Technical content

The M-Series is a low cost, miniature hydraulic/magnetic circuit breakers ideally designed for demanding applications requiring space saving features, aesthetics and snap-in front panel mounting. Its newest design features a compact, space saving, vertically mounted parallel pole confi guration, which is UL489A listed up to 50 amps and is well suited for telecommunication equipment fi tting in one rack unit. Furthermore, it features two uniquely designed terminals that provide the highest level of balanced circuit protection. In addition, these circuit breakers feature various styling options allowing for design fl exibility. They are available in choices of rocker actuator styles and colors, including paddle and baton style handle actuators, push-to-reset and push-pull pushbutton actuators, Visi-Rocker two color actuators as well as non-illuminated or illuminated rocker versions with LED or neon bulbs. The exclusive Rockerguard bezel helps prevent inadvertent actuation and wiping contact design insures long-term reliability. The M-Series circuit breakers are available in 1 & 2 poles or parallel poles, 0.02 to 50 amps, up to 250VAC or 80VDC with choices of time delays, terminals, panel hardware, actuator styles, colors, and imprinting. Features: w Parallel pole confi guration well suited for One Rack Unit w Meets CSA Standard 22.2 No. 100 for Generator & Welder markets w MIL-PRF-55629 and MIL STD 202 compliant w MIL-PRF-39019F ingress protection w Sealed toggle actuator w Compact design Applications: w Communication equipment w Vehicles w Marine w Generators w Power supplies w Medical Equipment M-Series Circuit Breaker Carling Technologies, Inc.

60 Johnson Avenue • Plainville, CT 06062-1177

Phone: (860) 793-9281 • Fax: (860) 793-9231 Email: sales@carlingtech.com • www.carlingtech.com

60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231

Email: sales @carlingtech.com • www.carlingtech.com 2 | CURRENT TOLERANCE (AMPS) (%) 0.10 - 20.0 ±25 20.1 - 50.0 ±35 M-Series Circuit Breaker - General Specifications Environmental Physical MechanicalElectrical Designed in accordance with requirements of specification MIL PRF-55629 & MIL-STD-202G as follows: *Manufacturer reserves the right to change product specification without prior notice. RESISTANCE PER POLE VALUES from Line to Load Terminals (Values Based on Series Trip Circuit Breaker) Maximum Voltage 125/250 VAC 50/60 Hz, 80 VDC (See Rating Tables.) Current Ratings Standard current coils: 0.100, in 1 amp increments, 18.0, 20.0, 25.0, 30.0. Other ratings available - see Ordering Scheme. Auxiliary Switch Rating SPDT; 7A 250VAC, 7A (Res) 28VDC, 4A (Ind.) 28VDC, 0.25A 80VDC (Res) (silver contacts), 0.1A 125VAC (gold contacts). Insulation Resistance Minimum of 100 Megohms at 500 VDC. Dielectric Strength UL, CSA 1500V, 50/60 Hz for one minute between all electrically isolated terminals. M-Series Circuit Breakers comply with the 8mm spacing and 3750 V 50/60Hz dielectric requirements from hazardous voltage to operator accessible surfaces, per Publications IEC 380, 435, 950, EN 60950 and VDE 0805. Resistance, Impedance Values from Line to Load Terminal - based on Series Trip Circuit Breaker. Endurance 10,000 ON-OFF operations @ 6 per minute with rated Current and Voltage. Trip Free All M-Series Circuit Breakers will trip on overload, even when actuator is forcibly held in the ON position. Trip Indication The actuator moves positively to the OFF position when an overload causes the circuit breaker to trip. Shock Withstands 100 Gs, 6ms, sawtooth while carrying rated current per Method 213, Cond. I. Instantaneous curves tested at 80% of rated current. Vibration Withstands 0.060” excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current per Method 204C, Test Condition A. Instantaneous curves tested at 80% of rated current. Moisture Resistance Method 106D, i.e., ten 24-hour cycles @ + 25°C to +65°C, 80- 98% RH. Salt Spray Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs). Thermal Shock Method 107D, Condition A (Five cycles @ -55°C to +25°C to +85°C to +25°C). Operating Temperature -40° C to +85° C Chemical Resistance Only the outside surfaces of the case and the handles may be cleaned with detergents or alcohol. Organic (hydrocarbon based) solvents are not recommended because they attack plastics. Caution should be taken when solvents are used to clean and remove flux from terminals. Lubricants should not be introduced into the handle/ bushing openings Number of Poles 1 or 2 Internal Circuit Configs. Series with or without Auxiliary Switch. Switch Only with or without Auxiliary Switch. Weight Approximately 30 grams/pole (Approximately 1.07 ounces/pole) Standard Colors See Ordering Scheme.a Pulse Tolerance Curves

