Features
- Input voltage range: 22 - 60VDC
- Operating ambient temperature range: -40°C to +80°C
- High efficiency up to 97%
- 1500VAC insulation voltage
- Two input status indicators, relay contact signal output
- DC OK function
- Operating altitude up to 5000m
- Supporting for N+1 parallel redundancy
- 3 Years Warranty MPIR-20 is one of Mornsun Din-rail parallel redundancy module. It features wide input voltage range, wide operating temperature, cost-effective, high efficiency and high reliability. It offers excellent EMC performance and meet IEC/EN61000-4, CISPR32/EN55032, IEC/EN/UL62368, EN61558, EN60335 standards and it is widely used in areas of industrial, electricity, security, telecommunications etc. Selection Guide Part Number Voltage Drop Vin-Vo (V/Typ.) Nominal Output Current (A) Efficiency (24/48VDC, %/Typ.) MPIR-20 0.65 20 97 Input Specifications Item Operating Conditions Min. Typ. Max. Unit Input Voltage Range DC input 22 24/48 60 V DC Input Current Range The sum of the two input currents is not more than 20A, input current rating of 10A per channel. -- 20 A Input Under-voltage Alarm* One input 24V, test another input voltage when triggers the under-voltage alarm (one LED turns off, the relay changes from on to off) V DC One input 48V, test another input voltage when triggers the under-voltage alarm (one LED turns off, the relay changes from on to off) Input Over-voltage Alarm* One input 24V, test another input voltage when triggers the over-voltage alarm (one LED turns off, the relay changes from on to off) One input 48V, test another input voltage when triggers the over-voltage alarm (one LED turns off, the relay changes from on to off) Hot Plug Unavailable Note: *LED state: Vin1 triggers the under-voltage alarm, Vin1 LED turns off, Vin2 LED turns on; Vin1 triggers the over-voltage alarm, Vin1 LED turns on, Vin2 LED turns off.
Newark.com/multicomp-pro Farnell.com/multicomp-pro sg.element14.com/b/multicomp-pro Page <2> 16/08/23 V1.2 Output Specifications Item Operating Conditions Min. Typ. Max. Unit Ripple & Noise* 20MHz bandwidth (peak-to-peak value) 200 -- mV DC OK Function When the two input voltages are normal and the voltage difference does not exceed the over-voltage or under-voltage alarm, the DC OK function is normal (the relay on), the two input LED indicators light on Output Power 24V/20A 480 W 48V/20A 960 General Specifications Item Operating Conditions Min. Typ. Max. Unit Isolation Test Input - output Electric strength test for 1min., leakage current < 2mA 1500 V AC Insulation Resistance Input - output At 500V DC 50 MΩ Operating Temperature -40 80 °C Storage Temperature -40 85 Storage Humidity Non-condensing -- 95 %RH Power Derating Operating temperature derating +60°C to +80°C 2.25 -- -- %/°C Safety Standard Meet IEC/EN/UL62368/ EN61558/EN60335 Safety Certification EN62368 Safety Class CLASS I MTBF MIL-HDBK-217F@25°C >1000,000 h Mechanical Specifications Case Material Metal (AL1100, SGCC) Dimensions 35mm x 125mm x 112.7mm Weight 365g (Typ.) Cooling Method Natural air cooling
Newark.com/multicomp-pro Farnell.com/multicomp-pro sg.element14.com/b/multicomp-pro Page <3> 16/08/23 V1.2 Electromagnetic Compatibility (EMC) Emissions CE CISPR32/EN55032 CLASS B RE CISPR32/EN55032 CLASS B Immunity ESD IEC/EN 61000-4-2 Contact ±8KV/Air ±15KV perf. Criteria A RS IEC/EN61000-4-3 10V/m perf. Criteria A EFT IEC/EN61000-4-4 ±2KV perf. Criteria A Surge IEC/EN61000-4-5 Line to line ±1KV/line to ground ±2KV perf. Criteria A CS IEC/EN61000-4-6 10 Vr.m.s perf. Criteria A Product Characteristic Curve
Newark.com/multicomp-pro Farnell.com/multicomp-pro sg.element14.com/b/multicomp-pro Page <4> 16/08/23 V1.2 Important Notice : This data sheet and its contents (the “Information”) belong to the members of the AVNET group of companies (the “Group”) or are licensed to it. No licence is granted for the use of it other than for information purposes in connection with the products to which it relates. No licence of any inte llectual property rights is granted. The Information is subject to change without notice and replaces all data sheets previously su pplied. The Information supplied is believed to be accurate but the Group assumes no responsibility for its accuracy or compl eteness, any error in or omission from it or for any use made of it. Users of this data sheet should check for themselves the Infor mation and the suitability of the products for their purpose and not make any assumptions based on information included or omitted. Liability for loss or damage resulting from any reliance on the Inf ormation or use of it (including liability resulting from negligence or where the Group was aware of the possibility of such loss or damage arising) is excluded. This will not operate to limit or restrict the Group’s liability for death or personal injury resulting from its negligence. Multicomp Pro is the registered trademark of Premier Farnell Limited 2019. Dimensions and Recommended Layout Notes: 1. Unless otherwise specified, parameters in this datasheet were measured under the conditions of Ta=25°C, humidity<75%RH with nominal input voltage and rated output load; 2. The ambient temperature derating of 5°C/1000m is needed for operating altitude greater than 2000m; 3. In order to improve the efficiency at high input voltage, there will be audible noise generated, but it does not affect product performance and reliability; Part Number Table Description Part Number DC-DC DIN Rail Redundancy Module, 20A MPIR-20