KSN MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL: KSN KSN SPECIFICATIONS ES-3514 Rev.9 Page 1/3 http://www.m-system.co.jp/ Plug-in Signal Conditioners K-UNIT INPUT LOOP POWERED ISOLATOR Functions & Features
- Loop-powered design eliminates output loop power supply
- 500 V DC input-to-output isolation
- 2 isolators housed in one enclosure
- 350 Ω output drive with 4 – 20 mA
- High-density mounting Typical Applications
- Isolation between control room and field instrumentation, between telemetering system and input device
- Eliminates ground problems in existing systems thanks to easiness of application without requiring additional power wiring (1.97) 123 (4.84) (3.15) mm (inch) K-UNIT MODEL: KSN–2[1][2]
ORDERING INFORMATION
- Code number: KSN-2[1][2] Specify a code from below for each of [1] and [2]. (e.g. KSN-2A6/Q)
- Specify the specification for option code /Q (e.g. /C01/S01) NO. OF CHANNELS 2: 2 channels [1] INPUT / OUTPUT A6: 4 – 20 mA DC / 1 – 5 V DC H6: 10 – 50 mA DC / 1 – 5 V DC AA: 4 – 20 mA DC / 4 – 20 mA DC HA: 10 – 50 mA DC / 4 – 20 mA DC [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output; between channels Zero adjustment (front) Voltage output: -5 to +5 % Current output: -0.5 to +0.5 % Span adjustment (front) Voltage output: 95 to 105 % Current output: 98.5 to 101.5 % INPUT & OUTPUT ■ Input 4 – 20 mA DC / Output 1 – 5 V DC Equivalent input impedance: Approx. 250 Ω with 20 mA input Operational range: 3 – 22 mA DC (Accuracy is assured within 4 – 22 mA) Load resistance: ≥ 50 kΩ ■ Input 10 – 50 mA DC / Output 1 – 5 V DC Equivalent input impedance: Approx. 100 Ω with 50 mA input Operational range: 7 – 55 mA DC (Accuracy is assured within 8 – 55 mA) Load resistance: ≥ 50 kΩ ■ Input 4 – 20 mA DC / Output 4 – 20 mA DC Equivalent input impedance: 230 Ω plus load resistance with 20 mA input Operational range: 3 – 22 mA DC (Accuracy is assured within 4 – 22 mA) Load resistance: 50 – 350 Ω (min. 50 Ω required for adequate operation) ■ Input 10 – 50 mA DC / Output 4 – 20 mA DC Equivalent input impedance: 90 Ω + [load resistance×0.16] with 50 mA input Operational range: 7 – 55 mA DC (Accuracy is assured within 8 – 55 mA) Load resistance: 50 – 600 Ω (min. 50 Ω required for
MODEL: KSN KSN SPECIFICATIONS ES-3514 Rev.9 Page 2/3 http://www.m-system.co.jp/ adequate operation)
- INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC INPUT CURRENT [mA] 4 12 20 5.0 approx. 3.7 VOLTAGE [V] ACROSS INPUT TERMINALS 3.0 approx. 5.0 4.0
- INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC INPUT CURRENT [mA] 10 30 50 5.0 approx. 3.7 VOLTAGE [V] ACROSS INPUT TERMINALS 3.0 approx. 5.0 4.0
- INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC INPUT CURRENT [mA] 4 12 20 10.0 VOLTAGE [V] ACROSS INPUT TERMINALS 3.0 approx. 5.6 (load 50Ω ) 6.0 12.0 approx. 5.0 8.0 approx. 3.8 approx. 9.6 (load 250Ω ) approx. 4.6 approx. 11.6 (load 350Ω )
- INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC INPUT CURRENT [mA] 10 30 50 10.0 VOLTAGE [V] ACROSS INPUT TERMINALS 3.0 approx. 4.9 (load 50Ω ) 6.0 approx. 4.7 8.0 approx. 3.8 approx. 6.5 (load 250Ω ) approx. 4.1 approx. 9.3 (load 600Ω ) INSTALLATION Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 200 g (0.44 lb) PERFORMANCE in percentage of span Accuracy: ±0.1 % Temp. coefficient: ±0.02 %/°C (±0.01 %/°F) Response time Voltage output: ≤ 0.5 sec. (0 – 90 %) Current output: Approx. 15 msec. (0 – 90 %) Load effect (current output) 4 – 20 mA input: 0.015 %/Ω (50 – 150 Ω) 10 – 50 mA input: 0.015 %/Ω (50 – 100 Ω) (The unit is calibrated with 250 Ω load at the factory.) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:
500 V AC @1 minute (input to output)
1500 V AC @1 minute (between channels)
2000 V AC @1 minute (input or output to ground)
MODEL: KSN KSN SPECIFICATIONS ES-3514 Rev.9 Page 3/3 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 3456 2187 80 (3.15) 80 (3.15) (.79) 40 (1 .57) 50 (1 .97) 7 .8 (.31) CLAMP (top & bottom) DIN RAIL 35mm wide2–4.5 (.18) dia. MTG HOLE 15 (.59) deep 8–M3.5 SCREW
- When mounting, no extra space is needed between units. SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Base Socket Ch 1. INPUT Ch 2. INPUT Chopper Buffer Amplifier Z S Channel 2 Ch 1. OUTPUT Ch 2. OUTPUT Inverter Rectifier ■VOLTAGE OUTPUT Base Socket Ch 1. INPUT 3 + Ch 2. INPUT S Channel 2 Ch 1. OUTPUT Ch 2. OUTPUT Inverter Isolation Load Effect Compensation Z ■CURRENT OUTPUT Specifications are subject to change without notice.