LFH250301C LITTELFUSE | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 7
Technical content
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 1 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS
250 V • 600 V
Description
The Littelfuse Class H/K5 and R blocks offer many benefits such as indication, snap-to-release DIN rail mounting and mounting flexibility for easier installation. Class H and Class R fuse blocks are dimensionally the same, but Class R blocks incorporate a rejection feature, which only allows Class R fuses to be inserted. Features/Benefits Accommodates a wide range of existing mounting configurations Indication offered on most 250 V and 600 V versions One hand release from DIN rail for ferrule style fuses Reinforced fuse clips are standard on all Class H and Class R fuse blocks Covers available for 100 A and lower to enhance safety Both hex and slot set screw options available on 60 Ampere, 600 Volt Class R box lugs Specifications Voltage Rating 250 V, 600 V Ampere Ratings 0–600 A Leakage Current <0.6 mA at 600 V Withstand Rating Class H: 10 kA RMS SYM Class R: 200 kA RMS SYM Materials: Base Thermoplastic Fuse Clip Tin plated copper alloy Box Lug Aluminum Pressure Plate Zinc plated steel Screw Zinc plated steel Flammability Rating UL94 V-0 Approvals UL Listed (File: E14721) CSA Certified (File: LR7316) Environmental RoHS Compliant, Lead (Pb) Free Recommended Fuses Class H/K5 Blocks – 250 V NLN Class R Blocks – 250 V FLNR/FLNR_ID, KLNR, LLNRK Class H/K5 Blocks – 600 V NLS Class R Blocks – 600 V FLSR/FLSR_ID, KLSR, LLSRK/LLSRK_ID, IDSR Web Resources Sample requests, downloadable CAD drawings and other technical information: Littelfuse.com/lfh Littelfuse.com/lfr
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 2 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS Ordering Information (Class H 250 V) AMP RATING ORDERING NUMBER INDICATION TORQUE WIRE RANGE WIRE TYPE BASE TEMP RATING DIN RAIL COVER ORDERING NUMBER * POLES BOX LUG HEX SCREW BOX LUG SLOT SCREW PRESSURE PLATE SCREW 1 — LFH250301C LFH250301P LFH250301S —
2.8 N-m (25 in-lbs)
6–14 AWG PRESSURE PLATE 10–14 AWG SCREW 10–22 AWG CU only Solid / Stranded 125 ˚C • LFH25030FBC2 — LFH250302C LFH250302P LFH250302S — 3 — LFH250303C LFH250303P LFH250303S — 1 — LFH250601CID — — •
5.6 N-m (50 in-lbs)
2–4 AWG 6–14 AWG CU-AL 125 ˚C • LFH25060FBC — LFH250601C — — — 2 — LFH250602CID — — • — LFH250602C — — — 3 — LFH250603CID — — • — LFH250603C — — — 100 1 LFH251001CID — — — • 13.6 N-m (120 in-lbs)
4.5 N-m (40 in-lbs)
4.0 N-m (35 in-lbs)
2/0–6 AWG
8 AWG
10–14 AWG CU-AL 130 ˚C — LFH25100FBCLFH251001C — — — —
3 LFH251003CID — — — •
