Features
- Offers the unique function to detect the following four major elements of a fire: - Smoke - Carbon Monoxide (CO) - Light/flame - Heat
- Supplies a separate CO detection signal.
- Presents the highest nuisance alarm immunity.
- Produces an automatic drift compensation of smoke sensor and CO cell.
- Uses only one address on the SLC.
- Includes the EasyTest CO testing capability.
- Complies with UL® Listed Standard 268 and UL® Listed Standard 2075.
- Separates the audible signal for fire or CO alarm when used with the B200S Base.
- Provides the CO cell end-of-life warning and fault. MCS-COF in a B200S Sounder Base
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60708 Rev. C page 2 of 2 www.gamewell-fci.com Specifications Physical Specifications Base Diameter: 6.875” (17.46 cm) installed in a B200S base Base Height: 3.46” (8.79 cm) installed in B200S base Shipping Weight: 4.6 oz Color: Ivory Material: Bayblend FR110 Operating Temperature Range:32° F to 100° F (0° C to 38° C) Operating Humidity Range: 15 to 90% relative humidity (non-condensing) Air Velocity: 0 to 4,000 ft/min (0 to 20 m/sec) Electrical Specifications Operating Voltage Range: 15 to 32 VDC Maximum Standby Current: 300 µA at 24 VDC (no communica- tion every 5 seconds with LED blink enabled). Maximum Alarm Current (LED on): 7.2 mA at 24 VDC Sensitivity Settings & Suggested
Applications
Level 1: 1% per foot (30.48 cm) of smoke. Very clean environments: Used in Laboratories. Level 2: 2% per foot (30.48 cm) of smoke. Clean environments: Used in offices. Level 3: 3% per foot (30.48 cm) of smoke. Moderately clean environments: Used in hotel rooms, dorm rooms. Level 4: 3% per foot (30.48 cm) of smoke with different algorithm processing an d weighting of sensor elements. Used in hotel rooms near a shower, boiler rooms. Level 5: 4% per foot (30.48 cm) of smoke. Used in equipment rooms, kitchens, paint shop. Level 6: Thermal alarm at 135° F (57° C). Warning: After the CO cell has reached the end-of-life, the CO sensor no longer provides life safety protection. How- ever, when the fire detector enters Photo, Thermal, Infra- red (PTIR) mode, the following sensitivities apply: Level 1: 1% per foot (30.48 cm) of smoke. Very clean environments: Used in Laboratories. Level 2: 2% per foot (30.48 cm) of smoke. Clean environments: Used in offices. Level 5: 3% per foot (30.48 cm) of smoke. Moderately clean environments: Used in hotel rooms, dorm rooms. Level 6: Thermal alarm at 135° F (57° C). Specifications (Continued) CO Monitoring UL Standard Reference - Alarm Thresholds are as follows: Parts per Million 70 ± 5ppm 150±5ppm 400± 10ppm Detector Response Time, min. 60-240 10-50 4-15 Note: Per UL Standard 2075, the MCS-COF has been tested to the sensitivity limits defined in UL Standard 2034.
Ordering Information
MCS-COF Advanced Multi-Criteria Fire/CO Detector Note: Due to the unique nature of this detector, please consult your Fire Alarm Control Panel Manufacturer for the specific model and compatibility. Accessories: B200S Addressable Sounder Base M02-04-01 Detector Test Magnet M02-09-01 Telescoping Test Magnet