MKS-X OMRON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 12
Technical content
General Purpose Power Relays MKS-X 1 General Purpose Power Relays MKS-X MK-S-series Relays with AC and DC Load switching Models
- Models for DC Loads can switch 220 VDC, 10 A (resistive). Models for AC Loads can switch 250 VAC, 15 A (resistive). Lineup includes models with 1FormA and 1FormA+1FormB contact arrangements. Models available with operation indicators and built-in test buttons. Standards: UL/CSA, IEC (TÜV certification) RoHS compliant.
Ordering Information
■List of Models ■Accessory (Order Separately) Connecting Socket and Hold-down Clips Note: 1. The P7M-06P , P7MF-06, and P7MF-06-D can be used with models for DC loads with an SPST -NO or SPST -NO/SPST -NC contact form or with models for AC loads with an SPST -NO or SPST -NO/SPST -NC contact form. 2. The P7MF-06-D has a built-in diode and can thus be used only with Relays with DC operating coils. Do not use it with a Relay wi th an AC operating coil. 3. Refer to Gang Mounting in the Safety Precautions section for the conditions required to gang mounti multiple relays side-by-side. 4. Use the Clips to securely mount the Relay and prevent it from falling due to vibration or shock. Models for DC Loads Models for AC Loads Contact form SPST-NO SPST-NO/SPST-NC SPST-NO SPST-NO/SPST-NC Type Model Model Model Model Standard MKS1XT-10 MKS2XT-11 MKS1T-10 MKS2T-11 Built-in Operation Indicators MKS1XTN-10 MKS2XTN-11 MKS1TN-10 MKS2TN-11 Test Button MKS1XTI-10 MKS2XTI-11 MKS1TI-10 MKS2TI-11 Test Button and Built-in Operation Indicators MKS1XTIN-10 MKS2XTIN-11 MKS1TIN-10 MKS2TIN-11 Classifications Built-in diode Socket Hold-down Clip Back-connecting Socket PCB Mount No P7M-06P PYC-A2Front-connecting Socket DIN Track or Panel Mount No P7MF-06 Ye s P7MF-06-D Rated voltage Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in the specifications. Example: MKS2XTIN-11 AC240 2. Refer to Terminal Arrangement and Internal Connections for all wiring diagrams.
2 General Purpose Power Relays MKS-X
■Contact Ratings Models for DC Loads Note: 1. If the L/R of an inductive load exceeds 7 ms with a Model for a DC Load, the arc interruption time must be less than approximately 50 ms to use the Relay. Design the circuit so that the arc interruption time is 50 ms or less. 2. These values apply to a switching frequency of 30 times per minute. Models for AC Loads Note: These values apply to a switching frequency of 20 times per minute. Contact form SPST-NO SPST-NO/SPST-NC Model MKS1XT(I)(N)-10 MKS2XT(I)(N)-11 Load Resistive load Inductive load Resistive load Inductive load Item L/R = 7 ms DC13 class L/R = 7 ms DC13 class Contact configuration NO Double-break Double-break NC --- Single-break Contact material AgSnIn AgSnIn Rated load NO 10 A, 220 VDC 5 A, 220 VDC 0.4 A, 220 VDC 5 A, 220 VDC 3 A, 220 VDC 0.2 A, 220 VDC NC --- 2 A, 220 VDC 0.3 A, 220 VDC 0.1 A, 220 VDC Rated carry current NO 10 A 5 A NC --- 2 A Max. switching voltage NO 220 VDC 220 VDC NC --- Max. switching current NO 10 A 5 A NC --- 2 A Max. switching capacity (reference value) NC --- 440 W --- ---Contact form SPST-NO SPST-NO/SPST-NC Model MKS1T(I)(N)-10 MKS2T(I)(N)-11 Load Resistive load Resistive loadItem Contact configuration NO Double-break Double-break NC --- Single-break Contact material AgSnIn AgSnIn Rated load NO 15 A, 250 VAC 15 A, 250 VAC NC --- 5 A, 250 VAC Rated carry current NO 15 A 15 A NC --- 5 A Max. switching voltage NO 250 VAC 250 VAC NC --- Max. switching current NO 15 A 15 A NC --- 5 A Max. switching capacity (reference value) NO 3,750 VA 3,750 VA NC --- 1,250 VA
