Current monitoring relays CM-SRS.2 For single-phase AC/DC currents The CM-SRS.2 is an electronic current monitoring relay that monitors single-phase mains (DC or AC) for over- and undercurrent from 3 mA to 15 A. All devices are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connecting terminals) and the completely tool-free Easy Connect Technology (push-in terminals). Characteristics – Monitoring of DC and AC currents (3 mA to 15 A) – TRMS measuring principle – One device includes 3 measuring ranges – Over- or undercurrent monitoring configurable – Hysteresis adjustable (3-30 %) – Tripping delay T V adjustable (0 s; 0.1-30 s) – 3 control supply voltage versions – Precise adjustment by front-face operating controls – Screw connection technology or Easy Connect Technology available – Housing material for highest fire protection classification UL 94 V-0 – Tool-free mounting on DIN rail as well as demounting – 2 c/o (SPDT) contacts – 22.5 mm (0.89 in) width – 3 LEDs for status indication Approvals / Marks A C R E L / a b Classifcations : EN 50155, IEC 60571, NF F 16-101/102, EN 45545-2 EN 50155, IEC 60571 Temp. class Voltage supply Vibration and shock acc to IEC/EN 61373 Coated pcb. S1 S2 C1 C2 T3 n n n - Cat 1, Class B no NF F 16-101/102 EN 45545-2 Flammability index Opticity and toxicity of smoke index Risk level achieved I2 F2 HL3
2 - Current monitoring relays CM-SRS.2 | Data sheet Order data Current monitoring relays Type Rated control supply voltage Connection technology Measuring ranges Order code CM-SRS.21P 24-240 V AC/DC Push-in terminals 3-30 mA, 10-100 mA, 0.1-1 A 1SVR740840R0400 110-130 V AC 1SVR740841R0400 220-240 V AC 1SVR740841R1400 CM-SRS.21S 24-240 V AC/DC Screw type terminals 3-30 mA, 10-100 mA, 0.1-1 A 1SVR730840R0400 110-130 V AC 1SVR730841R0400 220-240 V AC 1SVR730841R1400 CM-SRS.22S 24-240 V AC/DC Screw type terminals 0.3-1.5 A, 1-5 A, 3-15 A 1SVR730840R0500 110-130 V AC 1SVR730841R0500 220-240 V AC 1SVR730841R1500 Accessories Type Description Order code ADP .01 Adapter for screw mounting 1SVR430029R0100 MAR.12 Marker label for devices with DIP switches 1SVR730006R0000 COV.11 Sealable transparent cover 1SVR730005R0100
Data sheet | Current monitoring relays CM-SRS.2 - 3 Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CM-xxS.yyP Approved screw connection technology with double-chamber cage connecting terminals Type designation CM-xxS.yyS Push-in terminals – Tool-free connection of rigid and flexible wires with wire end ferrule – Easy connection of flexible wires without wire end ferrule by opening the terminals – No retightening necessary – One operation lever for opening both connecting terminals – For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) – Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) – Opening for testing the electrical contacting – Gas-tight Double-chamber cage connecting terminals – Terminal spaces for different wire sizes – One screw for opening and closing of both cages – Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connecting terminals have the same connection geometry as well as terminal position. 2CDC 253 025 F0011 2CDC 253 026 F0011
4 - Current monitoring relays CM-SRS.2 | Data sheet Functions Operating controls 2CDC 251 054 V0011
1 Adjustment of the hysteresis (MIN = Default)
2 Adjustment of the threshold value (MIN = Default)
3 Indication of operational states
U/T: green LED – control supply voltage/timing R: yellow LED – relay status I: red LED – over- / undercurrent
4 Adjustment of the tripping delay T V
5 DIP switches (see DIP switch functions)
The current monitoring relays CM-SRS.2 are designed for use in single-phase AC and/or DC systems for over- or undercurrent monitoring. The devices are available with different supply voltage ranges, provide an adjustable tripping delay and work according to the open-circuit principle. Operating mode The CM-SRS.2 with 2 c/o (SPDT) contacts are available in 2 versions with 3 measuring ranges: 3-30 mA, 10-100 mA, monitored wire to the corresponding terminal B1/B2/B3-C. The units are adjusted with front-face operating controls. The selection of over- b or undercurrent monitoring a is made with a DIP switch. Potentiometers, with direct reading scale, allow the adjustment of the threshold value I, the hysteresis % and the tripping delay T V. The hysteresis % is adjustable within a range of 3 to 30 % of the threshold value and the tripping delay T V over a range of instantaneous to a 30 s delay. Timing is displayed by a flashing green LED labelled U/T.