LFH251003C — — — — 200 1 LFH252001C — — — — 31.1 N-m (275 in-lbs) 250 kcmil-6 CU-AL 130 ˚C — —3 LFH252003C — — — 400 1 LFH254001C — — — — 31.1 N-m (275 in-lbs) (2) 350 kcmil-1/0 CU-AL 130 ˚C — —3 LFH254003C — — — 600 1 LFH256001C — — — — 42.4 N-m (375 in-lbs) (2) 500 kcmil-4 CU-AL 130 ˚C — —3 LFH256003C — — — Note: Reinforcing springs standard on all Class H fuse blocks. *Covers sold individually. One cover needed for each pole. Ordering Information (Class H 600 V) AMP RATING ORDERING NUMBER INDICATION TORQUE WIRE RANGE WIRE TYPE BASE TEMP RATING DIN RAIL COVER ORDERING NUMBER * POLES BOX LUG HEX SCREW BOX LUG SLOT SCREW PRESSURE PLATE SCREW 1 — LFH600301CID LFH600301PID LFH600301SID • 6–14 AWG PRESSURE PLATE 10–14 AWG SCREW 10–22 AWG CU only Solid / Stranded 130 ˚C • LFH60030FBC — LFH600301C LFH600301P LFH600301S — 2 — LFH600302CID LFH600302PID LFH600302SID • — LFH600302C LFH600302P LFH600302S — 3 — LFH600303CID LFH600303PID LFH600303SID • — LFH600303C LFH600303P LFH600303S — 1 — LFH600601CID — — — 2–4 AWG 6–14 AWG CU-AL 130 ˚C • LFH60060FBC — LFH600601C — — • 2 — LFH600602CID — — — — LFH600602C — — • 3 — LFH600603CID — — — — LFH600603C — — • 100 1 LFH601001CID — — — — 13.6 N-m (120 in-lbs) 2/0–6 AWG 10–14 AWG CU-AL 130 ˚C — LFH60100FBCLFH601001C — — — •
3 LFH601003CID — — — —
LFH601003C — — — • 200 1 LFH602001C — — — — 31.1 N-m (275 in-lbs) 250 kcmil-6 CU-AL 130 ˚C — —3 LFH602003C — — — 400 1 LFH604001C — — — — 31.1 N-m (275 in-lbs) (2) 350 kcmil-1/0 CU-AL 130 ˚C — —3 LFH604003C — — — 600 1 LFH606001C — — — — 42.4 N-m (375 in-lbs) (2) 500 kcmil-4 CU-AL 130 ˚C — —3 LFH606003C — — — Note: Reinforcing springs standard on all Class H fuse blocks. *Covers sold individually. One cover needed for each pole.
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 3 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS Ordering Information (Class R 250 V) AMP RATING ORDERING NUMBER INDICATION TORQUE WIRE RANGE WIRE TYPE BASE TEMP RATING DIN RAIL COVER ORDERING NUMBER * POLES BOX LUG HEX SCREW BOX LUG SLOT SCREW PRESSURE PLATE SCREW 1 — LFR250301C LFR250301P LFR250301S — 6–14 AWG PRESSURE PLATE 10–14 AWG SCREW 10–22 AWG CU only Solid / Stranded 125 ˚C • LFH25030FBC2 — LFR250302C LFR250302P LFR250302S — 3 — LFR250303C LFR250303P LFR250303S — 1 — LFR250601CID — — • 2–4 AWG 6–14 AWG CU-AL 125 ˚C • LFH25060FBC — LFR250601C — — — 2 — LFR250602CID — — • — LFR250602C — — — 3 — LFR250603CID — — • — LFR250603C — — — 100 1 LFR251003CID — — — • 13.6 N-m (120 in-lbs)
4.0 N-m (35 in-lbs
2/0–6 AWG 10–14 AWG CU-AL 130 ˚C — LFH25100FBCLFR251003C — — — —
3 LFR251001CID — — — •
LFR251001C — — — — 200 1 LFR252001C — — — — 31.1 N-m (275 in-lbs) 250 kcmil-6 CU-AL 130 ˚C — —3 LFR252003C — — — 400 1 LFR254001C — — — — 31.1 N-m (275 in-lbs) (2) 350 kcmil-1/0 CU-AL 130 ˚C — —3 LFR254003C — — — 600 1 LFR256001C — — — — 42.4 N-m (375 in-lbs) (2) 500 kcmil-4 CU-AL 130 ˚C — —3 LFR256003C — — — Note: Reinforcing springs standard on all Class H fuse blocks. *Covers sold individually. One cover needed for each pole. Ordering Information (Class R 600 V) AMP RATING ORDERING NUMBER INDICATION TORQUE WIRE RANGE WIRE TYPE BASE TEMP RATING DIN RAIL COVER ORDERING NUMBER * POLES BOX LUG HEX SCREW BOX LUG SLOT SCREW PRESSURE PLATE SCREW 1 — LFR600301CID LFR600301PID LFR600301SID • 6–14 AWG PRESSURE PLATE 10–14 AWG SCREW 10–22 AWG CU only Solid / Stranded 130 ˚C • LFH60030FBC — LFR600301C LFR600301P LFR600301S — 2 — LFR600302CID LFR600302PID LFR600302SID • — LFR600302C LFR600302P LFR600302S — 3 — LFR600303CID LFR600303PID LFR600303SID • — LFR600303C LFR600303P LFR600303S —