General Purpose Power Relays MKS-X 3 ■Coil Ratings Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20% for AC rated current and ±15% for DC coil resistance. 2. Performance characteristic data are measured at a coil temperature of 23°C. 3. The Maximum Voltage is the highest voltage that can be applied to the coil temporarily, not continuously. 4. The rated current is approximately 5 mA higher for Models with Built-in Operation Indicators (DC operating coils). ■Characteristics Note: 1. The values given above are initial values. 2. The contact resistance was measured for 1 A at 5 VDC using the voltage drop method. 3. The operate time was measured with the rated voltage imposed and any contact bounce ignored at an ambient temperature of 23°C. 4. The insulation resistance was measured with a 500-VDC insulation resistance tester at the same places as those used for checking the dielectric strength. 5. The electrical endurance was measured at an ambient temperature of 23°C. 6. P level: λ60=0.1 x 10-6/operations Item Rated current (mA) Coil resistance (Ω) Must operate voltage (V) Must release voltage (V) Max. voltage (V) Power consumption (VA, W)Rated voltage (V) 50 Hz 60 Hz AC 24 110 96.3 48.4 80% max. of rated voltage 30% min. of rated voltage at 60 Hz 25% min. of rated voltage at 50 Hz 110% of rated voltage Approx. 2.3 VA at 60 Hz Approx. 2.7 VA at 50 Hz 100 26.6 23.1 760 110 24.2 21.0 932 120 22.2 19.3 1,130 200 13.3 11.6 3,160 220 12.1 10.5 3,550 230 11.5 10.0 4,250 240 11.0 9.6 4,480 DC 12 126 95 15% min. of rated voltage Approx. 1.5 W 24 63.2 380 48 32.0 1,500 110 13.6 8,060 220 6.8 32,200 Contact resistance (See note 2) 100 mΩ max. Operate time (See note 3) AC: 20 ms max. DC: 30 ms max. Release time (See note 3) 20 ms max. Max. operating frequency Mechanical 18,000 operations/h Electrical Models for DC loads: 1,800 times/hour Models for AC loads: 1,200 times/hour Insulation resistance (See note 4) 100 MΩ min. Dielectric strength 2,500 VAC 50/60 Hz for 1 min. between coil and contacts 2,500 VAC 50/60 Hz for 1 min. between contacts of different polarity 1,000 VAC 50/60 Hz for 1 min. between contacts of same polarity Vibration resistance Destruction: 10 to 55 Hz, 1.0-mm double amplitude Malfunction: 10 to 55 Hz, 1.5-mm double amplitude Shock resistance Destruction: 1,000 m/s 2 when relay is properly mounted into P7M-06P PCB socket 500m/s2 when relay is properly mounted into P7MF-06(-D) socket Malfunction 100 m/s 2 Life expectancy Mechanical 1,000,000 operations min. (at 18,000 operations/hr) Electrical (See note 5) 100,000 operations min. (at rated load and maximum switching frequency) Minimum permissible load (Reference value. See note 6) 10 mA at 24 VDC Ambient operating temperature −40°C to 60°C (with no icing or condensation) Note: The range is −25°C to 60°C for models with built-in operation indicators. Ambient operating humidity 5% to 85% Weight SPST -NO: Approx. 73 g, SPST -NO/SPST -NC: Approx. 82 g
4 General Purpose Power Relays MKS-X
■Approved Standards UL Recognized CSA Certified IEC Standard/TÜV Certification: IEC61810-1 (Certification No. R50104853) Model Coil ratings Contact ratings Operations MKS1XT@-@ 12 to 220 VDC 24 to 240 VAC NO contacts
10 A, 220 VDC (Resistive)
5 A, 220 VDC L/R (T0.632) = 7 ms 0.4 A, 220 VDC L/R (T0.95) = 300 ms 6,000 MKS2XT@-@ NO contacts
5 A, 220 VDC (Resistive)
