LTMR08CBD SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

motor controller LTMR TeSys T - 24 V DC 8 A for CANopen Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 750.00 USD Main Range TeSys Product name TeSys T Device short name LTMR Product or component type Motor controller Device application Equipment monitoring and control Measurement current 0.4…8 A [Us] rated supply voltage 24 V DC Current consumption 56...127 mA Supply voltage limits 20.4…26.24 V DC Communication port protocol CANopen Complementary [Ui] rated insulation voltage 690 V EN/IEC 60947-1 690 V CSA C22.2 No 14

690 V UL 508

[Uimp] rated impulse withstand voltage 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 0.8 kV communication circuit EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1 Short-circuit withstand 100 kA EN/IEC 60947-4-1 Associated fuse rating 4 A gG output

0.5 A gG control circuit

Protection type Overload (long time) Phase failure Load fluctuation Phase imbalance Reverse polarity protection Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Dec 24, 2020

Thermal overload protection Earth-leakage protection Power factor variation Overload Locked rotor Network and machine diagnosis type Trip context information Remaining operating time before overload tripping Starting current and time Event recording Motor control command recording Running hours counter/operating time Waiting time after overload tripping Trip history information Phase fault and earth fault trip counters Fault recording Logic input number 6 Input current 7 mA Current state 0 guaranteed Logic input < 5 V <= 15 mA 5 ms Current state 1 guaranteed Logic input < 15 V 2...15 mA 15 ms Maximum output switching frequency 2 Hz Load current 5 A 250 V AC logic output

5 A 30 V DC logic output

Permissible power 480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output) Maximum operating rate 1800 cyc/h Contacts type and composition 1 NO + 1 NC fault signal 3 NO Metering type Average current Iavg Phase current I1, I2, I3 RMS Temperature Earth-fault current Imbalance current Measurement accuracy 5...15 % earth fault current internal measurement 1 % voltage 100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 Temperature 1 % current 5 % active and reactive power Overvoltage category III Connection pitch 0.20 in (5.08 mm) end end end end Pollution degree 3 Electromagnetic compatibility Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) Conducted RF disturbances 10 V)EN/IEC 61000-4-6) Surges 0.5 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 1 kV)EN/IEC 61000-4-5) Surges 2 kV)EN/IEC 61000-4-5)

Surges 2 kV)EN/IEC 61000-4-5) Surges 4 kV)EN/IEC 61000-4-5) Width 3.58 in (91 mm) Height 2.40 in (61 mm) Depth 4.82 in (122.5 mm) Net Weight 1.17 lb(US) (0.53 kg) Web services Web server Compatibility code LTMR Environment Standards EN 60947-4-1 CSA C22.2 No 14 IEC 60947-4-1 UL 508 IACS E10 Product certifications ATEX C-tick EAC LROS (Lloyds register of shipping) NOM BV RINA KERI ABS UL CSA DNV RMRoS GL CCC Protective treatment 12 x 24 hour cycles EN/IEC 60068-2-30 48 h EN/IEC 60070-2-11 TH EN/IEC 60068 Fire resistance 1202 °F (650 °C) EN/IEC 60695-2-12 1760 °F (960 °C) UL 94 Ambient air temperature for operation -20…60 °C Ambient air temperature for storage -40…176 °F (-40…80 °C) Operating altitude <= 6561.68 ft (2000 m) without derating Mechanical robustness Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27 IP degree of protection IP20 Ordering and shipping details Category 22338 - SOLID STATE OVERLOAD RELAYS Discount Schedule I12 GTIN 00785901498414 Nbr. of units in pkg. 1 Package weight(Lbs) 1.12 lb(US) (0.51 kg) Returnability No Country of origin CN Packing Units Unit Type of Package 1 PCE Package 1 Height 2.76 in (7 cm) Package 1 width 3.94 in (10 cm) Package 1 Length 5.31 in (13.5 cm) Unit Type of Package 2 S02 Number of Units in Package 2 10

Package 2 Weight 12.02 lb(US) (5.452 kg) Package 2 Height 5.91 in (15 cm) Package 2 width 11.81 in (30 cm) Package 2 Length 15.75 in (40 cm) Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Compliant EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Product out of China RoHS scope. Substance declaration for your information. Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. PVC free Yes Halogen content performance Halogen free plastic parts product Contractual warranty Warranty 18 months