MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 1/7 http://www.m-system.co.jp/ Super-mini Signal Conditioners with Display Mini-M M2E Series TWO-WIRE TRANSMITTER ALARM (PC programmable, dual or quad alarm trip) Functions & Features

  • Quad or dual trip
  • Settable with front button
  • ON delay time selectable
  • Hi/Lo trip and energized/de-energized coil independently selectable for each setpoint
  • Enclosed relays
  • Relays can be powered by 200 V AC and 100 V DC
  • Segment linearization and square root extraction configurable Typical Applications
  • Annunciator
  • Various alarm applications Mode Set Up Down (3.27) 124 (4.88) 29.5 (1.16) mm (inch) MODEL: M2EAXDY–[1]-[2][3]

ORDERING INFORMATION

  • Code number: M2EAXDY-[1]-[2][3] Specify a code from below for each [1] through [3]. (e.g. M2EAXDY-2-M2/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01/SET) INPUT – Field-selectable Current 4 – 20 mA DC (Input resistance 250 Ω) (Selectable within 0 – 20 mA DC) [1] OUTPUT 2: 4 points; N.O. or make contact 3: 4 points; N.C. or break contact 5: 2 points; SPDT or transfer contact [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-5169) Default setting will be used if not otherwise specified.

RELATED PRODUCTS

  • M2EA configurator software (model: M2EACFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual (EM-5151) for the M2EA configurator for applicable cable types. GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3 screw terminals (torque 0.8 N·m) Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (gray) Isolation: input to L1 or L4 alarm output to L2 or L3 alarm output to power (for output code 5, L3 alarm output and L4 alarm output is not available) Configuration: Program with front buttons or Via PC. Programmable features include: Refer to the parameter list. Configurator connection: 2.5 dia. miniature jack; RS-232-C level

MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 2/7 http://www.m-system.co.jp/ DISPLAY Display functions: Displays and sets measured range, engineering unit Number of pixels: 68 × 95 (horizontal × vertical) Character color: Yellow (reversing display of the current value and the alarm setting value when alarm is tripped) Display life: Approx. 60000 hours (Expected time for the Display brightness to be reduced to 50 % when the Display is used continuously with brightness setting 2 in 25 ℃) Display type: OEL display Display digit: Negative 5 digits, positive 6 digits (-99999 to 999999) Decimal point position: Selectable SUPPLY OUTPUT ■ SUPPLY OUTPUT (across the terminals 1 – 2) Output voltage: 24 – 28 V DC with no load

19 V DC minimum at 20 mA

Current rating: ≤ 22 mA DC Permissible load resistance: LR (Ω) ≤ (19 – Min. Operational Voltage)V ÷ 0.02 A

  • Shortcircuit Protection Current limited: 35 mA max. Protected time duration: No limit INPUT SPECIFICATIONS ■ DC Current Input resistance: Incorporated (250 Ω) Input range: 0 - 20 mA DC Minimum span: 1 mA DC The measurement available for -7.5 - +107.5% of input setting range. OUTPUT SPECIFICATIONS ■ Quad Alarm Relay rating: 100 V AC @ 1 A (cos ø = 1)

120 V AC @ 1 A (cos ø = 1)

240 V AC @ 0.5 A (cos ø = 1)

30 V DC @ 1 A (resistive load)

Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 120 VA or 30 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 × 107 cycles ■ DUAL ALARM Relay rating: 100 V AC @ 4 A (cos ø = 1)

120 V AC @ 4 A (cos ø = 1)

240 V AC @ 2 A (cos ø = 1)

30 V DC @ 4 A (resistive load)

Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 480 VA or 150 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 × 107 cycles 0 50 100 Input LL L HH H L2 (5–7) L3 (5–8) L4 (3–9) L1 (3–6) ON ON OFF ON ON OFF OFF OFF