3 A, 220 VDC L/R (T0.632) = 7 ms 0.2 A, 220 VDC L/R (T0.95) = 300 ms NC contacts
2 A, 220 VDC (Resistive)
0.3 A, 220 VDC L/R (T0.632) = 7 ms 0.1 A, 220 VDC L/R (T0.95) = 300 ms MKS1T@-@ NO contacts 15 A, 250 VAC (Resistive) MKS2T@-@ NO contacts 15 A, 250 VAC (Resistive) NC contacts 5 A, 250 VAC (Resistive) Model Coil ratings Contact ratings Operations MKS1XT@-@ 12, 24, 48, 110, 220 VDC 24, 100, 110, 120, 200, 220, 230, 240 VAC NO contacts DC-1: 10 A, 220 VDC 5 A, 220 VDC L/R (T0.632) = 7 ms DC-13: 0.4 A, 220 VDC 100,000 MKS2XT@-@ NO contacts DC-1: 5 A, 220 VDC 3 A, 220 VDC L/R (T0.632) = 7 ms DC-13: 0.2 A, 220 VDC NC contacts DC-1: 2 A, 220 VDC 0.3 A, 220 VDC L/R (T0.632) = 7 ms DC-13: 0.1 A, 220 VDC MKS1T@-@ NO contacts AC-1: 15 A, 250 VAC 50/60 Hz MKS2T@-@ NO contacts AC-1: 15 A, 250 VAC 50/60 Hz NC contacts AC-1: 5 A, 250 VAC 50/60 Hz
General Purpose Power Relays MKS-X 5 Engineering Data Maximum Switching Power Ambient Temperature vs. Pick-up and Drop out Voltage Inductive Load Switching Power (Models for DC Loads) MKS1XT@-10 MKS2XT@-11 MKS1T@-10 MKS2T@-11 100 0.4 0.1 0.01 100101 1.000 Switching voltage (V) Switching current (A)DC inductive load L/R = 7 ms DC resistive load DC inductive load DC13 class DC resistive load NO DC resistive load L/R = 7 ms NO DC resistive load NC DC resistive load L/R = 7 ms NC DC resistive load DC13 class NC DC resistive load DC13 class NO 100 0.2 0.3 0.1 0.01 100101 1.000 Switching voltage (V) Switching current (A) AC resistive load Switching voltage (V) Switching current (A) 100 0.1 0.01 100101 1.000 AC resistive load NO AC resistive load NC Switching voltage (V) Switching current (A) 100 0.1 0.01 100101 1.000 MKS2XT-11 AC Specification (60 Hz) MKS2XT-11 DC Specification MKS1XT@-10 MKS2XT @-11 Must operate voltage Must release voltage Ambient temperature (°C) Must operate/release voltage (%) Number of Relays: 5100 23-40 60 Must operate voltage Must release voltage Number of Relays: 5 Ambient temperature (°C) Must operate/release voltage (%) 100 23-40 60 100 0.1 100 50 10 0 7 Load time constant (ms) Switching current (A)
220 VDC
0.1 0.01 100 50 10 0 7 Load time constant (ms) Switching current (A)
6 General Purpose Power Relays MKS-X
Dimensions (Unit: mm) Terminal Arrangement and Internal Connection (Bottom View) Note: 1. Wire properly using the correct coil polarity. 2. The contact terminals on Models for DC Loads have polarity. Wire properly using the correct polarity. MKS1XT-10 MKS1XTI-10 MKS1XTN-10 MKS1XTIN-10 MKS2XT-11 MKS2XTI-11 MKS2XTN-11 MKS2XTIN-11 DC specification AC specification DC specification AC specification MKS1T-10 MKS1TI-10 MKS1TN-10 MKS1TIN-10 MKS2T-11 MKS2TI-11 MKS2TN-11 MKS2TIN-11 DC specification AC specification DC specification AC specification 34.5 max. 44 max. 34.5 max. 0.8 7.3 Models for DC Loads Standard Models MKS1XT-10 MKS2XT-11 Models with Built-in Operation Indicators MKS1XTN-10 MKS2XTN-11 Models for AC Loads Standard Models MKS1T-10 MKS2T-11 Models with Built-in Operation Indicators MKS1TN-10 MKS2TN-11 34.5 max. 3.5 44 max. 34.5 max. 0.8 7.3 29.7 0.5 Models for DC Loads Models with Test Button MKS1XTI-10 MKS2XTI-11 Models with Test Button and Built-in Operation Indicators MKS1XTIN-10 MKS2XTIN-11 Models for AC Loads Models with Test Button MKS1TI-10 MKS2TI-11 Models with Test Button and Built-in Operation Indicators MKS1TIN-10 MKS2TIN-11 BA 6 (+) BA 8 (+) 6 (+)4 B (− )A (+) 6 (+) 4 BA 6 (+) B (− )A (+) 8 (+) 6 (+) BA 8 (+) 6 (+) BA BA B (− )A (+) 6 4 BA B (− )A (+) BA
