METSEION7413 SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

PowerLogic ION7410 LV DC - DIN rail mount - utility meter base Product availability : Non-Stock - Not normally stocked in distribution facility Price** : 5,101.00 USD Main Range PowerLogic Product name PowerLogic ION7400 Device short name ION7413 Product or component type Power meter Complementary Power quality analysis EN 50160 2010 compliance report IEEE 519 2014 compliance report IEC 61000-4-30 class S power quality measurement up to the 63rd harmonic harmonic distortion waveform capture voltage sag and swell detection programmablity (logic and math functions) IEC 62586 power quality monitoring IEC 61000-4-15 flicker disturbance direction detection Device application WAGES metering Power monitoring Data aggregation Revenue billing Type of measurement Current Voltage Frequency Active and reactive power total Apparent power total Power factor total Active and reactive power per phase, rms Apparent power per phase, rms Power factor per phase, rms Active and reactive energy Apparent energy Supply voltage 20...60 V DC +/- 10 % Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications May 21, 2020

Power consumption in W 17 W Display type Without display Sampling rate 256 samples/cycle Measurement current 50…10000 mA Analogue input type voltage 5 MOhm) current 0.3 MOhm) Measurement voltage 57…400 V AC 42...69 Hz between phase and neutral 100…690 V AC 42...69 Hz between phases Frequency measurement range 42…69 Hz Number of inputs 3 digital 30 V AC 3 digital 60 V DC Measurement accuracy Current +/- 0.1 % Voltage +/- 0.1 % Active energy +/- 0.2 % Accuracy class Class 0.2S active energy IEC 62053-22 Class 0.2 active energy ANSI C12.20 Class 0.2 active power IEC 61557-12 Class 0.5S reactive energy IEC 62053-24 Class 0.5 power factor IEC 61557-12 Class 0.2 voltage IEC 61557-12 Class 0.2 current IEC 61557-12 Class 0.2 frequency IEC 61557-12 Class 0.2 active energy IEC 61557-12 Number of outputs 1 pulse Information displayed Voltage Current Frequency Power Energy consumption Harmonic distortion Communication port protocol Modbus RTU 115 kbauds - 2-wire ION 115 kbauds - 2-wire DNP3 IEC 61850 Modbus TCP/IP Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s RSTP 801.1d 2004 DLMS Communication port support Ethernet Screw terminal block RS485 Mini B USB USB Communication network type IPv6 (internet protocol) Data recording Sequence of event recording Trending/forecasting Harmonics logs Time stamping GPS synchronisation Waveform logs Min/max of instantaneous values Sag and swell logs Data logs Event logs Alarm logs Memory capacity 512 MB Web services Customizable home page File upload/download via FTP File upload/download via SFTP Web server Alarm notification by e-mail

Viewing of captured waveform (FTP) Viewing of captured waveform (web) HTTPS server Communication service NTP time synchronization SMTP e-mail notification RSTP support DHCP SNMP PTP time synchronization Cybersecurity Enable/disable communication ports Robust security logs Port hardening Password protection Syslog protocol support Mounting mode Clip-on Mounting support DIN rail Type of installation Indoor installation Installation category III Safety Construction III, 400…690 V IEC 61010-1:ed. 3 III, 400…690 V EN 61010-1:ed. 3 III, 347…600 V UL 61010-1:ed. 3 III, 347…600 V CSA C22.2 No 61010-1:ed. 3 Standards IEC 61326-1 IEC 62053-22 IEC 62053-24 IEC 62052-11 IEC 61557-12 IEEE 1588 IEC 62586 Product certifications CE CULus N998 China RoHS Width 3.56 in (90.5 mm) Depth 3.57 in (90.8 mm) Height 3.56 in (90.5 mm) Net weight 18.62 oz (528 g) Environment Electromagnetic compatibility Electrostatic discharge IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test IEC 61000-4-3 Electrical fast transient/burst immunity test IEC 61000-4-4 Surge immunity test IEC 61000-4-5 Conducted RF disturbances IEC 61000-4-6 Magnetic field at power frequency IEC 61000-4-8 Voltage dips and interruptions immunity test IEC 61000-4-11 Immunity to impulse waves IEC 61000-4-12 Conducted and radiated emissions EN 55022 Conducted and radiated emissions EN 55011 Conducted and radiated emissions FCC part 15 Conducted and radiated emissions ICES-003 Conducted RF disturbances 2...150 Hz) CLC/TR 50579 Surge withstand IEEE C37.90.1 IP degree of protection IP30 IEC 60529 Relative humidity 5…95 % Ambient air temperature for operation -13…158 °F (-25…70 °C) Ambient air temperature for storage -40…185 °F (-40…85 °C) Operating altitude 9842.52 ft (3000 m) Ordering and shipping details Category 09753 - POWERLOGIC ION 7400 HARDWARE Discount Schedule PM1 Returnability No

Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Dichloromethane (Methylene chloride) and Bisphenol A (BPA) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov REACh free of SVHC Yes EU RoHS Directive Compliant EU RoHS Declaration Toxic heavy metal free Yes Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Pro-active China RoHS declaration (out of China RoHS legal scope) Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.