M2EAXV MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 6
Technical content
MODEL: M2EAXV M2EAXV SPECIFICATIONS ES-5146 Rev.1 Page 1/6 http://www.m-system.co.jp/ Super-mini Signal Conditioners with Display Mini-M M2E Series DC ALARM (PC programmable, dual or quad alarm trip) Functions & Features
- Provides relay outputs at preset DC input levels
- Quad or dual trip
- Front LCD display indicating values in scaled engineering unit range is used to program the module
- Adjustable deadband (hysteresis)
- ON delay time selectable
- Hi/Lo trip and energized/de-energized coil independently selectable for each setpoint
- Settable with front button
- Enclosed relays
- Relays can be powered by 200 V AC and 100 V DC
- High-density mounting on DIN rail Typical Applications
- Annunciator
- Various alarm applications Mode Set Up Down (3.27) 124 (4.88) 29.5 (1.16) mm (inch) MODEL: M2EAXV–[1]-[2][3]
ORDERING INFORMATION
- Code number: M2EAXV-[1]-[2][3] Specify a code from below for each [1] through [3]. (e.g. M2EAXV-2-M2/Q)
- Specify the specification for option code /Q (e.g. /C01/S01/SET) INPUT – Field-selectable ◆ DC Input
- Current input: 0 - 50 mA DC
- Voltage input: -1000 - +1000 mV DC
- Voltage input: -10 - +10 V DC [1] OUTPUT 2: 4 points; N.O. or make contact 3: 4 points; N.C. or break contact 5: 2 points; SPDT or transfer contact [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-5146) Default setting will be used if not otherwise specified.
RELATED PRODUCTS
- M2EA configurator software (model: M2EACFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual (EM-5151) for the M2EA configurator for applicable cable types. GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3 screw terminals (torque 0.8 N·m) Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (gray) Isolation: input to L1 or L4 alarm output to L2 or L3 alarm output to power (for output code 5, L3 alarm output and L4 alarm output is not available) Configuration: Program with front buttons or Via PC.
MODEL: M2EAXV M2EAXV SPECIFICATIONS ES-5146 Rev.1 Page 2/6 http://www.m-system.co.jp/ Programmable features include: Refer to the parameter list. Configurator connection: 2.5 dia. miniature jack; RS-232-C level DISPLAY Display functions: Displays and sets measured range, engineering unit Number of pixels: 68 × 95 (horizontal × vertical) Character color: Yellow (reversing display of the current value and the alarm setting value when alarm is tripped) Display life: Approx. 60000 hours (Expected time for the Display brightness to be reduced to 50 % when the Display is used continuously with brightness setting 2 in 25 ℃) Display type: OEL display Display digit: Negative 5 digits, positive 6 digits (-99999 to 999999) Decimal point position: Selectable INPUT SPECIFICATIONS ■ DC Current Input resistance: Incorporated (23 Ω) Input range: 0 - 50 mA DC Minimum span: 2 mA Offset: Lower range can be any specific value within the input range provided that the minimum span is maintained. The measurement available for -5 - +105% of input setting range. ■ DC Voltage
- Narrow Spans (mV) Input range: -1000 – +1000 mV DC Minimum span: 100 mV
- Wide Spans (V) Input range: -10 – +10 V DC Minimum span: 1 V Offset: Lower range can be any specific value within the input range provided that the minimum span is maintained. Input resistance: 1 MΩ minimum The measurement available for -5 - +105% of input setting range. OUTPUT SPECIFICATIONS ■ Quad Alarm Relay rating: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 120 VA or 30 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 × 107 cycles ■ DUAL ALARM Relay rating: 100 V AC @ 4 A (cos ø = 1)
120 V AC @ 4 A (cos ø = 1)
240 V AC @ 2 A (cos ø = 1)
30 V DC @ 4 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 480 VA or 150 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 × 107 cycles 0 50 100 Input LL L HH H L2 (5–7) L3 (5–8) L4 (3–9) L1 (3–6) ON ON OFF ON ON OFF OFF OFF
- Example Quad N.O. contacts (LL, L, H, HH) Alarm Trip Operation Terminal No. in parentheses Trip operation in power failure Output code 2 : All relays turn OFF. Output code 3 : All relays turn ON. Output code 5 : Terminals 3 – 9, 5 – 8 turn ON. INSTALLATION Power Consumption
- AC: Max. 5 VA at 100 V Max. 6 VA at 200 V Max. 7 VA at 264 V
- DC: ≤ 2.5 W Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 10 to 85 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 200 g (0.44 lb) PERFORMANCE in percentage of FS input Accuracy (display accuracy, setting accuracy): ± (0.1% of FS + 1 digit) See CALCULATION EXAMPLES OF OVERALL ACCURACY. Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time (Filter time constant: 0 sec.): ≤ 0.5 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to L1 or L4 alarm output to L2 or L3 alarm output to power to ground) (for output code 5, L3 alarm output and L4 alarm output is not available)
MODEL: M2EAXV M2EAXV SPECIFICATIONS ES-5146 Rev.1 Page 3/6 http://www.m-system.co.jp/ CALCULATION EXAMPLES OF OVERALL ACCURACY [Example] Input Range -10 – +10 V, Input Setting -5 – +5 V
- Accuracy = Input Range Span (20 V) ÷ Input Span Setting STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (output) Installation Category II (power) Pollution Degree 2 Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) L1 or L4 alarm output to L2 or L3 alarm output: Basic insulation (300 V) RoHS Directive EN 50581 EXTERNAL VIEW Up Down Mode Set PERCENT 50.00 L4 ▲ 80.00 L3 ▲ 70.00 L2 ▼ 30.00 L1 ▼ 20.00 Display Mode Button Set Button Configurator Jack Up Button Down Button COMPONENT FUNCTION Display Indicates present values, setting values and abnormal information. çTwo types of present values at upper and lower are displayed by setting. Mode button Used to shift from measuring mode to each setting mode. çDestination to shift is changed by the time press- ing and holding the button. çUsed to return from each setting mode to measuring mode. (press and hold for 2 sec. or more) Set button Used to change setting value of setting parameter. çWhen at setting changeable state, used to enter (save) the setting value. çUsed to move on through digits of setting value for input scaling at setting changeable state. Used to release latching alarm in measuring mode (hold down more than 2 seconds). Up button Used to shift through setting parameter, and to increase or select setting value. Down button Used to shift through setting parameter, and to decrease or select setting value. Con/f_i gurator Jack Used to con/f_i gure with M2EA con/f_i gurator software (model: M2EACFG). At the same time, set the lockout setting of the unit to ‘lock’ . Refer to the operating manual (EM-5146-B) for detailed procedures.