1 LFR600601CID-HX LFR600601CID — — •
2–4 AWG 6–14 AWG CU-AL 130 ˚C • LFH60060FBC - LFR600601C — — —
2 LFR600602CID-HX LFR600602CID — — •
- LFR600602C — — —
3 LFR600603CID-HX LFR600603CID — — •
- LFR600603C — — — 100 1 LFR601001CID — — — • 13.6 N-m (120 in-lbs)
2/0–6 AWG 10–14 AWG CU-AL 130 ˚C — LFH60100FBCLFR601001C — — — —
3 LFR601003CID — — — •
LFR601003C — — — — 200 1 LFR602001C — — — — 31.1 N-m (275 in-lbs) 250 kcmil-6 CU-AL 130 ˚C — —3 LFR602003C — — — 400 1 LFR604001C — — — — 31.1 N-m (275 in-lbs) (2) 350 kcmil-1/0 CU-AL 130 ˚C — —3 LFR604003C — — — 600 1 LFR606001C — — — — 42.4 N-m (375 in-lbs) (2) 500 kcmil-4 CU-AL 130 ˚C — —3 LFR606003C — — — Note: Reinforcing springs standard on all Class H fuse blocks. *Covers sold individually. One cover needed for each pole.
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 4 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH25030C Littelfuse ® REVISION DRWG NO. TITLE C DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH25030-C SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 3/15/2011 501851ERP - RELEASE MRY 31.9 [1.26] 28.6 [1.13] 48.5 [1.91] 6.8 [.27] 74.7 [2.94] 40.1 [1.58] 8.4 [.33]5.6 [.22] R2.8 [.11] TYP n5.6 THRU [n.22 THRU] R2.8 [.11] TYP SPECIFICATIONS: VOLTAGE RATING: 250V AMPERE RATING: 30 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 2.8 N-m (25 IN-LBS) WIRE RANGE: 6-14 AWG Cu ONLY SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. LR7316) SERIES 76.5 [3.01] 3.6 [.14] 38.2 [1.51] 44.6 [1.76] 4.8 [.19] 13.0 [.51] 15.6 [.61] 23.8 [.94] 16.3 [.64] 32.2 [1.27] 15.9 [.63] 31.8 [1.25] 42.9 [1.69] R2.8 [.11] TYP DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH25060 Series Littelfuse ® REVISION DRWG NO. TITLE C DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH25060 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 3/15/2011 501851ERP - RELEASE MRY 119.7 [4.71] 37.3 [1.47] 57.4 [2.26] 24.9 [.98] R2.8 [.11] TYP SPECIFICATIONS: VOLTAGE RATING: 250V AMPERE RATING: 60 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 5.6 N-m (50 IN-LBS) 2-4 AWG
2.8 N-m (25 IN-LBS) 6-14 AWG
WIRE RANGE: 2-14 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. LR7316) 43.9 [1.73] 75.7 [2.98] 9.7 [.38] 14.8 [.58] 22.4 [.88] 55.8 [2.20] 43.1 [1.70] 5.5 [.21] 89.2 [3.51] 76.5 [3.01] 43.9 [1.73] 75.7 [2.98] R2.8 [.11] TYP R2.8 [.11] TYP DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION B OL-LFH25100 Littelfuse ® REVISION DRWG NO. TITLE C DRW DATE GRAMS/PIECE FINISH GOOD WT MYORK 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH25100 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 3/15/2011 501851ERP - RELEASE MRY B 12/8/2016 516738ECP/D - ADD TOLERANCES MRY 177.8 0.50 7.00 0.02[ ] R3.4 [.13] TYP SPECIFICATIONS: VOLTAGE RATING: 250V AMPERE RATING: 100 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 13.6 N-m (120 IN-LBS) 2/0-6 AWG
