7506701 TURCK | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 2
Technical content
Edition • 2020-01-31T12:14:12+01:00 ■ Intrinsically safe input circuits EEx ia ■ Application area acc. to ATEX: II (1) GD ■ Input circuit: 0/2 …10 VDC ■ Output circuit: 0/2…10 VDC, intrinsical- ly-safe ■ Galvanic separation of input circuits, output circuits and power supply
Edition • 2020-01-31T12:14:12+01:00 Type designation MK35-11EX0-LU/24VDC Ident-No. 7506701 Operating voltage range 19…29 VDC Input circuits 0/2 …10 VDC Voltage input VDC Voltage input 0/2…10 VDC Input resistance (voltage) ï 50000 kò Output circuits intrinsically-safe acc.to EN 50020, 1 x 0/2…10 VDC Galvanic isolation input circuit to output circuit and supply voltage for 250Veff; test voltage 4 kVeff Important note For Ex-applications the values specified in the corre- sponding Ex certificates (ATEX, IECEx, UL, etc.) ap- ply. Ex approval acc. to conformity certificate TÜV 01 ATEX 1659 Application area II (1) GD Ignition protection category [EEx ia] IIC Protection class IP20 Storage temperature -40…+80 °C Dimensions 89 x 18 x 70 mm Weight 87 g Mounting instructions DIN rail (NS35) or panel Housing material Polycarbonate/ABS Electrical connection 4 × 2-pin flat terminals with self-lifting pressure plates Terminal cross-section 1 x 2.5 mm / 2 x 1.5 mm Dimensions