LC1K1610F7 SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
TeSys K contactor - 3P - AC-3 <= 440 V 16 A - 1 NO aux. - 110 V AC coil Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 172.00 USD Main Range TeSys Product or component type Contactor Product name TeSys K Device short name LC1K Device application Control Contactor application Motor control Complementary Utilisation category AC-3 AC-1 Poles description 3P Power pole contact composition 3 NO [Ue] rated operational voltage Power circuit: 690 V AC 50/60 Hz Signalling circuit: 690 V AC 50/60 Hz [Ie] rated operational current 16 A<= 440 V AC-3 power circuit
20 A<= 690 V AC-1 power circuit
Control circuit type AC 50/60 Hz [Uc] control circuit voltage 110 V AC 50/60 Hz Motor power kW 4 kW 480 V AC 50/60 Hz 4 kW 500...600 V AC 50/60 Hz 4 kW 660...690 V AC 50/60 Hz 5.5 kW 440 V AC 50/60 Hz 4 kW 220...230 V AC 50/60 Hz 7.5 kW 380...415 V AC 50/60 Hz Auxiliary contact composition 1 NO [Uimp] rated impulse withstand voltage 8 kV Overvoltage category III Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Apr 27, 2021
[Ith] conventional free air thermal current
20 A 122 °F (50 °C) power circuit
10 A 122 °F (50 °C) signalling circuit
Irms rated making capacity 110 A AC signalling circuit IEC 60947
160 A AC power circuit NF C 63-110
160 A AC power circuit IEC 60947
Rated breaking capacity 110 A 440 V IEC 60947
80 A 500 V IEC 60947
70 A 660...690 V IEC 60947 [Icw] rated short-time withstand current 115 A 122 °F (50 °C) - 1 s power circuit
105 A 122 °F (50 °C) - 5 s power circuit
100 A 122 °F (50 °C) - 10 s power circuit
75 A 122 °F (50 °C) - 30 s power circuit
55 A 122 °F (50 °C) - 1 min power circuit
50 A 122 °F (50 °C) - 3 min power circuit
25 A 122 °F (50 °C) - >= 15 min power circuit
80 A - 1 s signalling circuit
90 A - 500 ms signalling circuit
110 A - 100 ms signalling circuit
Associated fuse rating 25 A gG <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit IEC 60947
10 A gG signalling circuit VDE 0660
Average impedance 3 mOhm - Ith 20 A 50 Hz power circuit [Ui] rated insulation voltage Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-5-1 Signalling circuit 600 V UL 508 Power circuit 600 V CSA C22.2 No 14 Signalling circuit 600 V CSA C22.2 No 14 Insulation resistance > 10 MOhm signalling circuit Inrush power in VA 30 VA 68 °F (20 °C)) Hold-in power consumption in VA 4.5 VA 68 °F (20 °C)) Heat dissipation 1.3 W Connections - terminals screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end Maximum operating rate 3600 cyc/h Auxiliary contacts type Instantaneous 1 NO Signalling circuit frequency <= 400 Hz Minimum switching current 5 mA signalling circuit Minimum switching voltage 17 V signalling circuit Mounting support Rail Plate Tightening torque 11.51 lbf.in (1.3 N.m) screw clamp terminals Philips No 2 11.51 lbf.in (1.3 N.m) screw clamp terminals flat Ø 6 mm Operating time 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 Non overlap distance 0.02 in (0.5 mm) Mechanical durability 10 Mcycles Electrical durability 1.3 Mcycles 16 A AC-3 <= 440 V Mechanical robustness Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Height 2.28 in (58 mm) Width 1.77 in (45 mm) Depth 2.24 in (57 mm) Net weight 0.40 lb(US) (0.18 kg) Environment Standards EN/IEC 60947-4-1 EN/IEC 60947-5-1 Product certifications CB Scheme IP degree of protection IP2x VDE 0106 Protective treatment TC conforming to IEC 60068 TC conforming to DIN 50016 Ambient air temperature for operation -13…122 °F (-25…50 °C) Ambient air temperature for storage -58…176 °F (-50…80 °C) Operating altitude 2000 m without derating Flame retardance V1 conforming to UL 94 Ordering and shipping details Category 22326 - CTR,K-LINE,AC,OPEN,NONREV Discount Schedule I12 GTIN 03389110709551 Nbr. of units in pkg. 1 Package weight(Lbs) 0.4 lb(US) (0.18 kg) Returnability No Country of origin FR Packing Units Unit Type of Package 1 PCE Package 1 Height 1.89 in (4.8 cm) Package 1 width 2.44 in (6.2 cm) Package 1 Length 2.56 in (6.5 cm) Unit Type of Package 2 S02 Number of Units in Package 2 50 Package 2 Weight 20.84 lb(US) (9.455 kg) Package 2 Height 5.91 in (15 cm) Package 2 width 11.81 in (30 cm) Package 2 Length 15.75 in (40 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration REACh free of SVHC Yes EU RoHS Directive Compliant EU RoHS Declaration Toxic heavy metal free Yes Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. Contractual warranty Warranty 18 months