LC1D1156LE7 SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V

115 A - 208 V AC 50/60 Hz coil

Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 479.00 USD Main Range TeSys Product name TeSys D Product or component type Contactor Device short name LC1D Contactor application Resistive load Motor control Utilisation category AC-3 AC-4 AC-1 Poles description 3P Power pole contact composition 3 NO [Ue] rated operational voltage Power circuit: <= 1000 V AC 25...400 Hz Power circuit: <= 300 V DC [Ie] rated operational current 200 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit

115 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit

Motor power kW 30 kW 220...230 V AC 50/60 Hz AC-3) 55 kW 380...400 V AC 50/60 Hz AC-3) 59 kW 415...440 V AC 50/60 Hz AC-3) 75 kW 500 V AC 50/60 Hz AC-3) 80 kW 660...690 V AC 50/60 Hz AC-3) 65 kW 1000 V AC 50/60 Hz AC-3) 18.5 kW 400 V AC 50/60 Hz AC-4) Motor power HP (UL / CSA) 30 hp 200/208 V AC 50/60 Hz 3 phase 40 hp 230/240 V AC 50/60 Hz 3 phase 75 hp 460/480 V AC 50/60 Hz 3 phase 100 hp 575/600 V AC 50/60 Hz 3 phase Control circuit type AC at 50/60 Hz [Uc] control circuit voltage 208 V AC 50/60 Hz Auxiliary contact composition 1 NO + 1 NC Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Jan 4, 2021

[Uimp] rated impulse withstand voltage 8 kV IEC 60947 Overvoltage category III [Ith] conventional free air thermal current

200 A 140 °F (60 °C) power circuit

Irms rated making capacity 1260 A 440 V power circuit IEC 60947

140 A AC for signalling circuit conforming to IEC 60947-5-1

250 A DC for signalling circuit conforming to IEC 60947-5-1

Rated breaking capacity 1100 A 440 V power circuit IEC 60947 [Icw] rated short-time withstand current 250 A 104 °F (40 °C) - 10 min power circuit

550 A 104 °F (40 °C) - 1 min power circuit

950 A 104 °F (40 °C) - 10 s power circuit

1100 A 40 °C - 1 s for power circuit

100 A - 1 s for signalling circuit

120 A - 500 ms for signalling circuit

140 A - 100 ms for signalling circuit

Associated fuse rating 250 A gG <= 690 V type 1 power circuit

200 A gG <= 690 V type 2 power circuit

10 A gG signalling circuit

Average impedance 0.6 mOhm - Ith 200 A 50 Hz power circuit [Ui] rated insulation voltage Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Electrical durability 0.8 Mcycles 200 A AC-1 <= 440 V

0.95 Mcycles 115 A AC-3 <= 440 V

Power dissipation per pole 24 W AC-1

7.9 W AC-3

Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 Product certifications LROS (Lloyds register of shipping) GL BV DNV RINA GOST CCC UL CSA Connections - terminals Control circuit: lugs-ring terminals (external diameter: 8 mm) Power circuit: lugs-ring terminals (external diameter: 25 mm) Power circuit: bars 1 cable(s) - busbar cross section: 5 x 25 mm Tightening torque Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5 Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8 Power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8 Operating time 6...20 ms opening 20...50 ms closing Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 Mechanical durability 8 Mcycles Maximum operating rate 2400 cyc/h 140 °F (60 °C) Complementary Coil technology Built-in bidirectional peak limiting diode suppressor

1...1.15 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz Inrush power in VA 280…350 VA 60 Hz 0.8 68 °F (20 °C)) 280…350 VA 50 Hz 0.8 68 °F (20 °C)) Hold-in power consumption in VA 2…18 VA 60 Hz 0.3 68 °F (20 °C)) 2…18 VA 50 Hz 0.3 68 °F (20 °C)) Heat dissipation 3…8 W 50/60 Hz Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 Signalling circuit frequency 25...400 Hz Minimum switching current 5 mA for signalling circuit Minimum switching voltage 17 V for signalling circuit Non-overlap time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact Insulation resistance > 10 MOhm for signalling circuit Contact compatibility M13 Compatibility code LC1D Environment IP degree of protection IP20 front face conforming to IEC 60529 Protective treatment TH conforming to IEC 60068-2-30 Pollution degree 3 Ambient air temperature for operation -40…60 °C 60…70 °C with derating Ambient air temperature for storage -76…176 °F (-60…80 °C) Operating altitude 0...3000 m Fire resistance 850 °C conforming to IEC 60695-2-1 Flame retardance V1 conforming to UL 94 Mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open6 Gn for 11 ms Height 6.22 in (158 mm) Width 4.72 in (120 mm) Depth 5.35 in (136 mm) Net Weight 5.51 lb(US) (2.5 kg) Ordering and shipping details Category 22359 - CTR,TESYS D,OPEN,80-150A AC&DC Discount Schedule I12 GTIN 00785901565284 Nbr. of units in pkg. 1 Package weight(Lbs) 4.83 lb(US) (2.19 kg) Returnability No Country of origin CZ Packing Units Unit Type of Package 1 PCE Package 1 Height 6.61 in (16.8 cm) Package 1 width 8.19 in (20.8 cm) Package 1 Length 7.28 in (18.5 cm) Offer Sustainability Sustainable offer status Green Premium product

California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Compliant EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Product out of China RoHS scope. Substance declaration for your information. Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. PVC free Yes Contractual warranty Warranty 18 months