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 3 M-Series Circuit Breaker - General Specifications Electrical Tables Table A: Lists UL Recognized and CSA Accepted configurations & performance capabilities as a Component Supplementary Protector. Table B: Lists UL Recognized,CSA Accepted and TUV and VDE Certified configurations and performance capabilities as a Component Supplementary Protector. Table B Notes:

1 Polarity Sensitive

2 Available only with Special Catalog Number. Consult Factory.

3 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 30 Amps maximum

4 TUV only, not VDE

5 Requires backup protection with a thermal magnetic circuit breaker rated 32 amps and having a Type C trip characteristic per EN60898/DIN VDE 0641 (C32A) for ratings greater than 15amps, and a thermal magnetic circuit breaker rated 16 amps and having a Type C trip characteristic per EN60898/DIN VDE 0641 (C16A) for ratings 15 amps and less Table A Notes: 2 Available only with Special Catalog Number. Consult Factory.

4 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 60 Amps maximum

Email: sales @carlingtech.com • www.carlingtech.com 4 | M-SERIES TABLE C: UL489A Listed WITHOUT BACKUP FUSE UL489A

80 DC 31-50 2 600

  1. Available only with Special Catalog Number. Consult Factory. POLES BREAKING INTERRUPTING CAPACITY (AMPS) M-SERIES TABLE D: Parallel Pole Construction UL489A Listed (COMMUNICATIONS EQUIPMENT - POLARITY SENSITIVE) SERIES CIRCUIT CONFIGURATION MAX. RATING FREQUENCY VOLTAGE CURRENT RATING GENERAL PURPOSE AMPS M-Series Circuit Breaker - General Specifications Electrical Tables Table C: Lists UL489A Listed and TUV Certified configurations and performance capabilities for use in Communications Equipment. Table D: Lists UL489A Listed configurations and performance capabilities for use in Communications Equipment. Table C Notes:

1 Available only with Special Caralog Number

Table D Notes: Component Recognition Program as Protectors, Supplementary (Guide CCN/QVNU2, File E75596) Communications Equipment (Guide CCN/DITT, File E189195) Component Supplementary Protector (Class 3215 30, File 047848 0 000) CSA Standard C22.2 No. 235 EN60934, VDE 0642 under File 10537 EN60934, under License No. R9671109

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 5 M-Series Parallel Pole Rocker - Ordering Scheme

6 CURRENT RATING (AMPERES)

631 31.000 635 35.000 640 40.000 645 45.000 650 50.000 CODE AMPERES Series Actuator Poles Current Rating Terminal Illumination Agency Approval Circuit Frequency & Delay M E P A5 22 1 TBD2 650

1 SERIES

M

7 TERMINAL

5 10-32 Screw (Bus Type)

3 POLES

2 Two

4 CIRCUIT/AUXILIARY SWITCH2

P Series Trip Current (Parallel Pole) with Auxiliary Switch, Silver Contacts Q Series Trip Current (Parallel Pole) .110 x 0.20 Q.C with Auxiliary Switch, Gold Contacts R Series Trip Current (Parallel Pole) .110 x 0.20 Q.C

5 FREQUENCY & TIME DELAY

12 AGENCY APPROVAL

11 BEZEL COLOR

A White without Rockerguard B Black without Rockerguard G Gray without Rockerguard

1 White with Rockerguard

2 Black with Rockerguard

7 Gray with Rockerguard

Color & Legend Legend Bezel Color

8 ILLUMINATION

9 ACTUATOR COLOR & LEGEND

1 White Black

2 Black White

3 Red White

4 Green White

5 Blue White

6 Yellow Black

7 Gray Black

8 Orange Black

10 LEGEND

2 ON - OFF Vertical

3 ON - OFF Horizontal

6 Dual Vertical

7 Dual Horizontal

2 ACTUATOR

Single Color Rocker Two Color Visi-Rocker Single Color Translucent Rocker A Angled D Indicate ON F Angled B Flat E Indicate OFF G Flat Notes:

1 Reminder of Rocker same color as Visi

2 Aux Switch only available with screw terminals

Email: sales @carlingtech.com • www.carlingtech.com 6 | M-Series Parallel Pole - Handle / Push Button - Ordering Scheme 631 31.000 635 35.000 640 40.000 645 45.000 650 50.000 CODE AMPERES M 5 10-32 Screw (Bus Type)