Data sheet | Current monitoring relays CM-SRS.2 - 5 Function diagrams Overcurrent monitoring b The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value exceeds the adjusted threshold value, the tripping delay T V starts and the red LED (overcurrent) glows. Timing of T V is displayed by the flashing W green LED. When T V is complete and the measured value still exceeds the threshold value minus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized) glows. If the measured value decreases below the threshold value minus the adjusted hysteresis, the output relays de-energize and the red and yellow LEDs turn off. A1-A2 11-14 (15-18) 11-12 (15-16) 21-24 (25-28) 21-22 (25-26) Threshold Hysteresis Measured value green LED red LED yellow LED TV < TV 2CDC 252 210 F0205 Undercurrent monitoring a The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value decreases below the adjusted threshold value, the tripping delay T V starts and the red LED (undercurrent) flashes W. Timing of T V is displayed by the flashing W green LED. When T V is complete and the measured value is still below the threshold value plus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized) glows. If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relays de-energize and the red and yellow LEDs turn off. A1-A2 11-14 (15-18) 11-12 (15-16) 21-24 (25-28) 21-22 (25-26) Threshold Hysteresis Measured value green LED red LED yellow LED TV < TV 2CDC 252 211 F0205
6 - Current monitoring relays CM-SRS.2 | Data sheet Electrical connection A1 A2 2125 2226 2428 A1 1115 2125 B1 B2 B3 2428 2226 A2 1115 1216 1418 1418 1216 C B1 B2 B3 C 2CDC 252 205 F0005 A1-A2 Rated control supply voltage B1-C Measuring range 1: CM-SRS.21: 3-30 mA CM-SRS.22: 0.3-1.5 A B2-C Measuring range 2: CM-SRS.21: 10-100 mA CM-SRS.22: 1-5 A B3-C Measuring range 3: CM-SRS.21: 0.1-1 A CM-SRS.22: 3-15 A 1115-1216/1418 Output contacts - open-circuit principle 2125-2226/2428 Connection diagram DIP switches 2CDC 252 272 F0005
1 ON Undercurrent monitoring
OFF Overcurrent monitoring OFF = Default
Data sheet | Current monitoring relays CM-SRS.2 - 7 Technical data Data at T a = 25 °C and rated values, unless otherwise indicated Input circuits Supply circuit A1-A2 Rated control supply voltage U s 110-130 V AC 220-240 V AC 24-240 V AC/DC Rated control supply voltage U s tolerance -15...+10 % Rated frequency 50/60 Hz 50/60 Hz or DC Typical current / power consumption 24 V DC - - 30 mA / 0.75 W 115 V AC 24 mA / 2.6 VA - 17 mA / 1.9 VA 230 V AC - 12 mA / 2.6 VA 11 mA / 2.6 VA Power failure buffering time 20 ms Transient overvoltage protection varistors Measuring circuit B1/B2/B3-C Monitoring function over- or undercurrent monitoring configurable Measuring method TRMS measuring principle Measuring inputs CM-SRS.21 CM-SRS.22 1) terminal connection B1-C B2-C B3-C B1-C B2-C B3-C measuring range 3-30 mA 10-100 mA 0.1-1 A 0.3-1.5 A 1-5 A 3-15 A pulse overload capacity t < 1 s 500 mA 1 A 10 A 15 A 50 A 100 A continuous capacity 50 mA 150 mA 1.5 A 2 A 7 A 17 A Threshold value adjustable within the indicated measuring range Tolerance of the adjusted threshold value 10 % of the range end value Hysteresis related to the threshold value 3-30 % adjustable Measuring signal frequency range DC / 15 Hz - 2 kHz Rated measuring signal frequency range DC / 50-60 Hz Maximum response time AC 80 ms DC 120 ms Accuracy within