  • Example Quad N.O. contacts (LL, L, H, HH) Alarm Trip Operation Terminal No. in parentheses Trip operation in power failure Output code 2 : All relays turn OFF. Output code 3 : All relays turn ON. Output code 5 : Terminals 3 – 9, 5 – 8 turn ON. LINEARIZATION ■ Linearization Types Linear: Proportional to the input Square root: The input is square root extracted. User's table: Segment linearization Calibration points: Max. 128 points; the input % and linearized value in scaling are specified in pairs. Selectable range: -7.5 to +107.5 % as input %; -99999 to +999999 as linearized values ■ Low-end Cutout:Low-end cutout (Low Cut) point selectable within the range of 0 to 100 %. With linear or segment linearization, the output signal is forcibly set to 0 % for the input lower than the low-cut point. With the square root extraction, the output signal is linear to the input when the latter is lower than the low-cut point.
  • Linear or User Table • Square Root Low-end cutout point Low-end cutout point input percent input percent INPUT LINEARIZATION INPUT LINEARIZATION INSTALLATION Power Consumption
  • AC: ≤ 7 VA at 100 V

MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 3/7 http://www.m-system.co.jp/ ≤ 10 VA at 200 V ≤ 12 VA at 264 V

  • DC: ≤ 4 W Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 10 to 85 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 200 g (0.44 lb) PERFORMANCE Accuracy (display accuracy, setting accuracy): differs depending on the linearization type. Linear: ±(0.08 % of FS + 1 digit) Square root extraction (1 % or more of input): ±(0.15 % of FS + 1 digit) Segment linearization: ±(0.08 % of FS + 1 digit) [gain ≤ 1] ±(0.08 % x gain of FS + 1 digit) [gain > 1] See CALCULATION EXAMPLES OF OVERALL ACCURACY. Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time (Filter time constant: 0 sec.): ≤ 0.5 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to L1 or L4 alarm output to L2 or L3 alarm output to power to ground) (for output code 5, L3 alarm output and L4 alarm output is not available) CALCULATION EXAMPLES OF OVERALL ACCURACY [Example] Input Range: 0 – 20 mA, Input Setting: 4 – 20 mA (when the linearization type is linear)
  • Accuracy = Input Range Span (20 mA) ÷ Input Span Setting (16 mA) × 0.08 % = ±0.1 % + 1 digit STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (output) Installation Category II (power) Pollution Degree 2 Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) L1 or L4 alarm output to L2 or L3 alarm output: Basic insulation (300 V) RoHS Directive EN 50581

MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 4/7 http://www.m-system.co.jp/ EXTERNAL VIEW Up Down Mode Set PERCENT 50.00 L4 ▲ 80.00 L3 ▲ 70.00 L2 ▼ 30.00 L1 ▼ 20.00 Display Mode Button Set Button Configurator Jack Up Button Down Button COMPONENT FUNCTION Display Indicates present values, setting values and abnormal information. çTwo types of present values at upper and lower are displayed by setting. Mode button Used to shift from measuring mode to each setting mode. çDestination to shift is changed by the time press- ing and holding the button. çUsed to return from each setting mode to measuring mode. (press and hold for 2 sec. or more) Set button Used to change setting value of setting parameter. çWhen at setting changeable state, used to enter (save) the setting value. çUsed to move on through digits of setting value for input scaling at setting changeable state. Used to release latching alarm in measuring mode (hold down more than 2 seconds). Up button Used to shift through setting parameter, and to increase or select setting value. Down button Used to shift through setting parameter, and to decrease or select setting value. Con/f_i gurator Jack Used to con/f_i gure with M2EA con/f_i gurator software (model: M2EACFG). At the same time, set the lockout setting of the unit to ‘lock’ . Refer to the operating manual (EM-5169-B) for detailed procedures.

MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 5/7 http://www.m-system.co.jp/ PARAMETER LIST MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Basic setting 01 Lockout setting Lock / Unlock — Lock 12 0 % input setting 0.00 – 19.00 mA 4.00 13 100 % input setting 1 .00 – 20.00 mA 20.00 14 0 % input scaling -99999 – 999999 — 0.00 15 100 % input scaling -99999 – 999999 — 100.00