4 CIRCUIT/AUXILIARY SWITCH1

P Series Trip Current (Parallel Pole) with Auxiliary Switch, Silver Contacts Q Series Trip Current (Parallel Pole) .110 x 0.20 Q.C with Auxiliary Switch, Gold Contacts R Series Trip Current (Parallel Pole) .110 x 0.20 Q.C

11 BUSHING COLOR

9 FRONT PANEL HARDWARE

B Knurled Nut, Bright Nickel C Knurled Nut, Bright Nickel w/Locking Ring D Knurled Nut, Black E Knurled Nut, Black w/Locking Ring F Panel Dress, Bright Nickel G Panel Dress, Bright Nickel w/Locking Ring H Panel Dress, Black J Panel Dress, Black w/Locking Ring Push Button

1 No outer Panel Hardware

2 Knurled Nut, Bright Nickel

10 LEGEND PLATE / BUTTON MARKING

Handle Actuator Legend Plate B ON - OFF Vertical C ON - OFF Horizontal Push-Pull Actuator Legend Plate

2 Rated Amps Horizontal

3 Rated Amps Line Side Down

4 Rated Amps Line Side Up

8 ACTUATOR COLOR & LEGEND

1 White

2 Black

3 Red

4 Green

5 Blue

6 Yellow

7 Gray

8 Orange

Notes:

1 Aux Switch only available with screw terminals

& Delay M M P 15 B2 B TBD2 650 Front Panel Hardware Legend Plate/ Marking Brushing Color

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 7 1.304 [33.12] 1.125 [28.58] .970 [24.64] 1.375 [34.93] 1.125 [28.58] 1.560 [39.62] .370 [9.40] MAX. INDICATE "OFF" (VISI-OFF) & SINGLE COLOR ON OFF .400 [10.16] ON OFF ±.020 ±.508 1.050 [26.67] ON PANEL CUT - OUT DETAIL (ROCKER) .125 [3.18] PANEL THICKNESS .093 [2.36] .062 [1.57] OFF 1.139 [33.76] DOUBLE POLE DIM. A ±.005 ±.13 LINE DIM. A 1.460 [37.08] +.005 +.13 -.000 -.00 1.420 [36.07] 1.385 [35.18] ROCKERGUARD CONFIGURATION .675 [17.14] .100 [2.54] LOAD ±.020 ±.508 .305 [7.75] ±.020 ±.508 PUSH-IN STUD 1.000 [25.4] .750 [19.05] .100 [2.54] 1.394 [35.41] .393 [9.97] 1.000 [25.4] .154 [3.91] ROCKER ACTUATOR DETAIL 1.530 [38.86] INDICATE "ON" (VISI-ON) .652 [16.56] .838 [21.29] PARALLEL POLE TERMINAL OPTIONS .912 [23.16] 10-32 SCREW W/ BUS BAR M SERIES PARALLEL POLE FORM & FIT DIAGRAMS NOTES: 1. ALL DIMENSIONS ARE IN INCHES [MILLIMETERS]. 2. TOLERANCE ±.010 [.25] UNLESS OTHERWISE SPECIFIED. 3. DIMENSIONS APPLY TO BOTH ROCKER STYLES. 4. I-O, ON-OFF OR DUAL LEGENDS AVAILABLE FOR VERTICAL OR HORIZONTAL MOUNTING. 5. NOTICE THAT CIRCUIT BREAKER LINE AND LOAD TERMINAL ORIENTATION ON INDICATE "OFF" IS OPPOSITE THAT OF INDICATE "ON". ME 5/10/12 LINE DR BY TITLE .625 [15.88] LOAD LOAD DWG NO SHT OF CLA-8121 APVD BY 1 3 REV A LINE REVISIONS RELEASED PER ECO 16976 LET A DATE 5-10-12 M-Series Parallel Pole - Form & Fit Drawings Notes: 1 ALL DIMENSIONS ARE IN INCHES [MILLIMETERS]. 2 TOLERANCE ±.010 [.25] UNLESS OTHERWISE SPECIFIED. 3 DIMENSIONS APPLY TO BOTH ROCKER STYLES. 4 I-O, ON-OFF OR DUAL LEGENDS AVAILABLE FOR VERTICAL OR HORIZONTAL MOUNTING. 5 NOTICE THAT CIRCUIT BREAKER LINE AND LOAD TERMINALORIENTATION ON INDICATE “OFF” IS OPPOSITE THAT OF INDICATE “ON”.

