LC1K09105E7 SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
TeSys K contactor - 3P - AC-3 <= 440 V 9 A - 1 NO aux. - 48 V AC coil Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 75.00 USD Main Range TeSys Product or component type Contactor Product name TeSys K Device application Control Contactor application Motor control Resistive load Complementary Utilisation category AC-3 AC-1 AC-4 Poles description 3P Power pole contact composition 3 NO [Ie] rated operational current 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit
9 A<= 440 V AC AC-3 power circuit
16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit
Control circuit type AC 50/60 Hz [Uc] control circuit voltage 48 V AC 50/60 Hz Motor power kW 2.2 kW 220...230 V AC 50/60 Hz AC-3 4 kW 380...415 V AC 50/60 Hz AC-3 4 kW 440 V AC 50/60 Hz AC-3 4 kW 480 V AC 50/60 Hz AC-3 4 kW 500...600 V AC 50/60 Hz AC-3 4 kW 660...690 V AC 50/60 Hz AC-3 2.2 kW 400 V AC 50/60 Hz AC-4 Auxiliary contact composition 1 NO Overvoltage category III Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Apr 27, 2021
[Ith] conventional free air thermal current
20 A 122 °F (50 °C) power circuit
10 A 122 °F (50 °C) signalling circuit
Irms rated making capacity 110 A AC power circuit NF C 63-110
110 A AC power circuit IEC 60947
110 A AC signalling circuit IEC 60947
Rated breaking capacity 110 A 415 V IEC 60947
110 A 440 V IEC 60947
80 A 500 V IEC 60947
110 A 220...230 V IEC 60947 110 A 380...400 V IEC 60947 70 A 660...690 V IEC 60947 Associated fuse rating 25 A gG <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit IEC 60947
10 A gG signalling circuit VDE 0660
Average impedance 3 mOhm - Ith 20 A 50 Hz power circuit Insulation resistance > 10 MOhm signalling circuit Inrush power in VA 30 VA 68 °F (20 °C)) Hold-in power consumption in VA 4.5 VA 68 °F (20 °C)) Heat dissipation 1.3 W Maximum operating rate 3600 cyc/h Auxiliary contacts type Instantaneous 1 NO Signalling circuit frequency <= 400 Hz Minimum switching current 5 mA signalling circuit Minimum switching voltage 17 V signalling circuit Operating time 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 Non overlap distance 0.02 in (0.5 mm) Mechanical robustness Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Environment Product certifications UL CSA Protective treatment TC conforming to IEC 60068 TC conforming to DIN 50016 Operating altitude 2000 m without derating Flame retardance V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 Ordering and shipping details Category 22326 - CTR,K-LINE,AC,OPEN,NONREV Discount Schedule I12 GTIN 03389110490404 Nbr. of units in pkg. 1 Package weight(Lbs) 0.45 lb(US) (0.20 kg) Returnability No Country of origin FR
Unit Type of Package 1 PCE Package 1 Height 1.89 in (4.8 cm) Package 1 width 2.44 in (6.2 cm) Package 1 Length 2.68 in (6.8 cm) Unit Type of Package 2 S02 Number of Units in Package 2 50 Package 2 Weight 23.21 lb(US) (10.526 kg) Package 2 Height 5.91 in (15 cm) Package 2 width 11.81 in (30 cm) Package 2 Length 15.75 in (40 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration REACh free of SVHC Yes EU RoHS Directive Compliant EU RoHS Declaration Toxic heavy metal free Yes Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Pro-active China RoHS declaration (out of China RoHS legal scope) Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. Contractual warranty Warranty 18 months