Page <1> V1.029/07/22 Enclosed Switch Disconnector Newark.com/multicomp-pro Farnell.com/multicomp-pro sg.element14.com/b/multicomp-pro Approvals CB. CE & SEMKO UL Standard UL508 International / European Standard IEC & EN 60947-1 and 3 Switch Specifications Data Range Switch Codes Units LB634P Rated operational voltage Ue IEC & EN Volts 690 V UL Volts 600 V Main switch: Isolating voltage up to Volts 750 V Rated impulse withstand voltage Uimp Volts 6 kV Rated uninterrupted current Iu Amps 40 A Rated operational current Ie IEC & EN AC-22A Up to 690V 40 A AC-21A Up to 690V 63 A AC-1 Up to 690V 63 A Rated operational power AC-23A (50-60Hz) IEC & EN 3 Phase 220 - 240V 22 kW 380 - 440V 30 kW 500 - 690V 45 kW Rated operational power AC-3 (50-60Hz) IEC & EN 3 Phase 220 - 240V 15 kW 440V 18.5 kW 690V 30 kW UL Power Rating DOL
3 Phase
1 Phase
Page <2> V1.029/07/22 Enclosed Switch Disconnector Newark.com/multicomp-pro Farnell.com/multicomp-pro sg.element14.com/b/multicomp-pro Data Range Switch Codes Units LB634P UL Short Circuit Ratings Fuse rating, class J Amps 70 A Fuse rating, class RK5 Amps - A Rated Fused short circuit current Amps 10 kA Short Circuit Capacity (IEC) Max fuse size (Type gl) Amps 63 A Rated Fused short circuit current Amps 30 kA Terminal Specification Single/ Multiple strand wire
2.5 Min-mm2
25 Max-mm2
10 Max-mm2
Recommended Tightening Torque 2 Nm Terminal Configuration Mounting Details Dimensions : Millimetres
Page <3> V1.029/07/22 Enclosed Switch Disconnector Newark.com/multicomp-pro Farnell.com/multicomp-pro sg.element14.com/b/multicomp-pro Part Number Table Description Part Number Enclosed Switch Disconnector, Boxed Isolator, 4 Pole, 63A LB634P Procedure to dismantle the cover
- Ensure the switch is in the OFF position
- Unscrew the cover screws & remove the cover
- For easy wiring the switch can be removed from the base by simply removing the two fixing screws. Once wiring is com- pleted replace the switch and secure in position with the fixing screws (taking care not to over tighten - recommended tightening torque 0.5Nm)
- After wiring ensure the profile orientation of the actuating spindle & knob shaft are in the same position
- Replace the cover & take care not to overtighten the screws (recommended tightening torque 0.5Nm)
- Do not install using power driven screwdrivers Note: There is no need to remove the switch handle in order to remove the cover. Important Notice : This data sheet and its contents (the “Information”) belong to the members of the AVNET group of companies (the “Group”) or are licensed to it. No licence is granted for the use of it other than for information purposes in connection with the products to which it relates. No licence of any intellectual property rights is granted. The Information is subject to change without notice and replaces all data sheets previously supplied. The Information supplied is believed to be accurate but the Group assumes no responsibility for its accuracy or completeness, any error in or omission from it or for any use made of it. Users of this data sheet should check for themselves the Information and the suitability of the products for their purpose and not make any assumptions based on information included or omitted. Liability for loss or damage resulting from any reliance on the Information or use of it (including liability resulting from negligence or where the Group was aware of the possibility of such loss or damage arising) is excluded. This will not operate to limit or restrict the Group’s liability for death or personal injury resulting from its negligence. Multicomp Pro is the registered trademark of Premier Farnell Limited 2019.