Email: sales @carlingtech.com • www.carlingtech.com 8 | .105 [2.67] .125 [3.18] HEX NUT .625 [15.88] KNURLED NUT .683 DIA [Ø17.27] PANEL DRESS NUT LEGEND PLATES .680 DIA [Ø17.27] .632 DIA [Ø16.05] .680 DIA [Ø17.27] .180 [4.57] .340 [8.64] B 0FF .025 [.64] LEGEND CODE: PANEL HARDWARE 1.025 [26.04] O N C O F F .125 [3.18] .470 [11.94]FLAT .500 [12.70] .222 [5.64] .500 DIA [Ø12.70] WITHOUT LOCKING RING .500 DIA [Ø12.70] WITH LOCKING RING .355 [9.02] ±.005 [±.13] +.010 -.000 +.25 -.000 +.010 -.000 MOUNTING DETAILS +.25 -.000 ±.030 ±.76 +.25 -.000 +.010 -.000 PADDLE ACTUATOR STYLE 1.395 12° 1/2-32 THD. 12° ON OFF M SERIES PARALLEL POLE FORM & FIT DIAGRAMS NOTES: 1. ALL DIMENSIONS ARE IN INCHES [MILLIMETERS]. 2. TOLERANCE ±.010 [.25] UNLESS OTHERWISE SPECIFIED. 3. DIMENSIONS APPLY TO BOTH ROCKER STYLES. 4. I-O, ON-OFF OR DUAL LEGENDS AVAILABLE FOR VERTICAL OR HORIZONTAL MOUNTING. 5. NOTICE THAT CIRCUIT BREAKER LINE AND LOAD TERMINAL ORIENTATION ON INDICATE "OFF" IS OPPOSITE THAT OF INDICATE "ON". ME 5/10/12 .031 [.79] LOCKING RING DR BY TITLE .342 [8.69] 2 3 APVD BY DWG NO SHT OF CLA-8121 REV A REVISIONS RELEASED PER ECO 16976 LET A DATE 5-10-12 .435 [11.05] DIA PANEL DRESS NUT PANEL HARDWARE HEX NUT .156 [3.56] .534 [13.56] 20 20 LINE MARKING CODE: BUTTON MARKING ORIENTATION .110QC AUXILIARY SWITCH TERMINALS LINE 3 4 LINE SNAP-IN BUSHING .162 [4.11] .625 [15.87] DIA MOUNTING DETAILS ±.002 ±.05 .280 [7.11] ON ±.030 ±.76 PUSH-PULL, PUSH TO RESET .375 [9.53] DIA .544[13.82] .494 [12.55] ±.030 ±.76 PUSH-PULL ACTUATOR STYLE ±.030 ±.76 FLAT 1.484 3/8" 8-32 THD. ACTUATOR COLOR VISIBLE IN OFF POSITION ONLY NOTES: 1. ALL DIMENSIONS ARE IN INCHES [MILLIMETERS]. 2. TOLERANCE ±.010 [.25] UNLESS OTHERWISE SPECIFIED. 3. DIMENSIONS APPLY TO BOTH ROCKER STYLES. 4. I-O, ON-OFF OR DUAL LEGENDS AVAILABLE FOR VERTICAL OR HORIZONTAL MOUNTING. 5. NOTICE THAT CIRCUIT BREAKER LINE AND LOAD TERMINAL ORIENTATION ON INDICATE "OFF" IS OPPOSITE THAT OF INDICATE "ON". ME 5/10/12 DR BY TITLE 3 3 M SERIES PARALLEL POLE FORM & FIT DIAGRAMS APVD BY DWG NO SHT OF CLA-8121 REV A .098 [2.49] .078 [1.98] REVISIONS RELEASED PER ECO 16976 LET A DATE 5-10-12 +.010 -.000 +.25 -.00 M-Series Parallel Pole - Form & Fit Drawings Notes: 1 ALL DIMENSIONS ARE IN INCHES [MILLIMETERS]. 2 TOLERANCE ±.010 [.25] UNLESS OTHERWISE SPECIFIED. 3 DIMENSIONS APPLY TO BOTH ROCKER STYLES. 4 I-O, ON-OFF OR DUAL LEGENDS AVAILABLE FOR VERTICAL OR HORIZONTAL MOUNTING. 5 NOTICE THAT CIRCUIT BREAKER LINE AND LOAD TERMINALORIENTATION ON INDICATE “OFF” IS OPPOSITE THAT OF INDICATE “ON”.