the rated control supply voltage tolerance ΔU ≤ 0.5 % Accuracy within the temperature range ΔU ≤ 0.06 % / °C Timing circuit Time delay T V 0 s or 0.1-30 s adjustable Repeat accuracy (constant parameters) ±0.07 % of full scale Tolerance of the adjusted time delay - Accuracy within the rated control supply voltage tolerance Δt ≤ 0.5 % Accuracy within temperature range Δt ≤ 0.06 % / °C User interface Indication of operational states Control supply voltage U/T: green LED V: control supply voltage applied W: tripping delay T V active Measured value I: red LED V: overcurrent W: undercurrent Relay status R: yellow LED V: output relay energized 1) For usage of the current monitoring relays according to UL, following limitations for the measuring circuits are applicable: The load on any single measuring circuit should not exceed 15 A at 51-150 V, 10 A at 151-300 V or 5 A at 301-600 V. This limitation is only valid for application according to UL and not for IEC applications.
8 - Current monitoring relays CM-SRS.2 | Data sheet Output circuits Kind of output 1115-1216/1418 relay, 1st c/o (SPDT) contact 2125-2226/2428 relay, 2nd c/o (SPDT) contact Operating principle open-circuit principle (output relay energizes if the measured value exceeds b / falls below a the adjusted threshold value) Contact material AgNi Rated operational voltage U e 250 V Minimum switching voltage / Minimum switching current 24 V / 10 mA Maximum switching voltage / Maximum switching current 250 V AC / 4 A AC Rated operational current I e AC-12 (resistive) at 230 V 4 A AC-15 (inductive) at 230 V 3 A DC-12 (resistive) at 24 V 4 A DC-13 (inductive) at 24 V 2 A AC rating (UL 508) utilization category (Control Circuit Rating Code) B 300 max. rated operational voltage 300 V AC max. continuous thermal current at B 300 5 A max. making/breaking apparent power at B 300 3600/360 VA Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime AC-12, 230 V, 4 A 0.1 x 10 6 switching cycles Maximum fuse rating to achieve short-circuit protection n/c contact 10 A fast-acting n/o contact 10 A fast-acting General data MTBF on request Duty time 100 % packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Weight Screw connection technology Easy Connect Technology (Push-in) Version 110-130 V AC 0.179 kg (0.395 lb) 0.168 kg (0.370 lb) Version 220-240 V AC 0.179 kg (0.395 lb) 0.168 kg (0.370 lb) CM-SRS.22 Version 24-240 V AC/DC 0.144 kg (0.318 lb) - Version 110-130 V AC 0.181 kg (0.399 lb) - Version 220-240 V AC 0.181 kg (0.399 lb) - Version 110-130 V AC 0.201 kg (0.443 lb) 0.190 kg (0.419 lb) Version 220-240 V AC 0.201 kg (0.443 lb) 0.190 kg (0.419 lb) CM-SRS.22 Version 24-240 V AC/DC 0.166 kg (0.366 lb) - Version 110-130 V AC 0.203 kg (0.448 lb) - Version 220-240 V AC 0.203 kg (0.448 lb) - Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool Mounting position any Minimum distance to other units 10 mm (0.39 in) at measured current > 10 A Material of housing UL 94 V-0 Degree of protection housing IP50 terminals IP20