4.5 N-m (40 IN-LBS) 8 AWG
4.0 N-m (35 IN-LBS) 10-14 AWG
WIRE RANGE: 2/0-14 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. LR7316) 53.6 0.50 2.11 0.02[ ] 72.6 0.50 2.86 0.02[ ] 133.0 0.50 5.23 0.02[ ] 53.6 0.50 2.11 0.02[ ] 72.6 0.50 2.86 0.02[ ] 133.0 0.50 5.23 0.02[ ] R3.4 [.13] TYP
250 V 30 A
250 V 60 A
250 V 100 A
Dimensions mm (inches)
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 5 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH25200 Series Littelfuse ® REVISION DRWG NO. TITLE D DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LF25200 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 5/24/2011 501832ERP - RELEASE MRY 181.1 [7.13] 76.2 [3.00] 228.6 [9.00] n8.6 THRU [n.34 THRU] 72.4 [2.85] 15.9 [.63] n8.7 THRU v n19.1 x 10.2 n.34 THRU v n.75 x .40[] R4.3 [.17] TYP 63.5 [2.50] 12.7 [.50] SPECIFICATIONS: VOLTAGE RATING: 250V AMPERE RATING: 200 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 31.1 N-m (275 IN-LBS) WIRE RANGE: 250kcmil-6 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. 007316_0_000) 63.5 [2.50] 52.6 [2.07] 128.5 [5.06] 12.7 [.50] 19.1 [.75] 165.1 [6.50] 184.2 [7.25] 215.9 [8.50] 52.5 [2.07] 128.7 [5.07] n19.1 x 9.5 [n.75 x .38] n8.6 THRU [n.34 THRU] DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH25400 Series Littelfuse ® REVISION DRWG NO. TITLE D DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH25400 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 5/24/2011 501832ERP - RELEASE MRY 88.9 [3.50] 292.1 [11.50] 95.3 [3.75] 15.9 [.63] 266.7 [10.50] n8.6 THRU v n19.1 x 11.2 n.34 THRU v n.75 x .44[] n8.6 THRU v n19.1 x 11.2 n.34 THRU v n.75 x .44[] 84.4 [3.32] 15.9 [.63] SPECIFICATIONS: VOLTAGE RATING: 250V AMPERE RATING: 400 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 31.1 N-m (275 IN-LBS) WIRE RANGE: 350kcmil-1/0 Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. 007316_0_000) 108.0 [4.25] 184.2 [7.25] 22.2 [.88] 66.7 [2.63] 95.3 [3.75] 196.9 [7.75] 15.9 [.63] 250.8 [9.88] DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH25600 Series Littelfuse ® REVISION DRWG NO. TITLE D DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH25600 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 5/24/2011 501832ERP - RELEASE MRY 355.6 [14.00] 114.3 [4.50] 114.3 [4.50] 317.5 [12.50] 19.1 [.75] 114.3 [4.50] n7.1 THRU v n14.2 x 11.2 n.28 THRU v n.56 x .44[] 110.6 [4.35] 15.9 [.63] n7.1 THRU v n14.2 x 11.2 n.28 THRU v n.56 x .44[] n8.6 THRU v n19.1 x 11.2 n.34 THRU v n.75 x .44[] SPECIFICATIONS: VOLTAGE RATING: 250V AMPERE RATING: 600 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 42.4 N-m (375 IN-LBS) WIRE RANGE: 500kcmil-4 Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. 007316_0_000) 139.7 [5.50] 215.9 [8.50] 19.1 [.75] 34.9 [1.38] 79.4 [3.13] 241.3 [9.50] 298.5 [11.75]