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 9 M-Series Handle/Pushbutton UL Recognized - Ordering Scheme

6 CURRENT RATING (AMPERES)8

020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 090 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 CODE AMPERES Series Actuator Poles Current Rating Terminal Actuator Color Agency Approval Circuit Frequency & Delay M M B 11 B1 B BC34 260 M

7 TERMINAL8

1 Push-On 0.250 Tab (Q.C.)

210 Screw 8-32 w/upturned lugs

310 Screw 8-32 (Bus Type)

1 One 2 Two

4 CIRCUIT2

A Switch Only (no coil) , Maintained Contacts B Series Trip (Current) with Auxiliary Switch, Silver Contacts Terminal Type: M Switch Only, (Current) Aux Switch .110 QC x .020 QC P3 Switch Only, Maintained Contacts .060 Dia, Round Solder Turret Q3,4 Switch Only, Maintained Contacts .058 Dia, Round Q.C. R3,13 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C. S3 Series Trip (Current) .060 Dia, Round Solder Turret T3,4 Series Trip (Current) .058 Dia, Round Q.C. U3,13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. with Auxiliary Switch, Gold Contacts 23,4 Switch Only, Maintained Contacts .058 Dia, Round Q.C. 33,13 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C. 43,4 Series Trip (Current) .058 Dia, Round Q.C. 53,13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. 9 Series Trip (Current) .110 QC x .020 QC

5 FREQUENCY & DELAY

03 DC 50/60Hz, Switch Only

10 DC Instantaneous

12 DC Short

14 DC Medium

30 DC, 50/60Hz Instantaneous

32 DC, 50/60Hz Short

34 DC, 50/60Hz Medium

62 50/60Hz Short, Hi-Inrush 64 50/60Hz Medium, Hi-Inrush

72 DC, Short,Hi-Inrush

74 DC,Medium, Hi-Inrush

92 DC, 50/60Hz Short, Hi-Inrush

94 DC, 50/60Hz Medium,

12 AGENCY APPROVAL8

C D E UL Recognized & CSA Accepted VDE Certified, UL Recognized & CSA Accepted TUV Certified, UL Recognized & CSA Accepted

11 BUSHING COLOR7

9 FRONT PANEL HARDWARE6

Bright nickel w/ locking ring Black Black w/ locking ring Panel Dress Nut Bright nickel Bright nickel w/ locking ring Black Black w/ locking ring Push-Button Handle A B C D E F G H J Handle Actuator Legend Plate (Actuator Styles M & N) A No Legend Plate B ON - OFF Vertical C ON - OFF Horizontal D I - O Vertical E I - O Horizontal Push-Pull Actuator Button Cap (Actuator Styles T & V)

1 No Marking

Push-to-Reset Actuator Button (Actuator Styles U& W)

2 ACTUATOR1

Push Button w/ Snap-In Mounting V Push-Pull N Baton U Push To Reset W Push To Reset Notes: 1 One actuator is located in the center of each multi-pole breaker. Actuator codes V & W limited to single pole breakers only. 2 Switch Only circuits are not available with Push-To-Reset actuators. For Switch Only circuits, select Current Coil Rating from the above chart: 3 One Auxiliary Switch is supplied per breaker. On two-pole breakers, standard Auxiliary Switch mounting is in pole one. Auxiliary Switch option limited to Series Trip and Switch Only circuits. Not available with back connect screw or push-in stud terminals. 4 Mates with AMP .058” diameter pin receptacles including 60983-1 (gold plated) and 60983-2 (tin plated). 5 Actuator color is only visible in the OFF position on Push-Pull actuators. 6 All units except snap-in mounting have one hex nut installed on bushing for use behind the panel. 7 Other colors available. Consult factory. 8 TUV and VDE Certification above 15 amps is for 2-pole only and is limited to a max. of 25 amps. Screw Terminal or Push-In Stud recommended above 20 amps. 9 30 amp rating not available with delay’s 30, 32, 34, 92 or 94. 10 Screw Terminals are VDE certified only with use of ring terminal attached to wire. 11 Terminal code A available with circuit codes A & B only. 12 Printed circuit board available with UL recognized approval only. 13 Auxiliary switch (flat Q.C.) available with UL recognized approvals only.

8 ACTUATOR COLOR & LEGEND5

A B C D E F H

Email: sales @carlingtech.com • www.carlingtech.com 10 | M-Series Handle/Pushbutton UL489A/UL Recognized – Ordering Scheme Series Actuator Poles Current Rating Terminal Actuator Color Agency Approval Circuit Frequency & Delay M M B 11 B1 B JB14 620 M

