LCY MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL: LCY http://www.m-system.co.jp/ LCY SPECIFICATIONS ES-1993 Rev.6 Page 1/3 Power Transducer Series L-UNIT BIDIRECTIONAL CURRENT TRANSDUCER Functions & Features
- Accepting 3-phase/3-wire AC current and voltage and detecting the magnitude and direction of the power flow by the phase angle of the signals
- Providing standard DC signal in proportion to the AC current
- DC output containing little ripple is ideal for computer input
- Isolation up to 2000V AC
- High-density mounting Typical Applications
- Measuring AC current flow in a factory having private power plants (2.95) 112 (4.41) (2.95) mm (inch) MODEL: LCY–1[1][2]–[3][4]
ORDERING INFORMATION
- Code number: LCY–1[1][2]-[3][4] Specify a code from below for each [1] through [4]. (e.g. LCY-11A-C/Q)
- Special output range (For codes Z & 0)
- Specify the specification for option code /Q (e.g. /C01/S01) CONFIGURATION 1: 3-phase / 3-wire [1] INPUT (balanced load) Current 1: 110 V AC / -5 - +5 A 2: 110 V AC / -1 - +1 A 3: 220 V AC / -1 - +1 A 4: 220 V AC / -5 - +5 A The negative polarity of input current indicates the direct (surplus) flow and the positive indicates the reverse flow. [2] OUTPUT Current A: 4 – 20 mA DC (Load resistance 550 Ω max.) DW: -20 – +20 mA DC (Load resistance 550 Ω max.) FW: -10 – +10 mA DC (Load resistance 1100 Ω max.) GW: -1 – +1 mA DC (Load resistance 11 kΩ max.) JW: -5 – +5 mA DC (Load resistance 2200 Ω max.) Z: Specify current (See OUTPUT SPECIFICATIONS) Voltage 6: 1 – 5 V DC (Load resistance 5000 Ω min.) 1W: -10 – +10 mV DC (Load resistance 10 kΩ min.) 2W: -100 – +100 mV DC (Load resistance 100 kΩ min.) 3W: -1 – +1 V DC (Load resistance 1000 Ω min.) 4W: -10 – +10 V DC (Load resistance 10 kΩ min.) 5W: -5 – +5 V DC (Load resistance 5000 Ω min.) 0: Specify voltage (See OUTPUT SPECIFICATIONS) [3] AUXILIARY POWER SUPPLY AC Power B: 100 V AC C: 110 V AC D: 115 V AC F: 120 V AC G: 200 V AC H: 220 V AC J: 240 V AC DC Power R: 24 V DC V: 48 V DC P: 110 V DC [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel GENERAL SPECIFICATIONS Construction: Stand-alone; terminal access at the front Connection: M3.5 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated steel (standard) or stainless steel
MODEL: LCY http://www.m-system.co.jp/ LCY SPECIFICATIONS ES-1993 Rev.6 Page 2/3 Housing material: Flame-resistant resin (black) Isolation: Voltage input to current input to output to auxiliary power Input waveform: Up to 5 % of 3rd harmonic content Overrange output: Approx. -10 to +120 % at 1 – 5 V Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) INPUT SPECIFICATIONS ■ INPUT Frequency: 50 or 60 Hz Detectable phase angle Reverse flow: lead 85° – 0° – lag 85° Direct flow: lag 95° – 180° – lag 265°
- Voltage Input Input burden: 0.5 VA Operational range: 50 – 120 % of rating Overload capacity: 150 % of rating for 10 sec., 120 % continuous
- Current Input Input burden: 0.1 VA (input -1 – +1 A)
0.5 VA (input -5 – +5 A)
Operational range: 10 – 120 % of rating Overload capacity: 1000 % of rating for 3 sec., 200 % for 10 sec., 120 % continuous OUTPUT SPECIFICATIONS ■ DC Current: -20 – +20 mA DC Minimum span: 1 mA Offset: max. 1.5 times span Load resistance: output drive 11 V maximum ■ DC Voltage: -10 – +10 V DC Minimum span: 5 mV Offset: Max. 1.5 times span Load resistance: Output drive 1 mA max.; at ≥ 0.5 V ■ OPERATION DIAGRAM (example) 0 +5A (R) -5A (D) OUT 20 mA (0.5) Keys: D = direct flow, R = reverse flow Note: When the input is less than half of the rated voltage or the tenth of the rated current, the transducer may output as "reverse" flow. (0.5) 0 +5 A (R) -5A (D) OUT +1 0V (0.5) -10V (0.5) INSTALLATION Auxiliary power supply
- AC: Operational voltage range: rating -15/+10 %, 50/60 Hz, approx. 2 VA
- DC: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating, ripple 10 %p-p max., approx. 2 W (18 mA at 110 V) Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 85 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span Accuracy: ±0.5 % with balanced load Response time: ≤ 2 sec. (0 – 100 % ±1 %) Ripple: 0.5 %p-p max. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (voltage input to current input to output to auxiliary power to ground) Impulse withstand voltage: 1.2 / 50 μsec., ±5 kV (input to output or ground)
MODEL: LCY http://www.m-system.co.jp/ LCY SPECIFICATIONS ES-1993 Rev.6 Page 3/3 CONNECTION DIAGRAM * The transducer can be powered from the input voltage when the voltage is sufficiently stable and meets other supply voltage requirements. LOAD 1 2 3 SOURCE P3 U P2 V u vFUSE VT k l CT L K 1S k l CT L K U(+) V(–) AUXILIARY POWER OUTPUT EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) DIN RAIL 35mm wide 8 (.31) M3.5 SCREW (Only on the used terminals) 75 (2.95) TERMINAL COVER 2–5.8 (.23) dia. or 2–4.8 (.18) dia. MTG HOLE 8 (.31) deep
- When mounting, no extra space is needed between units. 75 (2.95) 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 3 (.12) 1(.04) MOUNTING REQUIREMENTS unit: mm (inch) 2–M5 60 (2.36) 60 (2.36) ■ M5 SCREWS 2–M4 60 (2.36) 50 (1.97) ■ M4 SCREWS Specifications are subject to change without notice.