© 2015 Bel Power Solutions, Inc. North America +1-866.513.2839 Asia-Pacific +86.755.29885888 Europe, Middle East +353 61 225 977 tech.support@psbel.com BCD.00667_001 3 x 2 Footprint 120 Watts with Forced Air Cooling Approval to EN60601 3rd Edition Efficiencies up to 93% -40 To 70 Degree Operating Temperature Dual Fusing Thermal Shut-Down Feature >3.00 Million Hours, Telcordia -SR332-Issue 3 Standby Power < 0.3W Class II Option Available RoHS Compliant CE Marked The MBC 120 Series of open frame medical power supplies feature a wide universal AC input range of 85 V – 264 VAC, offering 120 W of output power in a compact footprint, with a variety of isolated single output voltages. The MBC series was designed to 3 rd edition medical approvals and provides 2x MOPP (Means of Patient Protection) isolation for Class I and Class II installations. These power supplies are ideal for medical, telecom, Datacom, industrial equipment and other applications. Diagnostic Drug Pump Dialysis Home Health Care Monitoring Portable Equipment
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com BCD.00667_001 MODEL NUMBER2 DESCRIPTION VOLTAGE MAX. LOAD (CONVECTION) MAX. LOAD (200 LFM) MIN. LOAD RIPPLE & NOISE 1 MBC120-1T12L MBC120-1012L Screw Terminal Molex Header 12 V 8.33 A 10.0 A 0.0 A 1% MBC120-1T15L MBC120-1015L Screw Terminal Molex Header 15 V 6.66 A 8.0 A 0.0 A 1% MBC120-1T24L MBC120-1024L Screw Terminal Molex Header 24 V 4.16 A 5.0 A 0.0 A 1% MBC120-1T30L MBC120-1030L Screw Terminal Molex Header 30 V 3.33 A 4.0 A 0.0 A 1% MBC120-1T48L MBC120-1048L Screw Terminal Molex Header 48 V 2.08 A 2.5 A 0.0 A 1% MBC120-1T58L MBC120-1058L Screw Terminal Molex Header 58 V 1.72 A 2.07 A 0.0 A 1% COVER-120-XBC metal cover kit accessory 1 Ripple is peak to peak with 20 MHz bandwidth and 10 μF (Tantalum capacitor) in parallel with a 0.1 μF capacitor at rated line voltage and load ranges. 2 For Class II Option (without input Earth pin) add suffix: -2 (e.g.: MBC120-1012L-2).
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com BCD.00667_001 Specifications are for nominal input voltage, 25°C unless otherwise stated. PARAMETER DESCRIPTION / CONDITION SPECIFICATION Input Voltage Universal (see derating under output power) 85-264 VAC / 390 VDC3 Input Frequency 47-63 Hz Input Current 115 VAC:
230 VAC:
1.2 A max. 0.65 A max. No Load Power Typical < 0.3 W Inrush Current
115 VAC:
264 VAC:
Leakage Current Typical (N.A. For Class II Option) Touch current 300 uA <100 uA Power Factor @ Full Load > 0.95 Switching Frequency Typical 60 KHz 3 Functional, not approved. PARAMETER DESCRIPTION / CONDITION SPECIFICATION Output Power With 200 LFM: Convection: 120 W Up to 100 W Efficiency
48 V, 58 V:
24 V, 30 V:
12 V, 15 V:
93% 91% 90% Hold-up Time Typical >10 ms Line Regulation +/-0.5% Load Regulation +/-1% Transient Response 25% step load change, at 0.1A/uS slew rate, 50% duty cycle, 50 Hz = 4% recovery time < 5 ms Voltage Adjustment +/-3% Rise Time Typical 55 ms Set Point Tolerance +/-1% Over Current Protection > 110% Over Voltage Protection Latch type (AC recycling required) 110 to 140% Short Circuit Protection Hiccup mode PARAMETER DESCRIPTION / CONDITION SPECIFICATION Operating Temperature Startup guaranteed, derate linearly above 50°C to 70°C as per Fig 1. -40 to +70°C -40 to 0°C Storage Temperature -40 to +85°C Cooling Forced: with 300 LFM (Refer to Mech. Drawing) Convection: for input 100-264 VAC (derate linearly to 80W @ 85VAC) 120 W 100 W Relative Humidity Noncondensing 5% to 95% Altitude Operating: Nonoperating: 16,000 ft 40,000 ft. Reliability MTBF according to Telcordia -SR332-Issue 3 3.00 million hours
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com BCD.00667_001 PARAMETER DESCRIPTION / CONDITION SPECIFICATION Conducted Emissions EN55022-B, CISPR22-B, FCC PART15 - B Static Discharge EN61000-4-2: Level-3 RF Field Susceptibility EN61000-4-3: Level-3 Fast Transients/Bursts EN61000-4-4: Level-3 Radiated Emissions Radiated: Radiated with external core: (King core K5B RC 25x12x15-M in input cable with 5 Turns) Level A Level B Surge Susceptibility EN61000-4-5: Level-3 Harmonic Current EN61000-3-2: Class D PARAMETER DESCRIPTION / CONDITION SPECIFICATION Isolation Voltage Input to Output: (For medical applications) Input to GND: (Not Applicable For Class II Option) Output to GND: for type BF for type B (N/A For Class II Option)
4000 VAC
1500 VAC
500 VAC
Safety Standard(s) Approved to the latest edition of the following standards: CSA/UL60601-1, EN60601-1 and IEC60601-1. Agency Approvals Nemko, UL, C-UL CE mark Complies with LVD Directive Figure 1 – Derating Curve CONNECTOR PIN DESCRIPTION / CONDITION MANUFACTURER / PN AC Input Connector J1 Pin 1 Pin 2 Pin 3 AC Line Not Fitted AC Neutral Screw Terminal (Option 1) Molex: 39357-0003 Tyco-2-1776112-3 Molex Header (Option 2) Molex: 1722861103 (Mating conn: Molex 1722561003) DC Output Connector J2 Pin 1, 2 Pin 3, 4 V1 +VE V1 - VE Screw Terminal (Option 1) Molex: 39357-0004 Tyco-2-1776112-4 Molex Header (Option 2) Molex: 1722861104 (Mating conn: Molex 1722561004)
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com BCD.00667_001 PARAMETER DESCRIPTION / CONDITION Weight 150 g Dimensions 76.2 x 50.8 x 30.1 mm (3 x 2 x 1.18 inch) Figure 2 - Mechanical Drawing - Screw Terminal (Option 1)
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com BCD.00667_001 Figure 3 - Mechanical Drawing - Molex Header (Option 2) NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.