MODEL: M2EAXV M2EAXV SPECIFICATIONS ES-5146 Rev.1 Page 4/6 http://www.m-system.co.jp/ PARAMETER LIST MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Basic setting 01 Lockout setting Lock / Unlock — Lock
10 Input range 0 – 50 mA
-1000 – +1000 mV -10 – +10 V — 0 – 50 mA 12 0 % input setting 0.00 – 48.00 -1000.0 – 900.0 -10.000 – 9.000 mA mV V 4.00 13 100 % input setting 2.00 – 50.00 -900.0 – 1000.0 -9.000 – 10.000 mA mV V 20.00 14 0 % input scaling -99999 – 999999 — 0.00 15 100 % input scaling -99999 – 999999 — 100.00
16 Input decimal point No decimal point
The number of decimal places : 1 – 5 — 2 places of decimals
17 Unit (INP Scaling) Choose from 68 types
- — %
30 L1 alarm enable Disable / Enable — Enable
31 L1 alarm setpoint -99999 – 999999
- — 20.00
32 L1 trip action High / Low — Low
33 L1 deadband 0 – 999999
- — 0.01
34 L1 coil at alarm Energized / De-energized — Energized
40 L2 alarm enable Disable / Enable — Enable
41 L2 alarm setpoint -99999 – 999999
- — 80.00 (2 points alarm) 30.00 (4 points alarm)
42 L2 trip action High / Low — High (2 points alarm)
Low (4 points alarm) 43 L2 deadband 0 – 999999 * — 0.01
44 L2 coil at alarm Energized / De-energized — Energized
50 L3 alarm enable Disable / Enable — Enable
51 L3 alarm setpoint -99999 – 999999
- — 70.00
52 L3 trip action High / Low — High
53 L3 deadband 0 – 999999
- — 0.01
54 L3 coil at alarm Energized / De-energized — Energized
60 L4 alarm enable Disable / Enable — Enable
61 L4 alarm setpoint -99999 – 999999
- — 80.00
62 L4 trip action High / Low — High
63 L4 deadband 0 – 999999
- — 0.01
64 L4 coil at alarm Energized / De-energized — Energized
70 Alarm ON-delay time 0 – 999 sec. 0 71 Power ON-delay time 0 – 999 sec. 5
72 Latching alarm Disable / Enable — Disable
89 Alarm test — — Cancel
Option 79 Filter time constant 0 – 30 sec. 0 80 Input Zero /f_i ne adjust -5.000 – 5.000 % 0.000 81 Input Span /f_i ne adjust 95.000 – 105.000 % 100.000
01 Lockout setting Lock / Unlock — Lock
Advanced 91 Display setting Upper: choose from 3 types Lower: choose from 5 types* — Upper: INPUT (Scaling) Lower: ALARM
92 Brightness 1 (darkest) – 4 (brightest) — 4
93 Display timeout 0 (always on), 1 – 60 min. 10
94 Reset all settings OFF / RESET — OFF
95 Version indication — — —
- For detailed setting, refer to the operating manual (EM-5146-B).
MODEL: M2EAXV M2EAXV SPECIFICATIONS ES-5146 Rev.1 Page 5/6 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 29 (1.14) 83 (3.27) 94 (3.70) (.31) 124 (4.88) 22 (.87) 6 (.23) 59 (2.32) 11–M3 SCREW 72 (2.83) 36 (1.42) 29.5 (1.16) 2–4.2x5 (.17x.20) MTG HOLE 6 (.24) deep DIN RAIL 35mm wide [4 (.16)]
- When mounting, no extra space is needed between units. 8 7 (.31) 123 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Digital Computation Circuit Digital Computation Circuit Low Drift Amplifie Low Drift Amplifie Display Circuit 23Ω CONTROL SW Display Circuit CONTROL SW RY RY RY RY RY RY ■OUTPUT CODE 2: N.O. RELAY ■OUTPUT CODE 3: N.C. RELAY ■OUTPUT CODE 5: SPDT RELAY Inductive Load (Coil) Inductive Load (Coil) Varistor or Spark Quenching Circuit 23Ω U 1CURRENT INPUT VOLTAGE INPUT 1CURRENT INPUT VOLTAGE INPUT JACK JACK CONFIGURATOR CONFIGURATOR U(+) V(–) POWER L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM Base Socket Base Socket U(+) V(–) POWER L2 OUTPUT L1 OUTPUT N.C. N.O. COM N.C. N.O. COM LOAD LOAD
- DC Powered Diode, Varistor or CR Circuit ■ Relay Protection
- AC Powered
MODEL: M2EAXV M2EAXV SPECIFICATIONS ES-5146 Rev.1 Page 6/6 http://www.m-system.co.jp/ Specifications are subject to change without notice.