MODEL: M8BS1-16 M8BS1-16 SPECIFICATIONS ES-5494 Rev.12 Page 1/6 http://www.m-system.co.jp/ Dual Output Super-mini Signal Conditioners Pico-M Series INSTALLATION BASE (16 positions) (CE) Functions & Features

  • Holding up to 16 modules of Pico-M series signal conditioners
  • Power for the I/O modules supplied via printed wiring on the base
  • Wiring within the instrumentation panel is minimized through the collective power input terminal MODEL: M8BS1-16[1]-[2][3]

ORDERING INFORMATION

  • Code number: M8BS1-16[1]-[2][3] Specify a code from below for each of [1] through [3]. (e.g. M8BS1-16U0-R/Q)
  • Specify the specification for option code /Q (e.g. /C01) [1] CONNECTION (output 1/output 2) U0: Screw terminal block / Screw terminal block U3: Omron MIL type connector / Screw terminal block Y1: Yokogawa DCS VMx/PM1 card use / Screw terminal block [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 63 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) Only solder side of the main PWB is coated. /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating GENERAL SPECIFICATIONS Capacity: 16 positions Connection Power input: M3.5 screw terminals (torque 0.8 N·m) Input and output: M3.5 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated steel Isolation: Input to output 1 to output 2 to power to FG Power indicator LED: ON with normal voltage level (For AC power model, LED is on the AC power unit) INSTALLATION Power Consumption
  • AC: 130 VA min.
  • DC: 2.5 A min. Operating temperature: 0 to 55°C (32 to 131°F) 0 to 50°C (32 to 122°F) for AC power Operating humidity: 30 to 90 %RH (non- condensing) 30 to 85 %RH for AC power Atmosphere: No corrosive gas or heavy dust Mounting: Surface Weight M8BS1-16U0: 1.9 kg (4.2 lb) for power code M2 1.5 kg (3.3 lb) for power code R M8BS1-16U3, M8BS1-16Y1: 1.7 kg (3.7 lb) for power code M2 1.3 kg (2.9 lb) for power code R PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength DC power:

1500 V AC @1 minute (input to output 1 or output 2 or

power to FG)

500 V AC @1 minute (output 1 to output 2 to power)

AC power: power)

1500 V AC @1 minute (input to FG)

500 V AC @1 minute (output 1 to output 2 to power to FG)

STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive

MODEL: M8BS1-16 M8BS1-16 SPECIFICATIONS ES-5494 Rev.12 Page 2/6 http://www.m-system.co.jp/ The AC power unit conforms with the following standards: EN 50178 Installation Category II Pollution Degree 2 Max. operating voltage 300 V RoHS Directive MOUNTING REQUIREMENTS unit: mm (inch) 460 (18.11) 4–M5 SCREW 50 (1.97) CONNECTION DIAGRAM ■ MODEL: M8BS1-16U0 (screw terminal block / screw terminal block) ■ CONNECTION DIAGRAM A B C D Ch.1 INPUT*A B C D Ch.16 INPUT* ■ DC Power Supply ■ AC Power Supply AC POWER UNIT FG 3 U V AC POWER FG POWER OUTPUT 1 A B C D Ch.1 INPUT*A B C D Ch.16 INPUT* OUTPUT 2 OUTPUT 1 OUTPUT 2 Ch.1 OUTPUT* –Ch.16 OUTPUT* OUTPUT 1 OUTPUT 2 OUTPUT 1 OUTPUT 2 Ch.1 OUTPUT* –Ch.16 OUTPUT* *The input and output terminals are reversed for model M8YSx, M8YCx. Use either Output 1 or Output 2 terminal for the input. ■ MODEL: M8BS1-16U3 (Omron MIL type connector, XG4A-3431 / screw terminal block) ̒Connector Pin Assignment CN1 PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ EJ EJ̄ 7PWUGF

MODEL: M8BS1-16 M8BS1-16 SPECIFICATIONS ES-5494 Rev.12 Page 3/6 http://www.m-system.co.jp/ ■ CONNECTION DIAGRAM A B C D CN1 Ch.1 INPUT*A B C D Ch.16 INPUT* AC POWER UNIT FG 3 U V AC POWER FG POWER A B C D CN1 Ch.1 INPUT*A B C D Ch.16 INPUT* ■ DC Power Supply ■ AC Power Supply OUTPUT 2 OUTPUT 2 Ch.1 OUTPUT* Ch.16 OUTPUT* OUTPUT 2 OUTPUT 2 Ch.1 OUTPUT* Ch.16 OUTPUT** The input and output terminals are reversed for model M8YSx, M8YCx. Use either Output 1 (connector) or Output 2 terminal for the input. ■ MODEL: M8BS1-16Y1 (Yokogawa DCS VMx/PM1 card use (PS-40PE-D4T1-PN1) / screw terminal block)

  • Location CN1: VMx / PM1 card use* The input or output 1 is connected to the connector. VM1/PM1/VM4 CARD INPUT or OUTPUT 1ɹ 2 ɹ 3 ɹ 4 ɹ 5 ɹ 6 ɹ 7 ɹ 8 ɹ9ɹ10 ɹ11 ɹ12 ɹ13 ɹ14 ɹ15 ɹ16 1ɹ 2 ɹ 3 ɹ 4 ɹ 5 ɹ 6 ɹ 7 ɹ 8 ɹ9ɹ10 ɹ11 ɹ12 ɹ13 ɹ14 ɹ15 ɹ16 VM2 CARD INPUT NO. VM2 CARD OUTPUT NO. 1ɹ 2 ɹ 3 ɹ 4 ɹ 5 ɹ 6 ɹ 7 ɹ 8 1ɹ 2ɹ 3ɹ 4ɹ 5ɹ 6ɹ 7ɹ 8 Pico-M LOCATION NO. *VMx / PM1 card (uses KS2 cable) VM1: analog input 16 points VM2: analog input 8 points / analog output 8 points VM4: analog output 16 points PM1: pulse input 16 points

