Features

  • Maximum Discharge Cur rent (Imax) 10kA, 8/20µs
  • Meets ANSI C136.2 Enhanced Level 10kV/5kA, IEEE C62.41 .2 Location Category C Low Exposure and US Dept. of Energy MSSLC Model Spec. T hermally Protected Varistor technology
  • Parallel and Series Connected SPD Options
  • IP66 Water-proof and Dust-proof
  • UL1449 Recognized (120Vac, 240Vac and 277Vac only)
  • Series- connected option for 240V and 277V is IEC 61643-11 Test Class II and EN 61643-11 Type 2 compliant.
  • Outdoor and Commercial LED Lighting
  • R oadway lighting
  • T raffic lighting
  • Digit al signage
  • W all wash lighting
  • IEC CB Scheme Certificate NL -37684 available for 240V and NL -40516 for 277V Compact f orm factor with mounting tabs
  • 240V ac and 277Vac are CE compliant and available for Class I and Class II installation based on IEC luminaire protection classes Series connected – V aristor thermal protection indication by removal of power to luminaire High line-to-earth/ ground resist ance
  • R ohS compliant
  • P arking garage lighting
  • Flood lighting
  • T unnel lighting
  • Street lighting Datasheet Samples Resources Absolute Maximum Ratings
  • For ratings of individual members of a series, see Device Ratings and Specifications chart CAUTION: Stresses above those listed in "Absolute Maximum Ratings" may cause permanent damage to the device. This is a stress only rating and operation of the device at these or any other conditions above those indicated in the operational sections of this specification is not implied. LSP05G Series Units Continous: Max AC Voltage Range (VM(AC)RMS) 150 to 510 V Continuous Cur rent 5 A Transient: Maximum Disc harge Current, 8/20μs Waveform (Imax) 10,000 A Nominal Disc harge Current, 8/20µs Waveform (In) 5,000 A Operating Ambient Temperature Range (TA) -45 to +85 °C Storage Temperature Range (TSTG) -45 to +90 °C Isolation Voltage Capability (When the thermal disconnect opens) 600 V Insulation Resistance >1,000 MΩ Agency Standard Agency File Number UL1449 for 120V , 240V , 277V Only E320116 Littelfuse’s LSP05G thermally protected Surge Protective Device is a self-protected device specially designed to be used in outdoor and commercial LED lighting fixtures for transient overvoltage protection. It has been developed with Littelfuse’s thermally protected varistor technology. Its built-in thermal disconnect function provides additional protection to prevent catastrophic failure and fire hazard even under extreme circumstances of varistor end-of-life or sustaining over voltage conditions. It also provides high line-to-earth/ ground resistance, facilitating faster production line testing. LSP05G series connected option allows clear indication of thermal fault protection by disconnecting power to luminaire, thereby signaling SPD module replacement. The LSP05G Surge Protective Device facilitates customer’s product compliance to IEEE C62.41.2 Location Category C Low ANSI C136.2 and US Dept. of Energy MSSLC Model Spec.

LED Lighting Surge Protection Module > LSP05G © 2016 Littelfuse, Inc. Specifications are subject to change without notice. Revised: 11/03/16 * = S or P † with 1500Vac Hi-Pot withstand capability in common mode (L -G and N-G) Glossary: 2. Maximum Discharge Current Imax (A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of discharge current uses the 8/20µs current waveform. 3. Nominal Discharge Current In (A): The nominal discharge current is a measure of the SPDs endurance capability; 15 impulses of discharge current uses the 8/20µs current waveform. 4. MLV: UL1449 Measured limiting voltage; the highest value of residual voltage measurements during the application of impulses of 8/20µs nominal discharge current (In); an average voltage value of 15 impulses 5. Up: IEC 61643-11 Voltage protection level; the highest value of residual voltage measurements during the application of impulses of 8/20µs nominal discharge current (In); a rounding voltage value of maximum measurement. 6. Series module used in parallel connection for indication circuit connection. 7 . LSP05G240S & LSP05G277S are certified by DEKRA with below IEC 61643-11 specifications LSP05G Series Device Ratings & Specifications Part Number Operating Voltage (VAC) MCOV/UC1 (VAC) Maximum Discharge Current2 Imax (A) Nominal Discharge Current3 In (A) Typical MLV4 (V) Typical Up (V) Safety Compliance IEC/EN 61643-1 16 & 7 UL1449 LSP05G120* 120 150 10,000 5,000 L -N:600 L -G:1410 N-G:1410 L -N:700 L -G:1600 N-G:1600 X LSP05G240* 240 275 10,000 5,000 L -N:970 L -G:1410 N-G:1410 L -N:1100 L -G:1600 N-G:1600 X X LSP05G277* 277 320 10,000 5,000 L -N: 1130 L -G: 1410 N-G:1410 L -N: 1200 L -G: 1600 N-G:1600 X X LSP05G347* 347 420 10,000 5,000 L -N: 1530 L -G: 1550 N-G: 1410 L -N: 1600 L -G: 1700 N-G: 1600 LSP05G480* 480 510 10,000 5,000 L -N: 1800 L -G: 1900 N-G: 1410 L -N: 2100 L -G: 2000 N-G: 1600 LSP05G480*H† 480 510 10,000 5,000 L -N: 1800 L -G: 3090 N-G: 3090 L -N: 2100 L -G: 3700 N-G: 3700 LSP05G240S Specification Parameter Value Unit Condition Temporary overvoltage TOV UT 337 V LV system fault 255 V x 1 .32 at tT = 5 s, TN power grid Temporary overvoltage TOV UT 442 V LV system fault 255 V x 1 .732 at tT = 120 min, TN power grid Power grids TN Backup fuse 16 A max., gG fuse End of life indication yes Optical, light ON: SPD is functional Light OFF: SPD has reached end-of-life Max earth leakage current at Uc 50 µA Max. rms, to GND LSP05G277S Specification Parameter Value Unit Condition Temporary overvoltage TOV UT 403 V LV system fault 305 V x 1 .32 at tT = 5 s, TN power grid Temporary overvoltage TOV UT 529 V LV system fault 305 V x 1 .732 at tT = 120 min, TN power grid Power grids TN Backup fuse 20 A max., gG fuse End of life indication yes Optical, light ON: SPD is functional Light OFF: SPD has reached end-of-life

