01M NA 30 0U FULL L6-30P 2 5.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36G18M INTL 32 0U FULL IEC 60309-332P6 2 7.4 24 (20)C13, (4)C19 68.9 2.0 2.1 P24G06M INTL 32 0U FULL IEC 60309-332P6 2 7.4 32 (24)C13, (8)C19 68.9 2.0 2.1 P32G13M INTL 32 0U FULL - wide IEC 60309-332P6 2 7.4 44 (38)C13, (6)C19 68.9 3.3 2.1 P44G14M 208VAC, 3-Phase NA 30 0U FULL L15-30P 3 8.6 24 (18)C13, (6)C19 68.9 2.0 2.1 P24G02M NA 30 0U FULL L21-30P 3 8.6 24 (18)C13, (6)C19 68.9 2.0 2.1 P24G03M NA 30 0U FULL L15-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36G22M NA 30 0U FULL L21-30P 3 8.6 36 (30)C13, (6)C19 68.9 2.0 2.1 P36G19M NA 50 0U FULL CS8365C 6 14.4 24 (12)C13, (12)C19 68.9 2.0 2.1 P24G04M NA 50 0U FULL CS8365C 3 10.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36G20M NA 60 0U FULL IEC 60309-460P9 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24G05M NA 60 0U FULL - 2 sided IEC 60309-460P9 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48G21M 230/415VAC, 3-Phase INTL 16 0U FULL IEC 60309-516P6 0 11.0 24 (18)C13, (6)C19 68.9 2.0 2.1 P24G07M INTL 16 0U FULL IEC 60309-516P6 0 11.0 36 (30)C13, (6)C19 68.9 2.0 2.1 P36G15M INTL 32 0U FULL IEC 60309-532P6 6 22.0 24 (12)C13, (12)C19 68.9 2.0 2.1 P24G08M INTL 32 0U FULL - wide IEC 60309-532P6 6 22.0 36 (24)C13, (12)C19 68.9 3.3 2.1 P36G16M INTL 32 0U FULL - 2 sided IEC 60309-532P6 6 22.0 48 (36)C13, (12)C19 71.7 2.0 4.4 P48G09M 415VAC, 3-Phase NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24G09M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24G13M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (24)C13 68.9 2.0 2.1 P24G14M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24G15M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24G16M NA 30 0U FULL IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 24 (24)C13 68.9 2.0 2.1 P24G17M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (12)C13, (12)C19 68.9 2.0 2.1 P24G10M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (18)C13, (6)C19 68.9 2.0 2.1 P24G18M NA 30 0U FULL NEMA L22-30P 6 17.3 24 (24)C13 68.9 2.0 2.1 P24G19M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36G01M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36G03M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36G04M NA 30 0U FULL - Wide IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36G05M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 36 (24)C13, (12)C19 68.9 3.3 2.1 P36G02M NA 30 0U FULL - Wide NEMA L22-30P 6 17.3 36 (30)C13, (6)C19 68.9 3.3 2.1 P36G06M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48G01M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 71.7 2.0 4.4 P48G07M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48G08M NA 30 0U FULL - 2 sided IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 71.7 2.0 4.4 P48G10M NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (36)C13, (12)C19 71.7 2.0 4.4 P48G02M (continued pg. 9)
WORLDWIDE SUBSIDIARIES AND SALES OFFICES For a copy of Panduit product warranties, log on to www.panduit.com/warranty PANDUIT US/CANADA Phone: 800.777.3300 PANDUIT EUROPE LTD. London, UK cs-emea@panduit.com Phone: 44.20.8601.7200 PANDUIT JAPAN Tokyo, Japan cs-japan@panduit.com Phone: 81.3.6863.6000 PANDUIT SINGAPORE PTE. LTD. Republic of Singapore cs-ap@panduit.com Phone: 65.6305.7575 PANDUIT AUSTRALIA PTY. LTD. Victoria, Australia cs-aus@panduit.com Phone: 61.3.9794.9020 PANDUIT LATIN AMERICA Guadalajara, Mexico cs-la@panduit.com Phone: 52.33.3777.6000 Visit us at www.panduit.com For more information Contact Technical Support by email: techsupport@panduit.com or by phone: (866) 405-6654 ©2019 Panduit Corp. ALL RIGHTS RESERVED. PUSP28--SA-ENG SmartZone™ G5 Intelligent Power Distribution Units (iPDUs) Monitored Switched Per Outlet - MSPO Series (continued) Region Input Current per phase Form Factor Input Plug Type Circuit Breakers Apparent Power (kVA) Outlet Count Outlet Configuration Length (inches) Width (inches) Depth (inches) at Outlet position Panduit SKU Part No. 415VAC, 3-Phase NA 30 0U FULL - 2 sided NEMA L22-30P 6 17.3 48 (48)C13 71.7 2.0 4.4 P48G11M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (48)C13 74.0 3.3 2.1 P48G03M NA 30 0U FULL - Wide + NEMA L22-30P 6 17.3 48 (48)C13 74.0 3.3 2.1 P48G04M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP44) 6 17.3 48 (48)C13 74.0 3.3 2.1 P48G12M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48G05M NA 30 0U FULL - Wide + NEMA L22-30P 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48G06M NA 30 0U FULL - Wide + IEC 60309 3P+N+E 6h 30A (IP67) 6 17.3 48 (42)C13, (6)C19 74.0 3.3 2.1 P48G13M Note: MOQ 80 & LT 20 Business Days applies for all 415V PDUs for N. America. All 415V PDUs for N. America feature 10 kAIC circuit breakers.