MODEL: M8BS1-16 M8BS1-16 SPECIFICATIONS ES-5494 Rev.12 Page 4/6 http://www.m-system.co.jp/ ■ CONNECTION DIAGRAM A B C D CN1 Ch.1 INPUT*A B C D Ch.16 INPUT* FG 3 U V AC POWER FG POWER A B C D CN1 Ch.1 INPUT*A B C D Ch.16 INPUT* OUTPUT 2 OUTPUT 2 Ch.1 OUTPUT* Ch.16 OUTPUT* OUTPUT 2 OUTPUT 2 Ch.1 OUTPUT* Ch.16 OUTPUT* ■ DC Power Supply ■ AC Power Supply * The input and output terminals are reversed for model M8YSx, M8YCx. Use either Output 1 (connector) or Output 2 terminal for the input. AC POWER UNIT EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) ■ M8BS1-16U0-M2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CH8 CH9 CH16 C D C D C D C D C D C D C D C D CH8CH1 A B A B A B A B A B A B A B A B C D C D C D C D C D C D C D C D CH16CH9 A B A B A B A B A B A B A B A B + – + 95 (3.74) 50 (1.97) 7.3(.29) 64–M3.5 OUTPUT TERMINALS 17 (.67) 440 (17.32) 460 (18.11) 480 (18.90) 64–M3.5 INPUT TERMINALS 7.3 (.29) 87 (3.43) OUTPUT 2 TERM. OUTPUT 1 TERM. AC POWER UNIT 5–M3.5 POWER TERMINALS *1. Included with M8CTx. CT PROTECTOR (CTR) *1 6.6 (0.26) 7"%+

MODEL: M8BS1-16 M8BS1-16 SPECIFICATIONS ES-5494 Rev.12 Page 5/6 http://www.m-system.co.jp/ ■ M8BS1-16U0-R 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 CH1 CH8 CH9 CH16 C D C D C D C D C D C D C D C D CH8CH1 A B A B A B A B A B A B A B A B C D C D C D C D C D C D C D C D CH16CH9 A B A B A B A B A B A B A B A B + – + 95 (3.74) 50 (1.97) 64–M3.5 INPUT TERMINALS 87 (3.43) 7.3(.29) 64–M3.5 OUTPUT TERMINALS 3–M3.5 POWER TERMINALS POWER LED 8.6 (.34) 17 (.67) 440 (17.32) 460 (18.11) 480 (18.90) 7.3 (.29) OUTPUT 2 TERM. OUTPUT 1 TERM. *1. Included with M8CTx. CT PROTECTOR (CTR) *1 ■ M8BS1-16U3-M2, M8BS1-16Y1-M2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CH1 CH8 CH9 CH16 C D C D C D C D C D C D C D C D CH8CH1 A B A B A B A B A B A B A B A B C D C D C D C D C D C D C D C D CH16CH9 A B A B A B A B A B A B A B A B 88 (3.46) 50 (1.97) 64–M3.5 INPUT TERMINALS 7.2(.28) 32–M3.5 OUTPUT TERMINALS 5–M3.5 POWER TERMINALS AC POWER UNIT 87 (3.43) 17 (.67) 7.3 (.29) 440 (17.32) 460 (18.11) 480 (18.90) CN1 CONNECTOR *1. Included with M8CTx. CT PROTECTOR (CTR) *1 6.6 (0.26) 7"%+

MODEL: M8BS1-16 M8BS1-16 SPECIFICATIONS ES-5494 Rev.12 Page 6/6 http://www.m-system.co.jp/ ■ M8BS1-16U3-R 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 CH1 CH8 CH9 CH16 C D C D C D C D C D C D C D C D CH8CH1 A B A B A B A B A B A B A B A B C D C D C D C D C D C D C D C D CH16CH9 A B A B A B A B A B A B A B A B 88 (3.46) 50 (1.97) 64–M3.5 INPUT TERMINALS 87 (3.43) 7.2(.28) 32–M3.5 OUTPUT TERMINALS 3–M3.5 POWER TERMINALS 8.6 (.34) 17 (.67) CN1 CONNECTOR POWER LED 440 (17.32) 460 (18.11) 480 (18.90) 7.3 (.29) *1. Included with M8CTx. CT PROTECTOR (CTR) *1 ■M8BS1-16Y1-R 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 CH1 CH8 CH9 CH16 C D C D C D C D C D C D C D C D CH8CH1 A B A B A B A B A B A B A B A B C D C D C D C D C D C D C D C D CH16CH9 A B A B A B A B A B A B A B A B 88 (3.46) 50 (1.97) 64–M3.5 INPUT TERMINALS 87 (3.43) 7.2(.28) 32–M3.5 OUTPUT TERMINALS 3–M3.5 POWER TERMINALS 8.6 (.34) 17 (.67) CN1 CONNECTOR POWER LED 440 (17.32) 460 (18.11) 480 (18.90) 7.3 (.29) *1. Included with M8CTx. CT PROTECTOR (CTR) *1 Specifications are subject to change without notice.