General Purpose Power Relays MKS-X 7 Connecting Socket Back-connecting Socket Front-connecting Socket 8.3 7.7 5.5 0.9 PCB Mounting Holes (Bottom View) Terminal Arrangement/Internal Connections (Bottom View) A B 39 max. 43 max. 21.9 4.35 0.9 7.7 8.3 5.5 39 max. 22.1 11.05 11.05 Dimensions P7M-06P 39 max. 24.3 34 max. 78 max. 66±0.3 31±0.2 P7MF-06 Note: 1. The internal connections diagram is for the MKS2(X)T@@-11. 2. The P7MF-06-D has polarity. Be careful to wire with the correct polarity. P7MF-06-D Two, M4 or two 3.5-dia. hole 35.5 Six, M3 x 8 Mounting Holes (TOP View) Terminal Arrangement/Internal Connections (TOP View)Dimensions P7MF-06 P7MF-06-D
8 General Purpose Power Relays MKS-X
One Set (Two Clips) 4.5 1.2 42.8 5 max. 4.5 Note: The minimum order for the PYC-A2 is ten clips. MK-S(X)64 61 P7M-06P MK-S(X) P7MF-06 P7MF-06-D
General Purpose Power Relays MKS-X 9 Safety Precautions Be sure to read the precautions and information common to all electromechanical relays, contained in the Technical User’s Guide, “Electromechanical Relays, Technical Information” for correct use. Precautions for Correct Use Installation Models for DC loads (i.e., models with “X” in the model number) have permanent magnets built into the insulating block. If a permanent magnet or other magnetic body comes near the Relay, magnetic interference will occur with the built-in permanent magnet and the contact switching capacity will be decreased. Models for AC loads do not contain a permanent magnet. When mounting a P7MF-06(-D) Front-mounting Socket to a DIN Track, attach PFP-M End Plates on both sides of the Socket to prevent it from moving. Gang Mounting Conditions for mounting multiple MKS-X relays on the same DIN rail. * Gang mounting of the Front-Mounting Sockets is not possible if the contact carry current exceeds 10A.Provide space on both the right and left sides of the Sockets. The mounting pitch is given in the following diagram. Wiring The contact terminals on Models for DC Loads (i.e., models with “X” in the model number) have polarity. Wiring with incorrect polarity may result in inability to turn OFF the Relay or loss of functionality. Be sure to check plarity when wiring DC coil MKS-X relays with built-in operation indicators. Operating Environment Do not use the Relay in environments with combustible gas. Doing so may result in explosion due to arcing. Storage Models for DC Loads (i.e., models with “X” in the model number) are magnetized because they have a built-in magnet to deflect and extinguish the arc. Do not install the Relay near IC cards or other items that may be adversely affected by magnetism. Usage Use the Relay mounted in the P7M-06P or P7MF-06(-D) Socket. Test Button Turn OFF the power supply before operating the test button. Always return the test button to the original position after you use it. Do not use the test button as a switch. The durability of the test button is 100 operations minimum. The circuit can be checked using either of two modes. Test Button Applications Example: Checking operation of Relays and sequence circuits. Socket Relay Rated current of Relay Back-Connecting Socket Front-Connecting Socket Models for DC Loads 10A ❍❍ Models for AC Loads 15A ❍ * 0 10 20 30 40 50 Applied current (A) Mounting interval (mm) Mounting interval Test Button DC specification: Blue AC specification: Red Normal Mode 1 (momentary) Press the button for operation. (No tool is required.) Mode 2 (locked) Lock the contacts by pressing down on the button and turning it.
