M6SXAT MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
MODEL: M6SXAT M6SXAT SPECIFICATIONS ES-7992 Rev.4 Page 1/5 http://www.m-system.co.jp/ Tension-Clamp Ultra-Slim Signal Conditioners M6S Series THERMOCOUPLE ALARM (PC programmable) Functions & Features
- Maintenance-free tension clamp connection
- 5.9-mm wide ultra-slim design
- Low profile allows the M6S module mounted in a 120-mm deep panel
- PC programmable
- Linearization and upscale and downscale burnout protection
- High-density mounting
- Power and status indicator LEDs 5.9 (.23) (3.70) 102 (4.02) mm (inch) MODEL: M6SXAT–[1]–R[2]
ORDERING INFORMATION
- Code number: M6SXAT-[1]-R[2] Specify a code from below for each [1] and [2]. (e.g. M6SXAT-2-R/Q)
- Temperature range (e.g. 0 – 1000°C)
- Specify the specification for option code /Q (e.g. /C01) [1] INPUT THERMOCOUPLE 1: (PR) 2: K (CA) 3: E (CRC) 4: J (IC) 5: T (CC) 6: B (RH) 7: R 8: S N: N 0: Specify (Please provide a emf table.) (Configurator software is used to change the input type and precise range.) OUTPUT Relay; SPDT or transfer contact POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating
RELATED PRODUCTS
- PC configurator software (model: M6CFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types. GENERAL SPECIFICATIONS Connection Input and output: Tension clamp Power input: Via the Installation Base (model: M6SBS) or Tension clamp Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm Housing material: Flame-resistant resin (black) Isolation: Input to output to power Burnout: Upscale standard; downscale or no burnout optional by programming In case of upscale standard, the alarm operates as if the input signal has exceeded over the range. Linearization: Standard Cold Junction Compensation: CJC sensor incorporated Power LED: Green light turns on when the power is supplied. Status indicator LED: Orange LED; Blinking patterns indicate different operating status of the transmitter. Alarm monitor LED: Red LED turns on when the alarm is tripped. Programming: Downloaded from PC Input type and range Input fine adjustments User’s Thermocouple table Burnout (Upscale, downscale or no burnout) Alarm setpoint (input %)
MODEL: M6SXAT M6SXAT SPECIFICATIONS ES-7992 Rev.4 Page 2/5 http://www.m-system.co.jp/ Trip action (High or Low) Relay coil (energized or de-energized) Power ON delay time (0 to 999 sec.) Alarm ON delay time (0 to 999 sec.) Hysteresis (deadband) (input %) Alarm test, and others Configurator connection: 2.5 dia. miniature jack; RS-232-C level Factory default setting Alarm setpoint: 80 % Trip action: High Relay coil at alarm: Energized Power ON delay time: 5 sec. Alarm ON delay time: 0 sec. Hysteresis (deadband) : 1.0 % Burnout: Upscale INPUT SPECIFICATIONS Input resistance: 1 MΩ min. Burnout sensing: ≤ 0.1 μA Temperature range: See Table 1. If not specified, the input range is shown below.
