MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 1/10 https://www.m-system.co.jp/ Multi-output Super-mini Signal Conditioners with Display M1E-1 Series DC ALARM (PC programmable, quad or octad alarm trip) Functions & Features
- Provides relay outputs at preset DC input levels
- Octad or quad trip
- Front LCD display indicating values in scaled engineering unit range is used to program the module
- Adjustable deadband (hysteresis)
- ON delay time selectable
- Hi/Lo trip and energized/de-energized coil independently selectable for each setpoint
- Settable with front buttons
- Enclosed relays
- Relays can be powered by 200 V AC and 100 V DC
- High-density mounting on DIN rail Typical Applications
- Annunciator
- Various alarm applications 36 (1.42) (3.90) 125 (4.92) mm (inch) Note: The /f_igure shows the combination of the unit and the base. MODEL: M1EAXV–1-[1]-R[2]
ORDERING INFORMATION
- Code number: M1EAXV-1-[1]-R[2] Specify a code from below for each of [1] and [2]. (e.g. M1EAXV-1-A-R/Q)
- Specify the specification for option code /Q (e.g. /C01/SET) NO. OF CHANNELS 1: 1 channel INPUT – Field-selectable ◆ DC Input
- Current input: 0 - 50 mA DC
- Voltage input: -1000 - +1000 mV DC
- Voltage input: -10 - +10 V DC [1] OUTPUT A: 8 points; N.O. or make contact B: 8 points; N.C. or break contact C: 4 points; SPDT or transfer contact POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-6031)
RELATED PRODUCTS
- Installation base (model: M1E-BS2)
- M1EA configurator software (model: M1EACFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual (EM-5994) for the M1EA configurator for applicable cable types. GENERAL SPECIFICATIONS Construction: Plug-in Connection
- Connected to base with connector
- Base M2.6 screw terminals (torque: 0.5 N·m) Applicable solderless terminal size (M3) Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (black) Isolation:
- Output code A, B: Input to L1 or L2 alarm output to L3 or
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 2/10 https://www.m-system.co.jp/ L4 alarm output to L5 or L6 alarm output to L7 or L8 alarm output to power
- Output code C: Input to L1 alarm output to L2 alarm output to L3 alarm output to L4 alarm output to power Configuration: Program with front buttons or Via PC. Programmable features include: Refer to the parameter list. Configurator connection: 2.5 dia. miniature jack; RS-232-C level ■Recommended solderless terminal size - M3 (unit: mm) 12max 6max 3max 4min 3.2 dia. (mm) DISPLAY Display functions: Displays and sets measured range, engineering unit Number of pixels: 68 × 95 (horizontal × vertical) Character color: Yellow (reversing display of the current value and the alarm setting value when alarm is tripped) Display life: Approx. 50000 hours (Expected time for the Display brightness to be reduced to 50 % when the Display is used continuously with brightness setting 2 in 25 ℃) Display type: OEL display Display digit: Negative 5 digits, positive 6 digits (-99999 to 999999) Decimal point position: Selectable INPUT SPECIFICATIONS ■ DC Current Input resistance: Incorporated (28 Ω) Input range: 0 - 50 mA DC Minimum span: 2 mA The measurement available for -5 - +105% of input setting range. ■ DC Voltage
- Narrow Spans (mV) Input range: -1000 – +1000 mV DC Minimum span: 100 mV
- Wide Spans (V) Input range: -10 – +10 V DC Minimum span: 1 V Input resistance: 1 MΩ minimum The measurement available for -5 - +105% of input setting range. OUTPUT SPECIFICATIONS Relay rating: 100 V AC @ 0.5 A (cos ø = 1) 120 V AC @ 0.5 A (cos ø = 1) 240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC Maximum switching power: 120 VA or 30 W Minimum load: 5 V DC @ 1 mA Mechanical life: 5 × 107 cycles LL L HH H Input
- Example Quad N.O. contacts (LL, L, H, HH) Alarm Trip Operation Trip operation in power failure Output code A: All relays turn OFF. Output code B: All relays turn ON. Output code C: Terminals 13 – 15, 16 – 18, 6 – 12, 1 – 7 turn ON. 0 50 100 ▲ ▲ ▲ ▲ L1 ON ON OFF ON ON OFF OFF OFF INSTALLATION Power consumption
- DC: ≤ 6 W Operating temperature: -5 to +55°C (23 to 131°F) Storage temperature: -5 to +55°C (23 to 131°F) Operating humidity: 10 to 85 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 150 g (0.33 lb) except base PERFORMANCE in percentage of FS input Accuracy (display accuracy, setting accuracy): ± (0.1% of FS + 1 digit) See CALCULATION EXAMPLES OF OVERALL ACCURACY. Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time (Filter time constant: 0 sec.): ≤ 0.5 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:
- Output code A, B: 1500 V AC @ 1 minute (Input to L1 or L2 alarm output to L3 or L4 alarm output to L5 or L6 alarm output to L7 or L8 alarm output to power to ground)
- Output code C: 1500 V AC @ 1 minute (Input to L1 alarm output to L2 alarm output to L3 alarm output to L4 alarm output to power to ground
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 3/10 https://www.m-system.co.jp/ CALCULATION EXAMPLES OF OVERALL ACCURACY [Example] Input Range -10 – +10 V, Input Setting -5 – +5 V
- Accuracy = Input Range Span (20 V) ÷ Input Span Setting STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (output) Pollution Degree 2
- Output code A, B Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) L1 or L2 alarm output to L3 or L4 alarm output to L5 or L6 alarm output to L7 or L8 alarm output: Basic insulation (300
- Output code C Input or output to power: Reinforced insulation (300 V) Input to output: Basic insulation (300 V) L1 alarm output to L2 alarm output to L3 alarm output to L4 alarm output: Basic insulation (300 V) RoHS Directive
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 4/10 https://www.m-system.co.jp/ EXTERNAL VIEW Mode Button Set Button Display Configurator Jack Up Button Down Button COMPONENT FUNCTION Display Indicates present values, setting values and abnormal information. Two types of present values at upper and lower are displayed by setting. Mode button Used to shift from measuring mode to each setting mode. The destination changes depending on how long the button is held down. Used to return from each setting mode to measuring mode (press and hold for 2 sec. or more). Up button Used to shift through setting parameters and to increase or select setting value. Down button Used to shift through setting parameter and to decrease or select setting value. Set button Used to change setting value of setting parameter. When at setting changeable state, used to enter (save) the setting value. Used to move through the digits of setting value at setting changeable state. Used to release latching alarm in measuring mode (press and hold for 2 sec. or more). Con/f_i gurator Jack Used to con/f_i gure with M1EA con/f_i gurator software (model: M1EACFG). At the same time, set the lockout setting of the unit to ‘lock’ . ■ COMPONENT FUNCTION Refer to the operating manual (EM-6031-B) for detailed procedures.
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 5/10 https://www.m-system.co.jp/ TERMINAL ASSIGNMENTS 6 7 2 3 4 8 9 16 17 12 13 14 18 19
- OUTPUT CODE: A, B • OUTPUT CODE: C No. FUNCTION No. FUNCTION No. FUNCTION No. FUNCTION
1 COM4 (L7 , L8) 11 L5 Alarm output 1 COM4 (L4) 11 NO (L3)
2 L7 Alarm output 12 L6 Alarm output 2 NO (L4) 12 NC (L3)
3 Input voltage + 13 COM1 (L1, L2) 3 Input voltage + 13 COM1 (L1)
4 Input current + 14 L1 Alarm output 4 Input current + 14 NO (L1)
5 Input – 15 L2 Alarm output 5 Input – 15 NC (L1)
6 COM3 (L5, L6) 16 COM2 (L3, L4) 6 COM3 (L3) 16 COM2 (L2)
7 L8 Alarm output 17 L3 Alarm output 7 NC (L4) 17 NO (L2)
8 No connection 18 L4 Alarm output 8 No connection 18 NC (L2)
9 No connection 19 Power + 9 No connection 19 Power +
10 No connection 20 Power – 10 No connection 20 Power –
- Base does not come with the unit. Please order separately.
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 6/10 https://www.m-system.co.jp/ PARAMETER LIST The following parameters can be set or checked, by the front button operation, or from the PC by using M1EA con/f_i guration software (model: M1EACFG). MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Input setting 01 Lockout setting Lock / Unlock — Lock
11 Input range 0 – 50 mA
-1000 – +1000 mV -10 – +10 V — 0 – 50 mA 12 0 % input setting 0.00 – 48.00 -1000.0 – 900.0 -10.000 – 9.000 mA mV V 4.00 13 100 % input setting 2.00 – 50.00 -900.0 – 1000.0 -9.000 – 10.000 mA mV V 20.00 14 0 % input scaling -99999 – 999999 — 0.00 15 100 % input scaling -99999 – 999999 — 100.00
16 Input decimal point No decimal point
The number of decimal places : 1 – 5 — 2 places of decimals
17 Unit (INP Scaling) Choose from 68 types