250 V 200 A
250 V 400 A
250 V 600 A
Dimensions mm (inches)
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 6 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH60030CID Littelfuse ® REVISION DRWG NO. TITLE C DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH60030-CID SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 3/15/2011 501851ERP - RELEASE MRY 166.7 [6.56] 38.4 [1.51] 20.7 [.82] 52.5 [2.07] R3.4 [.13] TYP R2.6 [.10] TYP SERIES SPECIFICATIONS: VOLTAGE RATING: 600V AMPERE RATING: 30 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 2.8 N-m (25 IN-LBS) WIRE RANGE: 6-14 AWG Cu ONLY SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. LR7316) 47.6 [1.87] 56.0 [2.20] 118.6 [4.67] 127.1 [5.00] 16.8 [.66] 21.5 [.85] 6.4 [.25] 86.4 [3.40] 47.6 [1.87] 56.0 [2.20] R3.4 [.13] TYP R2.6 [.10] TYP R3.4 [.13] TYP R2.6 [.10] TYP DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION B OL-LFH60060 Littelfuse ® REVISION DRWG NO. TITLE C DRW DATE GRAMS/PIECE FINISH GOOD WT MYORK 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH60060 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 3/15/2011 501851ERP - RELEASE MRY B 3/2/2017 517214ECP/D - ADD DIMENSION TOLERANCES MRY 184.2 1.50 7.25 0.06[ ] 7.1 THRU 12.7 12.7 .28 THRU .50 .50[ ] R3.4 [.13] TYP SERIES SPECIFICATIONS: VOLTAGE RATING: 600V AMPERE RATING: 60 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 5.6 N-m (50 IN-LBS) 2-4 AWG WIRE RANGE: 2-14 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. LR7316) 55.2 0.50 2.18 0.02[ ] 74.2 0.50 2.92 0.02[ ] 134.6 0.50 5.30 0.02[ ] 55.2 0.50 2.18 0.02[ ] 74.2 0.50 2.92 0.02[ ] R3.4 [.13] TYP 7.1 THRU 12.7 12.7 .28 THRU .50 .50[ ] R3.4 [.13] TYP 7.1 THRU 12.7 12.7 .28 THRU .50 .50[ ] DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH60100 Series Littelfuse ® REVISION DRWG NO. TITLE C DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH60100 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 3/15/2011 501851ERP - RELEASE MRY 228.6 [9.00] R3.4 [.13] TYP 53.4 [2.10] 145.3 [5.72] 66.0 [2.60] 22.9 [.90] SPECIFICATIONS: VOLTAGE RATING: 600V AMPERE RATING: 100 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 13.6 N-m (120 IN-LBS) 2/0-6 AWG WIRE RANGE: 2/0-14 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. LR7316) 64.6 [2.54] 15.0 [.59] 19.6 [.77] 33.8 [1.33] 172.8 [6.80] 61.0 [2.40] 79.8 [3.14] 107.0 [4.21] 125.7 [4.95] 64.6 [2.54] 172.8 [6.80] R3.4 [.13] TYP
600 V 30 A
600 V 60 A
600 V 100 A
Dimensions mm (inches)
Littelfuse.com © 2022 Littelfuse, Inc. Rev: 081622 7 of 7 POWR-GARD® Blocks and Holders Datasheet LF SERIES CLASS H/K5 AND R FUSE BLOCKS DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH60200 Series Littelfuse ® REVISION DRWG NO. TITLE D DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH60200 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 5/24/2011 501832ERP - RELEASE MRY 244.3 [9.62] 76.2 [3.00] 12.7 [.50] 52.3 [2.06] 84.2 [3.32] 228.6 [9.00] 12.7 [.50] 31.8 [1.25] n7.1 THRU v n18.3 x 10.2 n.28 THRU v n.72 x .40[] n8.7 THRU v n19.1 x 10.2 n.34 THRU v n.75 x .40[] n8.6 THRU [n.34 THRU] R4.3 [.17] TYP 52.3 [2.06] 72.4 [2.85] 15.9 [.63] SPECIFICATIONS: VOLTAGE RATING: 600V AMPERE RATING: 200 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 31.1 N-m (275 IN-LBS) WIRE RANGE: 250kcmil-6 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. 