LED Lighting Surge Protection Module > LSP05G © 2016 Littelfuse, Inc. Specifications are subject to change without notice. Revised: 11/03/16 Dimensions Series Version Parallel Version Notes: 1 . Black: Line; White: Neutral; Green: Ground. (P/N with suffix X3333/X3316: Brown: Line; Blue: Neutral; Green-Y ellow stripe: Ground) 2. Wire Gauge: AWG16, wire length: 100mm±20mm, wire stripping length:10±2mm. 3. Caution: Line/neutral wires must be correctly connected to AC power grid. Wiring error on line/neutral polarity may cause module failure. Repetitive Surge Capability 104 105 106 103 102 10 100 1,000 10,000 IMPULSE DURATION (/uni03BCs) 100,000 10,000 100 SURGE CURRENT (A) MODEL SIZE = 20mm 130 to 625V M(AC) RATING TA = -55oC TO 85oC 1,000 Pulse Rating (8x20µSec) Strikes Surge 1 10,000A 2 7 ,000A 15 5,000A 100 1,500A 1,000 700A

LED Lighting Surge Protection Module > LSP05G © 2016 Littelfuse, Inc. Specifications are subject to change without notice. Revised: 11/03/16 Part Numbering System LSP 05G 120 P N H Xxxxx Littelfuse Surge Protection Module 5kA (Nominal Discharge Current) Operating Voltage P: Parallel connection S: Series connection Blank: Waterproof IP66 N: Non-waterproof Blank: No Hi-Pot withstand capability in common mode H: With 1500Vac Hi-Pot withstand capability in common mode (L-G and N-G) X3316: without GND wire connection, available for 240Vac and 277Vac rating with CE Marking for Class II unearthed luminaire installation Wire Color: Line: Brown, Neutral: Blue X3379: Input wire length: 110mm +/-10mm, output wire length: 210mm+/-10mm Product is CE Marked for Class I earthed Luminaire installation and Class II unearthed Luminaire installation (if earth connection is not utilized). Other Options: X3333: with GND wire connection, avail- able for 240Vac and 277Vac rating with CE Marking for Class I earthed luminaire installation Wire Color: Line: Brown, Neutral: Blue, Ground/P: Green with yellow stripe Application/Installation Schematic L N G SPD L L N/G or AC/DC Power Supply LED Module L N Parallel Connection L N G SPD L L N/G or LED Module L N LED normally on Parallel Connection With LED indicating SPD status - ON (green): SPD is online - OFF: SPD needs replacement LSP10xxxS LSP10xxxS AC/DC Power Supply R L N G SPD LED Module L N Parallel Connection (for Class II Unearthed) AC/DC Power Supply ~X3316 L N G SPD LED Module L N Series Connection (for Class II Unearthed) ~X3316 AC/DC Power Supply L N G SPD SPD L L N/G or LED Module L N Series Connection Notes: 1 . Series module used in parallel connection for indication circuit connection. 2. LED indicator and associated circuitry are not included in the module. 3. Black wire is AC line voltage (hot); white wire is AC neutral voltage. 4. Black wire voltage is cut off when SPD needs replacement. LSP05GxxxS LSP05GxxxP L N G SPD L L N/G or AC/DC Power Supply LED Module L N Parallel Connection L N G SPD L L N/G or LED Module L N LED normally on Parallel Connection With LED indicating SPD status - ON (green): SPD is online - OFF: SPD needs replacement LSP10xxxS LSP10xxxS AC/DC Power Supply R L N G SPD LED Module L N Parallel Connection (for Class II Unearthed) AC/DC Power Supply ~X3316 L N G SPD LED Module L N Series Connection (for Class II Unearthed) ~X3316 AC/DC Power Supply L N G SPD SPD L L N/G or LED Module L N Series Connection AC/DC Power Supply LSP05GxxxS