1 PR: 0 – 1600°C
2 K: 0 – 1000°C
3 E: 0 – 500°C
4 J: 0 – 500°C
5 T: 0 – 300°C
6 B: 500 – 1600°C
7 R: 500 – 1600°C
8 S: 0 – 1600°C
N N: 0 – 1000°C OUTPUT SPECIFICATIONS ■ Relay Output Relay rating:
250 V AC @2 A (cos ø = 1)
30 V DC @2 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 500 VA or 60 W Minimum load: 5 V DC @100 mA Mechanical life: 5 × 106 cycles (rate 180/min.) 0 50 100 Input (%) ▲ Setpoint Output (3–4)ON (3–2)ON
- Setting Example Hi alarm (coil energized at alarm) or Lo alarm (coil de-energized at alarm) Alarm Trip Operation Terminal No. in parentheses Trip operation in power failure: Terminals 3 – 4 turn ON. INSTALLATION Power consumption: Approx. 0.5 W Operating temperature: -20 to +55°C (-4 to +131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Installation Base (model: M6SBS) or DIN rail Weight: 65 g (2.3 oz) PERFORMANCE in percentage of span Setpoint accuracy (trip point accuracy): Accuracy in Table 1 + Cold junction compensation error Cold junction compensation error: ±3°C at 25 ±10°C ±5.4°F at 77 ±18°F Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint) Burnout response time: ≤ 1 sec. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output to power to ground) CALCULATION EXAMPLES OF SETPOINT ACCURACY [Example] K thermocouple, 0 – 1000°C Absolute value accuracy (Table 1): 0.25°C CJC error (3°C) added: 3.25°C Setpoint accuracy = 3.25°C ÷ 1000°C × 100 = 0.33 % Table 1. C F THERMOCOUPLE MIN. MAXIMUM CONFORMANCE ACCURACY MIN. MAXIMUM CONFORMANCE ACCURACY SPAN RANGE RANGE SPAN RANGE RANGE (PR) 20 0 to 1760 0 to 1760 ±1.00 36 32 to 3200 32 to 3200 ±1.80 K (CA) 20 -270 to +1370 -150 to +1370 ±0.25 36 -454 to +2498 -238 to +2498 ±0.45 E (CRC) 20 -270 to +1000 -170 to +1000 ±0.20 36 -454 to +1832 -274 to +1832 ±0.36 J (IC) 20 -210 to +1200 -180 to +1200 ±0.25 36 -346 to +2192 -292 to +2192 ±0.45 T (CC) 20 -270 to +400 -170 to +400 ±0.25 36 -454 to +752 -274 to +752 ±0.45 B (RH) 20 100 to 1820 400 to 1760 ±0.75 36 212 to 3308 752 to 3200 ±1.35 R 20 -50 to +1760 200 to 1760 ±0.50 36 -58 to +3200 392 to 3200 ±0.90 S 20 -50 to +1760 0 to 1760 ±0.50 36 -58 to +3200 32 to 3200 ±0.90 N 20 -270 to +1300 -130 to +1300 ±0.30 36 -454 to +2372 -202 to +2372 ±0.54 (PR) K (CA) E (CRC) J (IC) T (CC) B (RH) R S N THERMOCOUPLE
MODEL: M6SXAT M6SXAT SPECIFICATIONS ES-7992 Rev.4 Page 3/5 http://www.m-system.co.jp/ STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (output) Pollution Degree 2 Input or power to output: Reinforced insulation (300 V) Input to power: Basic insulation (300 V) RoHS Directive EN 50581 EXTERNAL VIEW (With the cover open) Power LED Alarm Monitor LED Status Indicator LED Configurator Jack
MODEL: M6SXAT M6SXAT SPECIFICATIONS ES-7992 Rev.4 Page 4/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 94 (3.70) 5.9 (.23) DIN RAIL 35mm wide DIN RAIL HOOK *Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm 102 (4.02) [0.5 (.02)]SCREWDRIVER INSERTION ANGLE : approx. 40° WIRE INSERTION ANGLE : approx.35° TEST PROBE max. 2 (.08) dia. SCREWDRIVER INSERTION ANGLE : approx. 35° 5 6 7 8 1 2 3 4
- When mounting, no extra space is needed between units. SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Low Drift Amplifier NC NO COM ■ Relay Protection
- AC Powered • DC Powered POWER OUTPUT Ry CONFIGURATOR JACK STATUS LED ALARM MONITOR LED Digital Computation T/C comp. leadwire CJC SENSOR CONNECTOR POWER POWER LED Varistor or CR Circuit Diode, Varistor or CR Circuit LOAD Inductive Load (Coil) U LOAD Inductive Load (Coil)
MODEL: M6SXAT M6SXAT SPECIFICATIONS ES-7992 Rev.4 Page 5/5 http://www.m-system.co.jp/ Specifications are subject to change without notice.