EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 info1@de.ebmpapst.com www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type K3G450-PB24-05 Motor M3G150-IF Phase 3~ Nominal voltage VAC 400 Nominal voltage range VAC 380 .. 480 Frequency Hz 50/60 Type of data definition ml Speed (rpm) min-1 2600 Power input W 5250 Current draw A 8 Min. ambient temperature °C -25 Max. ambient temperature °C 50 ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations Data in accordance with ecodesign regulation EU 327/2011 Actual Request 2015 01 Overall efficiency ηes % 69.2 59
02 Measurement category A
03 Efficiency category Static
04 Efficiency grade N 72.2 62
05 Variable speed drive Yes
Data definition with optimum efficiency. The ErP data is determined using a motor-impeller combination in a standardised measurement configuration. 09 Power input Ped kW 5.22
09 Air flow qv m³/h 7865
09 Pressure increase pfs Pa 1606
10 Speed (rpm) n min-1 2620
11 Specific ratio* 1.02 * Specific ratio = 1 + pfs / 100 000 Pa LU-176459 Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 1 / 7
EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 Technical features Mass 48.2 kg Size 450 mm Motor size 150 Surface of rotor Coated in black Material of electronics housing Die-cast aluminium Material of impeller Aluminium sheet Material of mounting plate Sheet steel, galvanised Material of support bracket Steel, coated in black Material of inlet nozzle Sheet steel, galvanised Number of blades 5 Direction of rotation Clockwise, seen on rotor Type of protection IP55 Insulation class "F" Humidity (F) / environmental protection class (H) Max. permissible ambient motor temp. (transp./ storage) +80 °C Min. permissible ambient motor temp. (transp./storage) -40 °C Mounting position Refer to product drawing Condensation drainage holes Rotor-side Operation mode S1 Motor bearing Ball bearing Technical features - Output 10 VDC, max. 10 mA - Output 20 VDC, max. 50 mA - Output for slave 0-10 V - Operation and alarm display - Input for sensor 0-10 V or 4-20 mA - External 24 V input (programming) - External release input - Alarm relay - Integrated PID controller - Output limit - Motor current limit - PFC, passive - RS485 MODBUS RTU - Soft start - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Over-temperature protected electronics / motor - Line undervoltage / phase failure detection EMC interference immunity Acc. to EN 61000-6-2 (industrial environment) EMC interference emission Acc. to EN 61000-6-3 (household environment), except EN 61000-3-2 for professionally used devices with a total rated power greater than 1 kW Touch current acc. IEC 60990 (measuring network Fig. 4, TN system) <= 3.5 mA Electrical connection Terminal box Motor protection Reverse polarity and locked-rotor protection Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 2 / 7
EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 Protection class I (if protective earth is connected by customer) Product conforming to standard EN 61800-5-1; CE Approval CSA C22.2 no. 77 + CAN/CSA-E60730-1; EAC; UL 1004-7 + 60730-1 Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 3 / 7
EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 Product drawing 1 Installation position: Shaft horizontal (install the support struts only vertically as shown in the illustration!) or rotor on bottom; rotor on top on request 2 Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 3 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm 4 Tightening torque 3.5±0.5 Nm
5 Inlet nozzle with pressure tap (k-factor: 240)
6 Mounting holes for FlowGrid
Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 4 / 7
EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 Connection screen No. Conn. Designation Function / assignment KL 1 1 L1 Mains connection, power supply, phase, see type plate for voltage range KL 1 2 L2 Mains connection, power supply, phase, see type plate for voltage range KL 1 3 L3 Mains connection, power supply, phase, see type plate for voltage range PE PE Earth connection, PE connection KL 2 1 NO Status relay, floating status contact, make for failure KL 2 2 COM Status relay, floating status contact, changeover contact, common connection, contact rating, max. 250 VAC/2 A (AC1)/min. 10 mA KL 2 3 NC Status relay, floating status contact, break for failure KL 3 1 RSA Bus connection RS485, RSA, MODBUS RTU; SELV KL 3 2 RSB Bus connection RS485, RSB, MODBUS RTU; SELV KL 3 3 / 10 GND Signal ground for control interface, SELV KL 3 4 Ain1 U Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only for use as alternative to input Ain1; SELV Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 5 / 7
EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 No. Conn. Designation Function / assignment KL 3 5 + 10 V Fixed voltage output 10 VDC, +10 V +/-3 %, max. 10 mA, short-circuit-proof, power supply for ext. devices (e.g. potentiometer); SELV KL 3 6 Ain1 I Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only for use as alternative to input Ain1 U; SELV KL 3 7 Din1 Digital input 1: Enabling of electronics, Enabling: Pin open or applied voltage 5-50 VDC Disabling: Bridge to GND or applied voltage <1 VDC Reset function: Triggers software reset after a level change to <1 VDC; SELV KL 3 8 Din2 Digital input 2: Parameter set 1/2 switching, depending on EEPROM setting, the valid/used parameter set can be selected via the bus or via the digital input DIN2. Parameter set 1: Pin open or applied voltage 5-50 VDC Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV KL 3 9 Din3 Digital input 3: Controller function of integrated controller; depending on EEPROM setting, normal / inverse can be selected for the controller function of the integrated controller via the bus or the digital input Normal: Pin open or applied voltage 5-50 VDC Inverse: bridge to GND or applied voltage <1 VDC; SELV KL 3 11 Ain2 U Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input Ain2; SELV KL 3 12 + 20 V Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for ext. devices (e.g. sensors); SELV Alternatively: +24 VDC input for parametrisation without mains power KL 3 13 Ain2 I Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only for use as alternative to input Ain2 U; SELV KL 3 14 Aout Analogue output 0-10 V, max. 5 mA, output of current motor level control coefficient; parametrisable curve; SELV Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 6 / 7
EC centrifugal module - RadiPac backward curved, single inlet with support bracket K3G450-PB24-05 Charts: Air flow 50 Hz qv m³/h cfm Pfs Pa in wg 4000 8000 12000 0 2000 4000 6000 8000 500 1000 1500 2000 2 4 6 8 ρ = 1.15 kg/m³ ± 2 % Measurement: LU-176459-1 Air performance measured as per ISO 5801 Installation category A. For detailed information on the measuring set-up, please contact ebm-papst. Suction-side noise levels: LwA measured as per ISO 13347 / LpA measured with 1m distance to fan axis. The values given are valid under the measuring conditions mentioned above and may vary according to the actual installation situation. With any deviation from the standard set-up, the specific values have to be checked and reviewed with the unit installed. Measured values U V 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 f Hz n min-1 2600 2600 2600 2600 2430 2360 2335 2345 1840 1815 1800 1805 1235 1215 1210 1210 Ped W 3067 4640 5250 5141 2502 3460 3767 3677 1122 1598 1761 1708 402 543 594 574 I A 4.78 7.13 8.00 7.89 3.95 5.36 5.81 5.68 2.04 2.67 2.89 2.82 0.84 1.08 1.17 1.14 LpAin dB(A) LwAin dB(A) 102 LwAout dB(A) 102 100 qV m3/h 15055 11910 9045 6320 14010 10780 8090 5655 10495 8260 6235 4350 6990 5535 4185 2920 pfs Pa 800 1400 1800 660 1117 1445 388 663 855 176 299 386 qV cfm 8860 7010 5325 3720 8245 6345 4760 3325 6175 4865 3670 2560 4115 3260 2465 1720 pfs in. wg 0.00 3.21 5.62 7.23 0.00 2.65 4.48 5.80 0.00 1.56 2.66 3.43 0.00 0.71 1.20 1.55 U = Supply voltage · f = Frequency · n = Speed (rpm) · Ped = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · LwAout = Sound power level outlet side qV = Air flow · pfs = Pressure increase Item no. 55166-5-9980 · ENG · Revision 202515 · Release 2019-03-27 · Page 7 / 7