16 Input decimal point No decimal point

The number of decimal places : 1 – 5 — 2 places of decimals

17 Unit (INP Scaling) Choose from 68 types

  • — %

24 Low cut Enable / Disable — Disable

25 Low cut point 0.00 – 100.00 % 0.00

30 L1 alarm enable Enable /Disable — Enable

31 L1 alarm setpoint -99999 – 999999 — 20.00

32 L1 trip action High / Low — Low

33 L1 deadband 0 – 999999 — 0.01

34 L1 coil at alarm Energized / De-energized — Energized

40 L2 alarm enable Enable / Disable — Enable

41 L2 alarm setpoint -99999 – 999999 — 80.00 (2 points alarm) 30.00 (4 points alarm)

42 L2 trip action High / Low — High (2 points alarm)

Low (4 points alarm) 43 L2 deadband 0 – 999999 — 0.01

44 L2 coil at alarm Energized / De-energized — Energized

50 L3 alarm enable Enable / Disable — Enable

51 L3 alarm setpoint -99999 – 999999 — 70.00

52 L3 trip action High / Low — High

53 L3 deadband 0 – 999999 — 0.01

54 L3 coil at alarm Energized / De-energized — Energized

60 L4 alarm enable Enable / Disable — Enable

61 L4 alarm setpoint -99999 – 999999 — 80.00

62 L4 trip action High / Low — High

63 L4 deadband 0 – 999999 — 0.01

64 L4 coil at alarm Energized / De-energized — Energized

70 Alarm ON-delay time 0 – 999 sec. 0 71 Power ON-delay time 0 – 999 sec. 5

72 Latching alarm Enable / Disable — Disable

89 Alarm test — — Cancel

Option 79 Filter time constant 0 – 30 sec. 0 80 Input Zero /f_i ne adjust -5.000 – 5.000 % 0.000 81 Input Span /f_i ne adjust 95.000 – 105.000 % 100.000

01 Lockout setting Lock / Unlock — Lock

Advanced 91 Display setting Upper: choose from 3 types Lower: choose from 5 types* — Upper: INPUT (Scaling) Lower: ALARM

92 Brightness 1 (darkest) – 4 (brightest) — 4

93 Display timeout 0 (always on), 1 – 60 min. 10

94 Reset all settings OFF / RESET — OFF

95 Version indication — — —

Linearization 100 Linearization Linear, Square root, User’s table — Linear

166 Number of points 2 – 128 — 2

167 – 422 Table -7 .50 – 107 .50 (X) -99999 – 999999 (Y) % (X) — (Y) X001 -7 .50 Y001 -7 .50 X002 107 .50 Y002 107 .50

  • For detailed types, refer to the operating manual (EM-5169-B).

MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 6/7 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 29 (1.14) 83 (3.27) 94 (3.70) (.31) 124 (4.88) 22 (.87) 6 (.23) 59 (2.32) 11–M3 SCREW 72 (2.83) 36 (1.42) 29.5 (1.16) 2–4.2x5 (.17x.20) MTG HOLE 6 (.24) deep DIN RAIL 35mm wide [4 (.16)]

  • When mounting, no extra space is needed between units. 8 7 (.31) 123

MODEL: M2EAXDY M2EAXDY SPECIFICATIONS ES-5169 Rev.1 Page 7/7 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM No Connection INPUT ■ When 24V DC is Not Used ■ OUTPUT CODE 5: SPDT Relay Base Socket Base Socket ■ OUTPUT CODE 2: N.O. Relay ■ OUTPUT CODE 3: N.C. Relay 50 Ω 200Ω RY RY RY RY RY RY 24V DC Supply Shortcircui Portection1 50 Ω 200Ω 200Ω 50 Ω CONFIGURATOR JACK 2-WIRE TRANSMITTER V – (1 – 5V DC) MONITOR CONFIGURATOR JACK 2-WIRE TRANSMITTER V – (1 – 5V DC) MONITOR Digital Computation Circuit Display Circuit CONTROL SW 24V DC Supply Shortcircui Portection Digital Computation Circuit Display Circuit CONTROL SW L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM L4 OUTPUT L1 OUTPUT COM L3 OUTPUT L2 OUTPUT COM U(+) V(–) POWER L2 OUTPUT L1 OUTPUT N.C. N.O. COM N.C. N.O. COM U(+) V(–) POWER Inductive Load (Coil) Inductive Load (Coil) Varistor or Spark Quenching Circuit U LOAD LOAD

  • DC Powered Diode, Varistor or CR Circuit ■ Relay Protection
  • AC Powered Specifications are subject to change without notice.