10 General Purpose Power Relays MKS-X
General Purpose Power Relays MKS-X 11 Omron Electronic Components, LLC Terms and Conditions of Sales 1. Definitions : The words used herein are defined as follows. (a) Terms: These terms and conditions (b) Seller: Omron Electronic Com ponents LLC and its subsidiaries (c) Buyer: The buyer of Products, including any end user in section III through VI (d) Products: Products and/or services of Seller (e) Including: Including without limitation 2. Offer; Acceptance: These Terms are deemed part of all quotations, acknowledgments, invoices, purchase orders and other documents, whether electronic or in writing, relating to the sale of Products by Seller. Seller hereby objects to any Terms proposed in Buyer's purchase order or other documents which are inconsistent with, or in addition to, these Terms. 3. Distributor : Any distributor shall inform its customer of the contents after and including section III of these Terms. 1. Prices; Payment : All prices stated are current, subject to change without notice by Seller. Buyer agrees to pay the price in effect at the time the purchase order is accepted by Seller. Payments for Products received are due net 30 days unless otherwise stated in the invoice. Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. 2. Discounts : Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (a) the invoice is paid according to Seller's payment terms and (b) Buyer has no past due amounts owing to Seller. 3. Interest : Seller, at its option, may charge Buyer 1.5% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms. 4. Orders : Seller will accept no order less than 200 U.S. dollars net billing. 5. Currencies : If the prices quoted herein are in a currency other than U.S. dollars, Buyer shall make remittance to Seller at the then current exchange rate most favorable to Seller; provided that if remittance is not made when due, Buyer will convert the amount to U.S. dollars at the then current exchange rate most favorable to Seller available during the period between the due date and the date remittance is actually made. 6. Governmental Approvals : Buyer shall be responsible for all costs involved in obtaining any government approvals regarding the importation or sale of the Products. 7. Taxes : All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Seller or required to be collected directly or indirectly by Seller for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Seller. 8. Financial : If the financial position of Buyer at any time becomes unsatisfactory to Seller, Seller reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Seller may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts. 9. Cancellation; Etc: Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Seller fully against all costs or expenses arising in connection therewith. 10. Force Majeure : Seller shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority. 11. Shipping; Delivery: Unless otherwise expressly agreed in writing by Seller: (a) All sales and shipments of Products sh all be FOB shipping point (unless otherwise stated in writing by Seller), at which point title to and all risk of loss of the Products shall pass from Seller to Buyer, provided that Seller shall retain a security interest in the Products until the full purchase price is paid by Buyer; (b) Delivery and shipping dates are estimates only; and (c) Seller will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions. 12. Claims: Any claim by Buyer against Seller for shortage or damage to the Products occurring before delivery to the carrier or any claim related to pricing or other charges must be presented in detail in writing to Seller within 30 days of receipt of shipment. 1. Suitability: IT IS THE BUYER’S SOLE RESPOINSIBILITY TO ENSURE THAT ANY OMRON PRODUCT IS FIT AND SUFFICIENT FOR USE IN A MOTORIZED VEHICLE APPLICATION. BUYER SHALL BE SOLELY RESPONSIBLE FOR DETERMINING APPROPRIATENESS OF THE PARTICULAR PRODUCT WITH RESPECT TO THE BUYER’S APPLICATION INCLUDING (A) ELECTRICAL OR ELECTRONIC COMPONENTS, (B) CIRCUITS, (C) SYSTEM ASSEMBLIES, (D) END PRODUCT, (E) SYSTEM, (F) MATERIALS OR SUBSTANCES OR (G) OPERATING ENVIRONMENT. Buyer acknowledges that it alone has determined that the Products will meet their requirements of the intended use in all cases. Buyer must know and observe all prohibitions of use applicable to the Product/s. 2. Use with Attention: The followings are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible use of any Product, nor to imply that any use listed may be suitable for any Product: (a) Outdoor use, use involving potential chemical contamination or electrical interference. (b) Use in consumer Products or any use in significant quantities. (c) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. (d) Systems, machines, and equipment that c ould present a risk to life or property. 3. Prohibited Use: NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. 4. Motorized Vehicle Application: USE OF ANY PRODUCT/S FOR A MOTORIZED VEHICLE APPLICATION MUST BE EXPRESSLY STATED IN THE SPECIFICATION BY SELLER. 5. Programmable Products: Seller shall not be responsible for the Buyer's programming of a programmable Product. 1. Warranty : Seller's exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Seller (or such other period expressed in writing by Seller). SELLER MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT ALL OTHER WARRANTIES, NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. 2. Buyer Remedy : Seller's sole obligation hereunder shall be to replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product or, at Seller's election, to repay or credit Buyer an amount equal to the purchase price of the Product; provided that there shall be no liability for Seller or its affiliates unless Seller's analysis confirms that the Products were correctly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Seller before shipment. 