- — % 79 Filter time constant 0 – 30 sec. 0 80 Input Zero /f_i ne adjust -5.000 – 5.000 % 0.000 81 Input Span /f_i ne adjust 95.000 – 105.000 % 100.000 Alarm setting 30 L1 alarm enable Disable / Enable — Enable
31 L1 alarm setpoint -99999 – 999999
- — 10.00
32 L1 trip action High / Low — Low
33 L1 deadband 0 – 999999
- — 0.01
34 L1 coil at alarm Energized / De-energized — Energized
40 L2 alarm enable Disable / Enable — Enable
41 L2 alarm setpoint -99999 – 999999
- — 30.00 (4 points alarm) 20.00 (8 points alarm)
42 L2 trip action High / Low — Low
43 L2 deadband 0 – 999999
- — 0.01
44 L2 coil at alarm Energized / De-energized — Energized
50 L3 alarm enable Disable / Enable — Enable
51 L3 alarm setpoint -99999 – 999999
- — 70.00 (4 points alarm) 30.00 (8 points alarm)
52 L3 trip action High / Low — High (4 points alarm)
Low (8 points alarm) 53 L3 deadband 0 – 999999 * — 0.01
54 L3 coil at alarm Energized / De-energized — Energized
60 L4 alarm enable Disable / Enable — Enable
61 L4 alarm setpoint -99999 – 999999
- — 90.00 (4 points alarm) 40.00 (8 points alarm)
62 L4 trip action High / Low — High (4 points alarm)
Low (8 points alarm) 63 L4 deadband 0 – 999999 * — 0.01
64 L4 coil at alarm Energized / De-energized — Energized
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 7/10 https://www.m-system.co.jp/ MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Alarm setting 130 L5 alarm enable Disable / Enable — Enable 131 L5 alarm setpoint -99999 – 999999 * — 60.00
132 L5 trip action High / Low — High
133 L5 deadband 0 – 999999 * — 0.01
134 L5 coil at alarm Energized / De-energized — Energized
140 L6 alarm enable Disable / Enable — Enable
141 L6 alarm setpoint -99999 – 999999 * — 70.00
142 L6 trip action High / Low — High
143 L6 deadband 0 – 999999 * — 0.01
144 L6 coil at alarm Energized / De-energized — Energized
150 L7 alarm enable Disable / Enable — Enable
151 L7 alarm setpoint -99999 – 999999 * — 80.00
152 L7 trip action High / Low — High
153 L7 deadband 0 – 999999 * — 0.01
154 L7 coil at alarm Energized / De-energized — Energized
160 L8 alarm enable Disable / Enable — Enable
161 L8 alarm setpoint -99999 – 999999 * — 90.00
162 L8 trip action High / Low — High
163 L8 deadband 0 – 999999 * — 0.01
164 L8 coil at alarm Energized / De-energized — Energized
70 Alarm ON-delay time 0 – 999 sec. 0 71 Power ON-delay time 0 – 999 sec. 5
72 Latching alarm Disable / Enable — Disable
89 Alarm test — — Cancel
01 Lockout setting Lock / Unlock — Lock
Advanced 201 Display setting Upper: choose from 4 types * Lower: choose from 5 types* — Upper: INPUT (Scaling) Lower: ALARM
203 Brightness 1 (darkest) – 4 (brightest) — 4
204 Display timeout 0 (always on), 1 – 60 min. 10
205 Reset all settings OFF / RESET — OFF
206 Version indication — — —
- For details, refer to the operating manual (EM-6031-B). EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch] 125 (4.92) 36 (1 .42) DIN RAIL 35mm wide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 * Base does not come with the unit. Please order separately.
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 8/10 https://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm [inch] 99 (3.90) 2–M4 SCREW * Mounting requirements for base.
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 9/10 https://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Front Button RY RY RY RY Low Drift Amplifier 28Ω RY RY RY RY INPUT CURRENT INPUT VOLTAGE Display Circuit Digital Computation Circuit Isolation CONFIGURATOR JACK Base L4 OUTPUT L1 OUTPUT COM1 L3 OUTPUT L2 OUTPUT COM2 L8 OUTPUT L5 OUTPUT COM3 L7 OUTPUT L6 OUTPUT COM4 POWER L4 OUTPUT L1 OUTPUT COM1 L3 OUTPUT L2 OUTPUT COM2 L8 OUTPUT L5 OUTPUT COM3 L7 OUTPUT L6 OUTPUT COM4 ■OUTPUT CODE A: N.O. RELAY ■OUTPUT CODE B: N.C. RELAY
MODEL: M1EAXV-1 M1EAXV-1 SPECIFICATIONS ES-6031 Rev.2 Page 10/10 https://www.m-system.co.jp/ Front Button Display Circuit RY RY RY RY 15 3 28Ω N.C. N.O. COM1 N.C. N.O. COM2 N.C. N.O. COM3 N.C. COM4 N.O. INPUT CURRENT INPUT VOLTAGE Isolation CONFIGURATOR JACK Base Low Drift Amplifier Digital Computation Circuit L1 OUTPUT L2 OUTPUT L3 OUTPUT L4 OUTPUT POWER
- Relay Protection
- AC Powered Inductive Load (Coil) Varistor or Spark Quenching CircuitLOAD
- DC Powered Inductive Load (Coil) Diode, Varistor or CR CircuitLOAD ■OUTPUT CODE C: SPDT RELAY U Specifications are subject to change without notice.