7 TERMINAL4

1 Push-On 0.250 Tab (Q.C.)

2 Screw 8-32 w/upturned lugs

3 Screw 8-32 (Bus Type)

1 One

4 CIRCUIT

B Series Trip (Current) with Auxiliary Switch, Silver Contacts Terminal Type: M Switch Only, (Current) Aux Switch .110 QC x .020 QC S2 Series Trip (Current) .060 Dia, Round Solder Turret T2,3 Series Trip (Current) .058 Dia, Round Q.C. U3,12 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. with Auxiliary Switch, Gold Contacts 42,3 Series Trip (Current) .058 Dia, Round Q.C. 53,12 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. 9 Series Trip (Current) .110 QC x .020 QC

12 AGENCY APPROVAL9

J M N T UL489A Listed, TUV Certified UL Recognized, CSA Accepted UL Recognized, TUV Certified UL489A Listed A B C D E F H Bright nickel w/ locking ring Black Black w/ locking ring Panel Dress Nut Bright nickel Bright nickel w/ locking ring Black Black w/ locking ring Push-Button Handle A B C D E F G H J Handle Actuator Legend Plate (Actuator Styles M & N) A No Legend Plate B ON - OFF Vertical C ON - OFF Horizontal D I - O Vertical E I - O Horizontal Push-Pull Actuator Button Cap (Actuator Styles T & V)

18 No Marking

Push-to-Reset Actuator Button (Actuator Styles U& W) Push Button w/ Snap-In Mounting V Push-Pull N Baton U Push To Reset W Push To Reset Notes: 1 One actuator is located in the center of each multi-pole breaker. Actuator codes V & W limited to single pole breakers only. 2 One Auxiliary Switch is supplied per breaker. On two-pole breakers, standard Auxiliary Switch mounting is in pole one. Auxiliary Switch option limited to Series Trip and Switch Only circuits. Not available with Back Connected Screw or Push-in Stud terminals. 3 Mates with AMP .058” diameter pin receptacles including 60983-1 (gold plated) and 60983-3 (tin plated). 4 Screw terminals or Push-in Stud recommended above 20 amps. 5 Actuator color is only visible in the OFF position on Push-Pull actuators. 6 All units have one hex nut installed on bushing for use behind the panel. 7 Other colors available. Consult factory. 8 Not available with UL489A Listed breakers. 9 TUV certified to 25 amps. UL Recognized, CSA Accepted and UL Listed to 30 amps. 10 Terminal code A available with circuit codes A & B only. 11 Printed circuit board available with UL recognized approval only. 12 Auxiliary switch (flat Q.C.) available with UL recognized approvals only. 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 090 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 CODE AMPERES

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 11 M-Series Handle – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.

Email: sales @carlingtech.com • www.carlingtech.com 12 | M-Series Handle – PC Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 13 M-Series Handle - Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.

Email: sales @carlingtech.com • www.carlingtech.com 14 | M-Series Pushbutton – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 15 M-Series Pushbutton – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ± 0.20 [.51] unless otherwise specified.

3 Available with Push-Pull or Push-to-Reset Actuators

Email: sales @carlingtech.com • www.carlingtech.com 16 | M-Series Push-Pull – PC Terminal Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified.

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 17 M-Series Rocker UL Recognized – Ordering Scheme Series Actuator Poles Current Rating Terminal Illumination Agency Approval Circuit Frequency & Delay M G B H1 62 C C734 620 M A Switch Only (no coil) , Maintained Contacts B Series Trip (Current) with Auxiliary Switch, Silver Contacts Terminal Type: M Switch Only, (Current) Aux Switch .110 QC x .020 QC P3 Switch Only, Maintained Contacts .060 Dia, Round Solder Turret Q3,4 Switch Only, Maintained Contacts .058 Dia, Round Q.C. R3,16 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C. S3 Series Trip (Current) .060 Dia, Round Solder Turret T3,4 Series Trip (Current) .058 Dia, Round Q.C. U3,16 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. with Auxiliary Switch, Gold Contacts 23,4 Switch Only, Maintained Contacts .058 Dia, Round Q.C. 33,16 Switch Only, Maintained Contacts .080 Dia x .020 Flat Q.C. 43,4 Series Trip (Current) .058 Dia, Round Q.C. 53,16 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. 9 Series Trip (Current) .110 QC x .020 QC 62 50/60Hz Short, Hi-Inrush 64 50/60Hz Medium, Hi-Inrush

12 AGENCY APPROVAL10

C D E UL Recognized & CSA Accepted VDE Certified, UL Recognized & CSA Accepted TUV Certified, UL Recognized & CSA Accepted

11 BEZEL COLOR / STYLE9

Color without Rockerguard with Rockerguard White A 1 Black B 2 Gray G 7 Actuator Color Legend Bezel Color

8 ROCKER ILLUMINATION

without resistor, 120VAC/250VAC LED7,8 without resistor with resistor, 4-8 VDC with resistor, 9-16 VDC Amber K L M A Neon B Red D E F Green Glow8 C Green G H J

9 ACTUATOR & LEGEND COLOR

A B C D E F Legend Black White White White White Black Black Black Legend White White White White White Black Actuator White Black Red Green Blue Yellow Gray Orange Visi & Legend (remainder of rocker same color as bezel) White Black Red Green Blue Yellow Gray Orange Actuator Clear Red Transparent Green Transparent Amber Transparent Smoke Gray Transparent White Translucent

10 LEGEND11

1 No Legend

4 I - O Vertical

5 I - O Horizontal

Notes: 1 One actuator is located in the center of each multi-pole breaker.

