configuration through EPiC Mobile App unique commis - sioning tool. Accurate measurement Class 0.5 measurement ac - cording to IEC 61557-12 and advanced power quality functionalities, including historical measurements. Intuitive access Simplified access to the device via touch screen display or 5 pushbuttons keypad. Clear visualization Color display and App-structured menu for advanced graphic visualization. Easy to install Fast one-hand mounting and comfortable installation with clips in only 57 mm depth inside the panel. Fast wiring All-removable terminals and one tool process to speed up the wiring activities. Full communication ABB Ability™ native network analyzers with complete communication protocols and I/O options for integra - tion in any system. A M4M NETWORK ANALYZERS. THE COMPLETE OFFERING M4M Network analyzers Accurate electrical measuring and power monitoring. Simple in every aspect, M4M enables accurate energy efficiency evaluations and perfectly fits the ABB solution for monitoring, optimization and control of electrical system.
A 3PRODUCT OVERVIEW Intuitive interface Touchscreen display and easy-to-access App- structured menu make network analyzers’ configuration and operation simple and quick. Graphic color display for advanced visualization of the Class 0,5S accurate parameters, interactive pop-ups and complete notifications. Quick navigation is ensured by Homepage and favorite page setting. Smart commissioning All M4M network analyzers are equipped with Bluetooth BLE module, ensuring smart configuration and quick visualization via unique EPiC commissioning tool, both available as mobile App and desktop software. Availability of remote firmware update regularly at any time guarantees the latest and the most secure version of the device with no impact on operations. Fast installation and wiring All terminals on M4M are removable, including the current transformers (CTs) inputs for current measurement, allowing to carry out the wiring directly on the terminals and speeding up the process. Moreover, the vertical disposition of the terminals makes the cabling inside the switchboard more comfortable. Full integration ABB Ability™-native network analyzers, automatically integrated in ABB Ability™ Electrical Distribution Control System cloud-computing platform, allowing to monitor, optimize and control the complete electrical system. Wide integration in all main applications through embedded communication protocols (Modbus RTU, Modbus TCP/IP, BACnet/IP, Profibus DP V0). Installation in any panel Comfortable installation and secure fix on the panel is ensured by the easy-to-use clips, with different thickness setup for compatibility with any panel. One-hand mounting of the device thanks to the hooks on the housing. The reduced depth of only 57 mm inside the panel makes M4M suitable even in small-size switchboards. Rogowski coils compatibility Specific M4M versions compatible with ABB’s R4M Rogowski coils allow to retrofit in existing installations, integrating power quality metering with 0 downtime. The pre-wired terminals of R4M coils allow to save up to 70% time for current transformers cabling compared to standard CTs.
Voltage range [V] 48 - 240 VAC/VDC ±15% Frequency [Hz] 50 or 60 ± 5% Power consumption [VA] 10 VA max Installation category CAT III 300V class per IEC 61010-1 edition 3 Protection fuse T1 A - 277 VAC Measurement accuracy* Measurement type True RMS up to the 40th harmonic 128 samples per cycle, zero blind IEC 61557-12 IEC 61557-12 PMD/S/K70/0,5 Active energy Class 0,5 acc. to IEC 61557-12 [*] Class 0,5S acc. to IEC 62053-22 Reactive energy Class 2 acc. to IEC 61557-12 Class 2S acc. to IEC 62053-23 Active power Class 0,5 acc. to IEC 61557-12 Reactive power Class 2 acc. to IEC 61557-12 Class 1 acc. to IEC 61557-12 Apparent power Class 0,5 acc. to IEC 61557-12 Voltage Class 0,2 acc. to IEC 61557-12 Current Class 0,2 acc. to IEC 61557-12 Neutral current Calculated Class 0,2 acc. to IEC 61557-12 Frequency Class 0,1 acc. to IEC 61557-12 Unbalances (Current, Voltage) Class 0,2 acc. to IEC 61557-12 Harmonics, THD (Current, voltage) Class 1 acc. to IEC 61557-12 Voltage measurement inputs Measurement range [V] 50 - 400 VAC (L-N) 87 - 690 VAC (L-L) Measurement category 400V~ (CAT III) Rated frequency [Hz] 50-60 Hz Max. VT secondary (indirect connection) [V] 400 VAC (L-N) Max over voltage [V] 800 VAC (L-L) Protection fuse [V] T1 A - 277 VAC A M4M NETWORK ANALYZERS. THE COMPLETE OFFERING Technical features M4M 20 M4M 30
