MCBC SENSATA | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
Features
- Microcontroller based burst fire control SSR
- Ratings from 25 A to 90 A @ 48-530 VAC
- Low-voltage, current, or potentiometer control
- Output status indicator
- Separate output enable / disable control
- Two time-base periods available
- For use with a wide range of resistive loads Description 120 V 240 V 480 V Operating Voltage (47-63 Hz) [Vrms] 48-140 180-280 300-530 Transient Overvoltage [Vpk] 400 600 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 5 7 12 Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] 200 200 200 Description 25 A 50 A 90 A 40-140 VAC MCBC1225 MCBC1250 MCBC1290 180-280 VAC MCBC2425 MCBC2450 MCBC2490 300-530 VAC MCBC4825 MCBC4850 MCBC4890 PRODUCT SELECTION
www.sensata.comCopyright © 2024 Sensata Technologies, Inc. Output Status Functions Description LED Initial Logic Supply On Flash Once Load Voltage Missing / Load Open (w/control disabled) Flash Once Intermittenly Load Voltage Missing / Load Open (w/control enabled) Flash Twice Intermittently Analog Input < Threshold Off Analog Input < Threshold < Max. Varying On/Off Analog Input > Max. On, Bright Input (1) Description DC Control DC Voltage Supply Range (VDC) [P1] 8-32 Input Current Range [mA] [P1] 28-30 Nominal Input Impedance [Ohm] [P3] 30K Control Must Operate Voltage "On"[VDC][P3] 5-32 Control Must Release Voltage "Off" [VDC][P3] 0-4 Control Input Current [mA][P3] 0-1.25 PLV Range Option A [VDC][P4] (3) 0-5 PLV Range Option B [VDC][P4] (3) 0-7 PLV Range Option C [VDC][P4] (3) 0-10 PLV Range Option D [VDC][P4] (3) 4-20 Nominal Input Impedance Option A,B,C [Ohm][P4] 20K Nominal Input Impedance Option D [Ohm][P4] 220 Output Description 25 A 50 A 90 A Maximum Load Current Arms 25 50 90 Minimum Load Current [Arms] 150 150 150 Maximum Surge Current (16.6 msec)[Apk] 250 625 1200 Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 Thermal Resistance Junction to Case (Rjc) [°C/W] 1.02 0.63 0.28 Maximum I² t for Fusing (8.3 msec) [A²sec] 260 1620 6000
www.sensata.comCopyright © 2024 Sensata Technologies, Inc. MECHANICAL SPECIFICATIONS THERMAL DERATE INFORMATION General Dielectric Strength, Input/Output/Base (50/60 Hz) 4000 VRMS Minimum Insulation Resistance (@ 500 VDC) 109 Ohms Maximum Capacitance, Input/Output 10 pF Ambient Operating Temperature Range -20 to 80°C Ambient Storage Temperature Range -40 to 125 °C Weight (typical) 3.0 oz (86.5g) Encapsulation Thermally conductive Epoxy Terminals-Power Screws and Saddle Clamps Furnished, Unmounted Terminals-Control Barrier Strip Screw Terminals Max. Terminal (Power) Screw Torque 20 lb-in (8-32 screws, dry without grease) Tolerances: ±0.02 in / 0.5 mm All dimensions are in inches [millimeters]
www.sensata.comCopyright © 2024 Sensata Technologies, Inc. WIRING DIAGRAMS OUTPUT VS ANALOG INPUT SIGNAL CURVES
www.sensata.comCopyright © 2024 Sensata Technologies, Inc. Series MC Product Type BC: Burst Fire Control Operating Voltage 12: 48-140 Vrms 24: 180-280 Vrms 48: 300-530 Vrms Rated Load Current 25: 25 Amps 50: 50 Amps 90: 90 Amps Analog Control Signal A: 0-5 VDC B: 0-7 VDC C: 0-10 VDC D: 4-20 mA E: Internal Potentiometer Time Base Period F: 10 AC Cycles L: 20 AC Cycles ORDERING OPTIONS Example : MCBC2425CF MC BC 24 25 C F AGENCY APPROVALS & CERTIFICATIONS (1) All parameters at 25°C unless otherwise specified. (2) Voltages are reference to GND (Ground = 0 VDC) P2 (3) PLVI voltage can go up to max. supply voltage without damage (4) Heat sinking required, see derating curves GENERAL NOTES NOTE: Not all combinations are available. Consult factory for information on the availability of a specific part number. Required for valid part number For options only and not required for valid part number E116949
+1 (800) 350 2727 sales.crydom@sensata.com Europe, Middle East & Africa +44 (1202) 416170 ssr-info.eu@sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 Rev:08/04/24_ ECN 20395 FDE-07-01 Rev. B www.sensata.com CONTACT USCopyright © 2024 Sensata Technologies, Inc. Datasheets provided by Sensata Technologies, Inc., its subsidiaries and/or affiliates (“Sensata”) are solely intended to assist third parties (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, valuation, and judgment in designing Buyer’s systems and products. Sensata datasheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular datasheet. Sensata may make corrections, enhancements, improvements, and other changes to its datasheets or components without notice. Buyers are authorized to use Sensata datasheets with the Sensata component(s) identified in each particular datasheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATASHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATASHEETS OR USE OF THE DATASHEETS, EXPRESS, IMPLIED, OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATASHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY , AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA. WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
- The product’s side panels may be hot, allow the product to cool before touching
- Follow proper mounting instructions including torque values
- Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Disconnect all power before installing or working with this equipment
- Verify all connections and replace all covers before turning on power Failure to follow these instructions will result in death or serious injury.