2 For Switch Only circuits, select Current Coil Rating from the above chart:

3 One Auxiliary Switch is supplied per breaker. On two-pole breakers, standard Auxiliary Switch mounting is in pole one. Auxiliary Switch option limited to Series Trip & Switch Only circuits, & is not available in single pole illuminated breakers, or Back Connected Screw or Push-in Stud terminals. 4 Mates with AMP .058” diameter pin receptacles: 60983-1 (gold plated) & 60983-2 (tin plated).

5 For neon bulb applications at 120VAC @ 47K, 1/4 WATT and for 250VAC applications @ 150K,

1/4 WATT, external resistors must be supplied by customer. 6 On Visi-Rocker breakers, Visi portion of rocker cannot be the same color as the bezel.

7 For LED (DC or rectified AC) applications, LED is mounted in the center of the rocker actuator with

electrical characteristics: 100 millicandela at 20mA; Maximum power dissipation = 75mW at 25°C; Maximum forward current = 25mA; Typical forward voltage = 2.1V at 20mA; Typical reverse current = 100uA at 3V. Customer supplies the proper external resistor limiting current to these values.

8 Rocker color for LED’s and green neon lamp must be clear, smoke gray, white translucent or match

color of LED or neon lamp. 9 Other colors available. Consult factory. 10 TUV 20A, VDE 15A Certified to 25 amps. UL Recognized and CSA Accepted to 30 amps. Screw Terminals or Push-in Stud recommended above 20 amps. 11 TUV or VDE Certified must have I-O or Dual Legends. Legend required on Visi-Rocker breakers. 12 30 amp rating not available with delay’s 30, 32, 34, 92 or 94. 13 Screw Terminals are VDE certified only with use of ring terminal attached to wire. 14 Terminal code A available with circuit codes A & B only. 15 Printed circuit board available with UL recognized approval only. 16 Auxiliary switch (flat Q.C.) available with UL recognized approvals only. Non-Illuminated single color A Angled B Flat Two Color Visi-Rocker D Indicate ON E Indicate OFF llluminated single color F Angled G Flat 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 090 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 CODE AMPERES 1 Push-On 0.250 Tab (Q.C.)

Email: sales @carlingtech.com • www.carlingtech.com 18 | M-Series Rocker UL489A/UL Recognized – Ordering Scheme Series Actuator Poles Current Rating Terminal Illumination Agency Approval Circuit Frequency & Delay M A B A1 61 1 J214 620 M B Series Trip (Current) with Auxiliary Switch, Silver Contacts Terminal Type: M Switch Only, (Current) Aux Switch .110 QC x .020 QC S Series Trip (Current) .060 Dia, Round Solder Turret T3 Series Trip (Current) .058 Dia, Round Q.C. U3,13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. with Auxiliary Switch, Gold Contacts 43 Series Trip (Current) .058 Dia, Round Q.C. 53,13 Series Trip, Maintained Contacts .080 Dia x .020 Flat Q.C. 9 Series Trip (Current) .110 QC x .020 QC J M N T UL489A Listed & TUV Certified UL Recognized & CSA Accepted TUV Certified, UL Recognized & CSA Accepted UL489A Listed

11 BEZEL COLOR / STYLE8

Color without Rockerguard with Rockerguard White A 1 Black B 2 Gray G 7 Actuator Color Legend Bezel Color without resistor, 120VAC/250VAC LED without resistor 5,7 with resistor, 4-8 VDC with resistor, 9-16 VDC Amber K L M A Neon B Red D E F Green Glow7 C Green G H J A B C D E F Legend Black White White White White Black Black Black Legend White White White White White Black Actuator White Black Red Green Blue Yellow Gray Orange Visi & Legend (remainder of rocker same color as bezel) White Black Red Green Blue Yellow Gray Orange Actuator Clear Red Transparent Green Transparent Amber Transparent Smoke Gray Transparent White Translucent

10 LEGEND10

1 No Legend (Single Color or Illuminated Rocker Options Only)

Notes: 1 One actuator is located in the center of each multi-pole breaker. 2 One Auxiliary Switch is supplied per breaker. Auxiliary Switch option limited to Series Trip & Switch Only circuits, and is not available in single pole illuminated breakers, or with Back Connected Screw or Push-in Stud terminals. 3 Mates with AMP .058” diameter pin receptacles: 60983-1 (gold plated) & 60983-1 (tin plated).