Current measurement inputs Number of current inputs 3 (L1, L2, L3) 4 (L1, L2, L3, N) Indirect insertion with CT CT rated secondary current 5 A (Class 0.5S)
1 A (Class 1)
Measurement range without accuracy derating 50 mA - 6 A Starting current 5 mA Burden 0.024 VA at 6 A Indirect insertion with Rogowski coils M4M 20 Rogowski M4M 30 Rogowski Rated current 10.000 A Measurement range without accuracy derating 100 A - 12 kA Starting current [A] 10 A I/O Digital Output Voltage (min - max) 5 - 240 VAC/DC Current (min - max) 2 - 100 mA Max ON state drop voltage 1,5 V Max R value at Min voltage conditions (5 V) 1750 Ohm Min R value at Max voltage conditions (240 V) 2400 Ohm Pulse duration [ms] 20 ms ON, 20 ms OFF Pulse frequency 25 Hz Alarm activation delay [s] 1 - 900 s (programmable) Alarm return hysteresis 0 - 40% (programmable) Digital Input Maximum voltage 240 VAC/DC Max voltage for OFF state on input 20 VAC/DC Min voltage for ON state on input 45 VAC/DC Analogue Output Programmable electrical span Span [0 - 20 mA or 4 - 20 mA] Load Typical 250 Ohm, max 500 Ohm A 5TECHNICAL FEATURES M4M 20 M4M 30
Mechanical characteristics Overall dimensions 96 mm x 96 mm x 77 mm (Depth inside the switchboard: 57 mm ) IP degree of protection (acc. to IEC 60529) Front: IP54 Terminals: IP20 Weight [g] 400 Terminal characteristics Voltage inputs Nominal cross section: 2,5 mm2 Solid/stranded wire: 0,2 - 2,5 mm2 (AWG 24 - 12) Pitch: 7,62 mm Poles: 4 Current inputs Nominal cross section: 2,5 mm2 Solid/stranded wire: 0,2 - 2,5 mm2 (AWG 24 - 12) Pitch: 5,08 mm Poles: 6 Screw flanges for fixing ominal cross section: 2,5 mm2 Solid/stranded wire: 0,2 - 2,5 mm2 (AWG 24 - 12) Pitch: 5,08 mm Poles: 8 Screw flanges for fixing RS-485 Serial port Nominal cross section: 2,5 mm2 Solid/stranded wire: 0,2 - 2,5 mm2 (AWG 24 - 12) Pitch: 5,08 mm Poles: 3 I/O Nominal cross section: 2,5 mm2 Solid/stranded wire: 0,2 - 2,5 mm2 (AWG 24 - 12) Pitch: 5,08 mm Poles: 3 (Programmable I/O, only on M4M
20 I/O)
Poles: 3 (Digital outputs) Poles: 3 (Analogue outputs, only on M4M Nominal cross section: 2,5 mm2 Solid/stranded wire: 0,2 - 2,5 mm2 (AWG 24 - 12) Pitch: 5,08 mm Poles: 5 (Programmable I/O) Poles: 3 (Programmable I/O only on M4M
30 I/O)
Poles: 3 (Analogue outputs, only on M4M Only with ABB Rogowski probes: - R4M-200 2CSG202150R1101 (200 mm diameter) - R4M-80 2CSG202160R1101 (80 mm diameter) Climatic conditions Operating temperature -25 to 70 °C (K70 acc. to IEC 61557-12) Storage temperature -40 to 85 °C (K70 acc. to IEC 61557-12) Relative humidity Max 93% (non-condensing) at 40°C Pollution degree 2 Altitude < 2.000 m User Interface Access to device 5 pushbuttons Touchscreen Display type Graphic color display Display dimensions 70 x 52 mm (3.5") A M4M NETWORK ANALYZERS. THE COMPLETE OFFERING Technical features M4M 20 M4M 30
Modbus RTU M4M 20 Modbus, M4M 20 I/O, M4M 20 Rogowski M4M 30 Modbus, M4M 30 I/O, M4M 30 Rogowski Communication interface RS485 with optical isolation Parity number Odd, Even, None Stop bit 1, 2 Address 1-247 Connector 3 pole terminal Profibus DP-V0 M4M 20 Profibus M4M 30 Profibus Protocol Profibus with slave DP-V0 function in compliance with IEC 61158 regulations Communication interface RS485 with optical isolation Baud rate Automatic detection [9.6 - 12 Mbps] Address 0-126 Connector DB 9 female connector (do not use connectors with 90° cable outlet) LED indicators Green for communication status Red for communication error Modbus TCP/IP M4M 20 Ethernet M4M 30 Ethernet Protocol Modbus TCP/IP Communication interface RJ45 RJ45 (2 ports for daisy-chain) BACnet M4M 20 Bacnet M4M 30 Bacnet Protocol BACnet/IP Communication interface RJ45 Bluetooth Type BLE (Bluetooth Low Energy) Real-time clock Clock drift - ~ 0.4 seconds per day Battery backup time - ~ 3 years without control power Standards Power metering and monitoring devices (PMD) IEC 61557-12 (IEC 62053-22, IEC 62053-23) Electrical safety IEC 61010-1 EMC IEC 61326-1 (IEC 61000-3-2, IEC 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4- 4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11) A 7TECHNICAL FEATURES M4M 20 M4M 30