Data sheet | Current monitoring relays CM-SRS.2 - 9 Electrical connection Screw connection technology Easy Connect Technology (Push-in) Connecting capacity fine-strand with(out) wire end ferrule 1 x 0.5-2.5 mm² (1 x 18-14 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) 2 x 0.5-1.5 mm² (2 x 18-16 AWG) rigid 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) Stripping length 8 mm (0.32 in) Tightening torque 0.6 - 0.8 Nm (7.08 lb.in) Environmental data Damp heat, cyclic (IEC/EN 60068-2-30) 55 °C, 6 cycles Vibration, sinusoidal Class 2 Shock Class 2 Isolation data Rated insulation voltage U i supply / measuring circuit / output 600 V output 1 / output 2 250 V Rated impulse withstand voltage U imp supply / measuring circuit / output 6 kV 1.2/50 μs output 1 / output 2 4 kV 1.2/50 μs Pollution degree 3 Overvoltage category III Standards / Directives Standards IEC/EN 60947-5-1, IEC/EN 60255-27, EN 50178 Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU RoHS Directive 2011/65/EU Railway application standards EN 50155, IEC 60571 “Railway applications – Electronic equipment used on rolling stock” temperature class T3 supply voltage category S1, S2, C1 IEC/EN 61373 “Railway applications – Rolling stock equipment – Shock and vibration tests” Category 1, Class B EN 45545-2 Railway applications – Fire protection on railway vehicles – part 2: Requirements for fire behavior of materials HL3 and components ISO 4589-2 LOI 32.3 % EN ISO 5659-2 Ds max (T10.03) 104 NF F 16-101: Rolling stock. Fire behaviour. Materials choosing NF F 16-102: Railway rolling stock. Fire behaviour. Materials choosing, application for electric equipment I2 / F2 DIN 5510-2 Preventive fire protection in railway vehicles. Part 2: Fire behaviour and fire side effects of materials and parts fullfilled
10 - Current monitoring relays CM-SRS.2 | Data sheet Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-2 electrostatic discharge IEC/EN 61000-4-2 Level 3 radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3 electrical fast transient / burst IEC/EN 61000-4-4 Level 3 surge IEC/EN 61000-4-5 Level 3 conducted disturbances, induced by radio-frequency fields IEC/EN 61000-4-6 Level 3 Interference emission IEC/EN 61000-6-3 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B Technical diagrams Load limit curves 300 200 100 12 46 10 IA V V 0.1 0.2 0.5 resistive load 2CDC 252 194 F0205 AC load (resistive) 300 200 100 1 2 4 6 10 IA V V 0.1 0.2 0.5 resistive load 2CDC 252 193 F0205 DC load (resistive) cos ϕ F 0.5 0.6 0.7 0.8 0.9 1.0 2CDC 252 192 F0205 Derating factor F for inductive AC load Switching current [A] Switching cycles 250 V resistive load 2CDC 252 148 F0206 Contact lifetime
Data sheet | Current monitoring relays CM-SRS.2 - 11 Dimensions in mm and inches 113.4 4.47” 22.5 0.89” 85.6 3.37” 103.7 4.08” 105.9 4.17” 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89” 68 2.68” 110.5 4.31” 8 0.32” 4.8 0.19” front to back 2CDC 252 010 F0011 6.5 62.5 10 11.5 0.256” 2.461” 2.362” 70 2.756” 0.394” 0.787” 0.453” 2CDC 252 008 F0010 19.9 4T22 7.85 0.309” 0.783” 22.2 0.874” 2CDC 252 020 F0011 ADP .01 - Adapter for screw mounting MAR.12 - Marker label for devices with DIP switches COV.11 - Sealable transparent cover Further documentation Document title Document type Document number Electronic products and relays Technical catalogue 2CDC 110 004 C02xx CM-SRS.1, CM-SRS.2 Instruction manual 1SVC 730 610 M0000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays. CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls.
P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Contact us Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Copyright© 2016 ABB All rights reserved Document number 2CDC 112 168 D0201 (07.2016)