3. Limitation on Liability : SELLER AND ITS AFFILIATES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. FURTHER, IN NO EVENT SHALL LIABILITY OF SELLER OR ITS AFFILITATES EXCEED THE INDIVIDUAL PRICE OF THE PRODUCT ON WHICH LIABILITY IS ASSERTED. 4. Indemnities : Buyer shall indemnify and hold harmless Seller, its affiliates and its employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Seller is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. 1. Intellectual Property : The intellectual property embodied in the Products is the exclusive property of Seller and its affiliates and Buyer shall not attempt to duplicate it in any way without the written permission of Seller. Buyer (at its own expense) shall indemnify and hold harmless Seller and defend or settle any action brought against Seller to the extent that it is based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party. 2. Property; Confidentiality : Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Seller. All information and materials supplied by Seller to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party. 3. Performance Data : Performance data is provided as a guide in determining suitability and does not constitute a warranty. It may represent the result of Seller's test conditions, and the users must correlate it to actual application requirements. 4. Change In Specifications : Product specifications and descriptions may be changed at any time based on improvements or other reasons. It is Seller’s practice to change part numbers when published ratings or features are changed, or when significant engineering changes are made. However, some specifications of the Product may be changed without any notice. 5. Errors And Omissions : The information on Seller’s website or in other documentation has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 6. Export Controls : Buyer shall comply with all applicable laws, regulations and licenses regarding (a) export of the Products or information provided by Seller; (b) sale of Products to forbidden or other proscribed persons or organizations; (c) disclosure to non- citizens of regulated technology or information. 1. Waiver : No failure or delay by Seller in exercising any right and no course of dealing between Buyer and Seller shall operate as a waiver of rights by Seller. 2. Assignment : Buyer may not assign its rights hereunder without Seller's written consent. 3. Law : These Terms are governed by Illinois law (without regard to conflict of laws). Federal and state courts in Cook County, Illinois have exclusive jurisdiction for any dispute hereunder. 4. Amendment : These Terms constitute the entire agreement between Buyer and Seller relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. 5. Severability : If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. I. GENERAL II. SALES III. PRECAUTIONS IV. WARRANTY AND LIMITATION V. INFORMATION; ETC. VI. MISCELLANEOUS
12 General Purpose Power Relays MKS-X
Certain Precautions on Specifications and Use 1. Suitability for Use . Seller shall not be responsible for conformity with any stan- dards, codes or regulations which apply to the combination of the Product in Buyer's application or use of the Product. At Buyer's request, Seller will pro- vide applicable third party certification documents identifying ratings and limi- tations of use which apply to the Produc t. This information by itself is not sufficient for a complete determination of the suitability of the Product in com- bination with the end product, machine, sy stem, or other application or use. Buyer shall be solely responsible for determining appropriateness of the par- ticular Product with respect to Buyer' s application, product or system. Buyer shall take application responsibility in all cases but the following is a non- exhaustive list of applications for which particular attention must be given: (i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document. (ii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. (iii) Use in consumer products or any use in significant quantities. (iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERL Y RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. 2. Programmable Products . Seller shall not be respons ible for the user's pro- gramming of a programmable product, or any consequence thereof. 3. Performance Data . Performance data given in this publication is provided as a guide for the user in determining suitability and does not constitute a war- ranty. It may represent the result of Seller's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to Seller's Warranty and Limitations of Liability. 4. Change in Specifications . Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our prac- tice to change part numbers when publi shed ratings or features are changed, or when significant construction changes are made. However, some specifica- tions of the Product may be changed without any notice. When in doubt, spe- cial part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Seller representative at any time to confirm actual specifications of purchased Product. 5. Errors and Omissions . The information in this publication has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors, or omissions. 6. RoHS Compliance . Where indicated, our products currently comply, to the best of our knowledge as of the date of this publication, with the requirements of the European Union's Directive on the Restriction of certain Hazardous Substances ("RoHS"), although the requirements of RoHS do not take effect until July 2006. These requirements may be subject to change. Please consult our website for current information. OMRON ON-LINE Global - http://www.omron.com USA - http://www.components.omron.com Cat. No. J175-E-02 Printed in USA OMRON ELECTRONIC COMPONENTS LLC 55 E. Commerce Drive, Suite B Schaumburg, IL 60173 847-882-2288 09/09 Specifications subject to change without notice Complete “Terms and Conditions of Sale” for product purchase and use are on Omron’s website at http://www.components.omron.com – under the “About Us” tab, in the Legal Matters section. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.