4 For neon bulb applications at 120VAC @ 47K, 1/4 WATT and for 250VAC applications @ 150K,

1/4 WATT, external resistors must be supplied by customer.

5 For LED (DC or rectified AC) applications, LED is mounted in the center of the rocker actuator with

electrical characteristics as follows: 100 millicandela at 20mA; Maximum power dissipation = 75mW at 25°C; Maximum forward current = 25mA; Typical forward voltage = 2.1V at 20mA; Typical reverse current = 100uA at 3V. Customer supplies the proper external resistor limiting current to these values. 6 On Visi-Rocker breakers, Visi portion of rocker cannot be the same color as the bezel.

7 Rocker color for LED’s and green neon lamp must be clear, smoke gray, white translucent or

match color of LED or neon lamp. 8 Other colors available. Consult factory. 9 TUV Certified to 25 amps. UL Recognized, CSA Accepted and UL489A Listed to 30 amps. Screw Terminals recommended above 20 amps. 10 UL489A Listed must have ON-OFF or Dual legends. TUV Certified approvals must have I - O or Dual legends. 11 Terminal code A available with circuit codes A & B only. 12 Printed circuit board available with UL recognized approval only. 13 Auxiliary switch (flat Q.C.) available with UL recognized approvals only. Non-Illuminated single color A Angled B Flat Two Color Visi-Rocker D Indicate ON E Indicate OFF llluminated single color F Angled G Flat 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 090 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 CODE AMPERES

7 TERMINAL9

1 Push-On 0.250 Tab (Q.C.)

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 19 M-Series Rocker – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Schematic shown represents current trip circuit.

Email: sales @carlingtech.com • www.carlingtech.com 20 | M-Series Rocker – Form & Fit Drawings Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal orientation on indicate OFF is opposite of indicate ON. 2 I-O, ON-OFF or dual legends available for vertical or horizontal mounting. For pole orientation with horizontal legend, rotate front view clockwise 90°. 3 All dimensions are in inches [millimeters]. 4 Tolerance ± 0.20 [.51] unless otherwise specified.

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 21 M-Series Rocker – Supplementary Diagrams

Email: sales @carlingtech.com • www.carlingtech.com 22 | M-Series Circuit Breaker - Time Delay Curve Notes: 1 Delay Curves 12,14, 22, 24, 32, 34, 62, 64, 72, 74, 92, 94: Breakers to hold 100% and must trip at 135% of rated current and greater within the time limit shown in this curve. 2 Delay Curves 10, 20, 30: Breakers to hold 100% and must trip at 150% of rated current and greater within the time limit shown in this curve. 3 All Curves: Curve data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading. Breakers are mounted in standard wall-mount position. 4 The minimum inrush pulse tolerance handling capability is 12 times the rated current on standard delays and 18 times the rated current on high inrush delays. These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse. High inrush delays should be specified for applications with high initial surge currents of short duration, such as switching power supplies, highly capacitive loads and transformer loads. Medium Medium D4 Instantaneous Short Short D2 Dual Rated AC/DC

Email: sales @carlingtech.com • www.carlingtech.com Email: sales @carlingtech.com • www.carlingtech.com | 23 * Intentionally left blank

Carling Technologies, Inc.

60 Johnson Avenue • Plainville, CT 06062

Phone: (860) 793-9281 • Fax: (860) 793-9231 Email: sales@carlingtech.com • www.carlingtech.com East Region Sales Office, CT • ersm@carlingtech.com Midwest Region Sales Office, IL • mrsm@carlingtech.com West Region Sales Office, CA • wrsm@carlingtech.com Asia-Pacific Headquarters Carling Technologies, Asia-Pacific Ltd., Kowloon, Hong Kong Int + 852-2737-2277 • Fax: Int + 852-2736-9332 Email: sales@carlingtech.com.hk Shenzhen, China • shenzhen@carlingtech.com Shanghai, China • shanghai@carlingtech.com Pune, India • india@carlingtech.com Kaohsiung, Taiwan • taiwan@carlingtech.com Yokohama, Japan • japan@carlingtech.com Europe / Middle East / Africa Headquarters Carling Technologies LTD