LHZ MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL: LHZ http://www.m-system.co.jp/ LHZ SPECIFICATIONS ES-1983 Rev.11 Page 1/3 Power Transducer Series L-UNIT FREQUENCY TRANSDUCER Functions & Features
- Providing a DC output signal in proportion to deviation (±5 Hz) from center frequency (50 Hz or 60 Hz)
- DC output containing little ripple is ideal for computer input
- Isolation up to 2000 V AC
- Highdensity mounting Typical Applications
- Centralized monitoring and control of power management system in manufacturing facility or building
- Measuring frequency for UPS (2.95) 112 (4.41) (2.95) mm (inch) MODEL: LHZ-[1][2][3]-[4][5]
ORDERING INFORMATION
- Code number: LHZ–[1][2][3]-[4][5] Specify a code from below for each [1] through [5]. (e.g. LHZ-11A-C/Q)
- Special output range (For codes Z & 0)
- Specify the specification for option code /Q (e.g. /C01/S01) [1] FREQUENCY 1: 45 – 55 Hz 2: 55 – 65 Hz 3: 45 – 65 Hz [2] INPUT 1: 110 V AC 2: 220 V AC [3] OUTPUT Current A: 4 – 20 mA DC (Load resistance 600 Ω max.) D: 0 – 20 mA DC (Load resistance 600 Ω max.) E: 0 – 16 mA DC (Load resistance 750 Ω max.) F: 0 – 10 mA DC (Load resistance 1200 Ω max.) G: 0 – 1 mA DC (Load resistance 12 kΩ max.) J: 0 – 5 mA DC (Load resistance 2400 Ω max.) Z: Specify current (See OUTPUT SPECIFICATIONS) Voltage 1: 0 – 10 mV DC (Load resistance 10 kΩ min.) 2: 0 – 100 mV DC (Load resistance 100 kΩ min.) 3: 0 – 1 V DC (Load resistance 1000 Ω min.) 4: 0 – 10 V DC (Load resistance 10 kΩ min.) 5: 0 – 5 V DC (Load resistance 5000 Ω min.) 6: 1 – 5 V DC (Load resistance 5000 Ω min.) 0: Specify voltage (See OUTPUT SPECIFICATIONS) [4] AUXILIARY POWER SUPPLY AC Power B: 100 V AC C: 110 V AC D: 115 V AC F: 120 V AC G: 200 V AC H: 220 V AC J: 240 V AC DC Power R: 24 V DC V: 48 V DC P: 110 V DC [5] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel GENERAL SPECIFICATIONS Construction: Stand-alone; terminal access at the front Connection: M3.5 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated steel (standard) or stainless steel Housing material: Flame-resistant resin (black)
MODEL: LHZ http://www.m-system.co.jp/ LHZ SPECIFICATIONS ES-1983 Rev.11 Page 2/3 Isolation: Input to output to auxiliary power Computation: One-shot Overrange output: Approx. -10 to +120 % at 1 – 5 V Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) INPUT SPECIFICATIONS Input burden: 1 VA Overload capacity: 150 % of rating for 10 sec., 120 % continuous Operational range: 85 – 120 % of rating OUTPUT SPECIFICATIONS ■ DC Current: 0 – 20 mA DC Minimum span: 1 mA Offset: Max. 1.5 times span Load resistance: Output drive 12 V max. ■ DC Voltage: 0 – 12 V DC Minimum span: 5 mV Offset: Max. 1.5 times span Load resistance: Output drive 1 mA max.; at ≥ 0.5 V OUT 20mA 55 65 Hz45 OUT 10V 55 65 Hz45 ■ OPERATION DIAGRAM (example) Remark: When there is no input voltage, the transducer outputs as negative (–) overrange. INSTALLATION Auxiliary power supply
- AC: Operational voltage range: rating -15/+10 %, 50/60 Hz, approx. 2 VA
- DC: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating, ripple 10 %p-p max., approx. 2 W (18 mA at 110 V) Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 85 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 300 g (0.66 lb) PERFORMANCE in percentage of span Accuracy: ±1 % (at 23°C ±10°C or 73.4°F ±18°F) Response time: ≤ 1 sec. (0 – 100 % ±1 %) Ripple: 0.5 %p-p max. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output to auxiliary power to ground) Impulse withstand voltage: 1.2 / 50 μsec., ±5 kV (input to output or ground)
MODEL: LHZ http://www.m-system.co.jp/ LHZ SPECIFICATIONS ES-1983 Rev.11 Page 3/3 CONNECTION DIAGRAM U V u vFUSE VT OUTPUT U(+) V(–) LOAD SOURCE *The transducer can be powered from the input voltage when the voltage is sufficiently stable and meets other supply voltage requirements. AUXILIARY POWER EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) DIN RAIL 35mm wide 8 (.31) M3.5 SCREW (Only on the used terminals) 75 (2.95) TERMINAL COVER 2–5.8 (.23) dia. or 2–4.8 (.18) dia. MTG HOLE 8 (.31) deep
- When mounting, no extra space is needed between units. 75 (2.95) 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 3 (.12) 1(.04) MOUNTING REQUIREMENTS unit: mm (inch) 2–M5 60 (2.36) 60 (2.36) ■ M5 SCREWS 2–M4 60 (2.36) 50 (1.97) ■ M4 SCREWS Specifications are subject to change without notice.