007316_0_000) 160.1 [6.31] 192.0 [7.56] 63.5 [2.50] 44.5 [1.75] 63.5 [2.50] 165.1 [6.50] 76.7 [3.02] 84.1 [3.31] 160.3 [6.31] 196.9 [7.75] n19.1 x 10.2 [n.75 x .40] n8.6 THRU [n.34 THRU] DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH60400 Series Littelfuse ® REVISION DRWG NO. TITLE D DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH60400 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 5/24/2011 501832ERP - RELEASE MRY 88.9 [3.50] 368.3 [14.50] 15.9 [.63] 22.2 [.88] 95.3 [3.75] 146.1 [5.75] 266.7 [10.50] 15.9 [.63] 84.4 [3.32] 15.9 [.63] n8.6 THRU v n19.1 x 11.2 n.34 THRU v n.75 x .44[] SPECIFICATIONS: VOLTAGE RATING: 600V AMPERE RATING: 400 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 31.1 N-m (275 IN-LBS) WIRE RANGE: 350kcmil-1/0 Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. 007316_0_000) 222.3 [8.75] 273.1 [10.75] 66.7 [2.63] 73.0 [2.88] 250.8 [9.88] 95.3 [3.75] 273.1 [10.75] n8.6 THRU v n19.1 x 11.2 n.34 THRU v n.75 x .44[] DES PLAINES, ILLINOIS 60016 3RD ANGLE PROJECTION A OL-LFH60600 Series Littelfuse ® REVISION DRWG NO. TITLE D DRW DATE GRAMS/PIECE FINISH GOOD WT M. York 3/15/2011 MATL SPEC FINISH UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE IN MILLIMETERS, DIMENSIONS IN BRACKETS [ ] ARE INCHES DIMENSIONING AND DO NOT INCLUDE PLATING. TOLERANCING TO BE INTERPRETED IN ACCORDANCE WITH ANSI Y14.5M-1994 DENOTES CRITICAL CHARACTERISTICS. DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE DENOTES A CHARACTERISTIC THAT PROVIDES AN INDICATION OF PROCESS PERFORMANCE. PROCEDURE FOR MEASUREMENT AND TRACKING TO BE DEFINED IN LITTELFUSE INSPECTION INSTRUCTIONS. DENOTES CP DIMENSIONS, -MINIMUM CP VALUE MUST BE WITHIN THE DIMENSIONAL LIMITATIONS SHOWN ON DRAWING AND INITIALLY LOCATED TO ALLOW FOR MAXIMUM TOOL LIFE. CPK CP SHEET 1 OF 1 SCALE LFH60600 SERIES OUTLINE NTS REVISION REV DATE DESCRIPTION A 5/24/2011 501832ERP - RELEASE MRY114.3 [4.50] 431.8 [17.00] 19.1 [.75] 114.3 [4.50] 177.8 [7.00] 317.5 [12.50] n8.6 THRU v n19.1 x 11.2 n.34 THRU v n.75 x .44[] 110.6 [4.35] 15.9 [.63] n7.1 THRU v n14.2 x 11.2 n.28 THRU v n.56 x .44[] SPECIFICATIONS: VOLTAGE RATING: 600V AMPERE RATING: 600 AMPERES INTERRUPT RATING: 10kA TERMINAL TYPE: BOX LUG SUGGESTED TORQUE: 42.4 N-m (375 IN-LBS) WIRE RANGE: 500kcmil-4 AWG Cu/Al SOLID/STRANDED APPROVALS: UL LISTED (FILE NO. E14721) CSA CERTIFIED (FILE NO. 007316_0_000) 254.0 [10.00] 34.9 [1.38] 79.4 [3.13] 95.3 [3.75] 19.1 [.75] 298.5 [11.75] 114.3 [4.50] 317.5 [12.50] n7.1 THRU v n14.2 x 11.2 n.28 THRU v n.56 x .44[]
600 V 200 A
600 V 400 A
600 V 600 A