Comparing the two versions M4M 20 - Class 0,5S M4M 30 - Class 0,5S Real-time TRMS current • • TRMS voltage • • Frequency • • Active, Reactive and Apparent power • • Power factor • • Operating timer, countdown timer • • Energy Active, Reactive and Apparent energy • • 4 quadrants Energy (Import/Export) • • Tariffs / • Power Quality THD (I, VLN, VLL) • • Individual Harmonics / 40th Unbalances (I, VLN, VLL) / • Neutral current Calculated Measured Phasors (I, VLN) / • Waveforms (I, VLN, VLL) / • Data recording and logs Single alarms 25 25 Warnings, alarms and errors logs • • Complex alarms with logics / 4 Demand values (average) Basic Advanced Min/Max Demand values Basic Advanced Energy Trending logs / • RTC / • HMI Graphic color Graphic color touchscreen Graphs visualization Basic Advanced Notifications • • Homepage and favourite page • • Password protection • • Connectivity Automatic integration in ABB Ability™ EDCS • • Bluetooth Low Energy • • Communication Protocols Modbus RTU, Modbus TCP/IP, Profibus DP-V0, BACnet/IP Modbus RTU, Modbus TCP/IP, Profibus DP-V0, BACnet/IP RJ45 Daisy Chain (Ethernet version) / • A M4M NETWORK ANALYZERS. THE COMPLETE OFFERING Accuracy
Same dimensions for all M4M 20 and M4M 30 versions A 9OVERALL DIMENSIONS Dimensions A: 96 mm B: 96 mm C: 77,5 mm D: 57 mm E: 20,5 mm F: 92 mm M4M 20 B F A C ED
Communication protocol I/O Bbn Order details Weight Pack
8012542 EAN Type code Order code [1 piece kg] unit pc
BLE 2 Digital out. 511519 M4M 20 2CSG251151R4051 0,400 1 BLE, Modbus RTU 2 Digital out. 511410 M4M 20 Modbus 2CSG251141R4051 BLE, Modbus TCP/IP 2 Digital out. 044710 M4M 20 Ethernet 2CSG204471R4051 BLE, Profibus DP-V0 2 Digital out. 511311 M4M 20 Profibus 2CSG251131R4051 BLE, BACnet/IP 2 Digital out. 368311 M4M 20 Bacnet 2CSG236831R4051 BLE, Modbus RTU 2 Progr. I/O, 2 Digital out., 2 Analogue out. 511618 M4M 20 I/O 2CSG251161R4051 Communication protocol I/O Bbn Order details Weight Pack BLE, Modbus RTU 2 Digital Outputs 070818 M4M 20 Rogowski 2CSG207081R4051 0,400 1 M4M 20 M4M 20 is ABB’s network analyzer range that provides complete and accurate electrical pa - rameters monitoring and basic power quality analysis. Equipped with graphic color display for advanced visualization of the measured parameters and Bluetooth module for smart commissioning. Ordering codes A M4M NETWORK ANALYZERS. THE COMPLETE OFFERING M4M 20 - ROGOWSKI VERSION M4M 20 is also available as compatible with ABB’s R4M Rogowski coils for current measure - ment, increasing the flexibility of network analyzers offer and allowing retrofit in any exist - ing installations. M4M 20 Rogowski together with R4M Rogowski coils ensures the integration of basic power quality metering in any existing system with 0 downtime.
Communication protocol I/O Bbn Order details Weight Pack BLE, Modbus RTU 4 Progr. I/O 747611 M4M 30 Modbus 2CSG274761R4051 0,400 1 BLE, Modbus TCP/IP 4 Progr. I/O 746812 M4M 30 Ethernet 2CSG274681R4051 BLE, Profibus DP-V0 4 Progr. I/O 367918 M4M 30 Profibus 2CSG236791R4051 BLE, BACnet/IP 4 Progr. I/O 024514 M4M 30 Bacnet 2CSG202451R4051 BLE, Modbus RTU 6 Progr. I/O, 2 Analogue out. 024712 M4M 30 I/O 2CSG202471R4051 Bbn Order details Weight Pack Communication protocol I/O 8012542 EAN Type code Order code [1 piece kg] unit pc BLE, Modbus RTU 4 Prog. I/O 024613 M4M 30 Rogowski 2CSG202461R4051 0,400 1 Diameter (mm) Bbn Order details Weight Pack 80 021605 R4M-80 2CSG202160R1101 0,150 200 021506 R4M-200 2CSG202150R1101 0,250 M4M 30 M4M 30 is ABB’s network analyzer range that allows complete power quality analysis and en - ergy efficiency evaluations. Equipped with touchscreen color display for simplified access to the device and with Blue- tooth module for smart commissioning. A 11ORDERING CODES M4M 30 - ROGOWSKI VERSION M4M 30 is also available as compatible with ABB’s R4M Rogowski coils for current measure - ment, increasing the flexibility of network analyzers and allowing retrofit in any existing in - stallations. M4M 30 Rogowski together with R4M coils ensure integration of complete PQ analysis in any existing system with 0 downtime. R4M ROGOWSKI COILS R4M Rogowski coils are flexible current transformer based on Rogowski technology, ideal to retrofit existing installa-tions up to 12kA. Available in two different sizes (80mm or 200mm diameters), R4M coils are directly equipped with pre-wired removable terminals that per - fectly fit M4M 20 Rogowski (3 Rogowski coil inputs) and M4M 30 Rogowski (4 Rogowski coil inputs), with no need for external integrators.