K70 BANNER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 8
Technical content
Sure Cross® Wireless K70 Touch Buttons combine the best of Banner's popular Touch Button family with its reliable, field- proven, Sure Cross wireless architecture.
- Available in 900 MHz and 2.4 GHz ISM Bands Up to three colors in one device
- Rugged, water-resistant IP65 housing with UV-stabilized material
- Bright, uniform indicator segments appear gray when off to eliminate false indication from ambient light
- Excellent immunity to false triggering by water spray, detergents, oils, and other foreign materials
- Ergonomically designed to eliminate hand, wrist, and arm stresses associated with repeated switch operation; require no physical force to operate Models Blank = 2 m Integral Cable Q = M12/Euro-style Integral QD QP = QD models require mating cordset ConnectionHousing G = Y = R = B = W = Color/Position K70 Wireless Model Key QK70 G R Y White Blue Red Green Yellow Pigtail with M12/Euro-style QD Blank = None 1 2 3Radio Band DXN2 DXN2 - Node 2.4 GHz DXN9 - Node 900 MHz T2 = Touch Activation Method Example model number: K70DXN9T2GRYQ Configuration Instructions Set the Radio Module DIP Switches Before applying power to the device, set the radio module's DIP switches. Default configurations are noted with (*). After changing DIP switch positions, cycle power to the device for the changes to take effect. DIP Switches Binding Push Button LED DIP Switch 1: Radio Transmit Power—The 900 MHz radios can be operated at 1 watt (30 dBm) or 250 mW (24 dBm). While the Performance radios operate in 1 Watt mode, they cannot communicate with the older 150 mW radios. To communicate with the older 150 mW radios, operate this radio in 250 mW mode. For 2.4 GHz models, this DIP switch is disabled. The transmit power for 2.4 GHz is fixed at about 65 mW EIRP (18 dBm), making the 2.4 GHz Performance models automatically compatible with older 2.4 GHz models. EZ-LIGHT® K70 Wireless Touch Button Original Document 189843 Rev. D
3 November 2016
DIP Switch 1 Position 900 MHz Models 2.4 GHz Models OFF * 1 Watt (30 dBm) Operation Disabled ON 250 mW (24 dBm) Operation DIP Switch 2: Touch Button Behavior—Use DIP Switch 2 to set the latching or momentary behavior of the touch button. DIP Switch 2 Position 900 MHz and 2.4 GHz Models OFF * Latching—Output toggles between activated and non-activated on successive touches ON Momentary—Remains activated while touch is present DIP Switches 3 and 4: Indicator Mapping—DIP switches 3 and 4 map the activation of the touch button to the one of the indicator light colors/positions to give visual feedback when the touch output is active. DIP Switches Touch Button to Indicator Mapping 3 4 OFF * OFF * Mapped to Color / Position 1 OFF ON Mapped to Color / Position 2 ON OFF Mapped to Color / Position 3 ON ON Mapping disabled Assembling the K70 Align notches on dome and base and press together Rotate the dome clockwise to lock into place (notches shown in locked position). EZ-LIGHT® K70 Wireless Touch Button 2 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 189843 Rev. D
M12/Euro-style Pinouts (Male) Key 12–30 V dc 1 = brown 3 = blue Bind the K70 to the Gateway and Assign the Node Address Before beginning the binding procedure, apply power to all the devices. DIP Switches Binding Push Button LED Enter binding mode on the Gateway.
- For board modules, triple-click the button.
- For housed models, triple-click button 2. On the board modules, the green/red LED flashes. On the housed models, both LEDs flash red. 2. Assign the K70 a Node address using the Gateway's rotary dials. Use the left rotary dial for the left digit and the right rotary dial for the right digit. For example, to assign your K70 to Node 01, set the left dial to 0 and the right dial to 1. Valid Node addresses are 01 through 47. 3. Remove any components to access the circuit board in the base module of the K70. 4. Enter binding mode on the K70 by triple-clicking the button. The bicolor LED flashes alternately while it searches for a Gateway in binding mode. After the K70 is bound, the LED is red and green for four seconds (looks amber), then it flashes four times (looks amber). The K70 automatically exits binding mode, cycles power, and enters Run mode. 5. Write the Node address on the provided label. This makes it easier to identify the physical Node location within a multi-Node network. 6. Reassemble the components back onto the base. 7. Repeat steps 2 through 5 for as many K70 Wireless Touch Buttons as are needed for your network. 8. After binding all K70s, exit binding mode on the Gateway.
- For board modules, double-click the button.
- For housed models, double-click button 2. LED Behavior for the Nodes Nodes do not sample inputs until they are communicating with the Gateway. The radios and antennas must be a minimum distance apart to function properly. Recommended minimum distances are:
900 MHz 150 mW radios: 6 feet
900 MHz 1 Watt radios: 15 feet
2.4 GHz 65 mW radios: 1 foot
EZ-LIGHT® K70 Wireless Touch Button P/N 189843 Rev. D www.bannerengineering.com - Tel: +1-763-544-3164 3
LED (Bi-color) Node Status Flashing green Radio link okay Green and red flashing alternately In Binding mode Both colors are solid for 4 seconds, then flash 4 times; looks amber Binding mode is complete Flashing red, once every 3 seconds Radio link error Flashing red, once every second Device error Sure Cross® User Configuration Tool The User Configuration Tool (UCT) software runs on any Windows machine and uses a USB to RS-485 adapter cable to connect your Gateway to the computer. The User Configuration Tool (UCT) offers an easy way to link I/O points in your wireless network, view I/O register values graphically, and set system communication parameters when a host system is not part of the wireless network. Download the most recent revisions of the UCT software from Banner Engineering's website: http://www.bannerengineering.com/wireless. The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for
1 Watt radios, BWA-HW-006 can be used for all other radios) converter
cable to pass information between your computer and the Gateway. Creating Flash Patterns Use the User Configuration Tool (UCT) to set the Duty Cycle, For Outputs of Node 1, output 9, to 0x0F0F as shown below, to achieve this flash pattern. Flash a K70 light by entering a time-based bit mask into the Duty Cycle parameter for that output register. Bit 0 represents the first 62.5 ms time window, bit 1 represents the second 62.5 ms window, etc. For example, turn ON the output from 0 to 250 ms, OFF from 250 to 500 ms, ON from 500 to 750 ms, then OFF again from 750 ms to 1 second by writing 0x0F0F to the appropriate output. Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bin 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 Hex 0 F 0 F Light Turned off from 750 ms to 1 s Turned on from 500 to 750 ms Turned off from 250 to 500 ms Turned on from 0 to 250 ms This example shows 0F0F being written to the Duty Cycle, For Outputs parameter for Node 1, output 9. EZ-LIGHT® K70 Wireless Touch Button 4 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 189843 Rev. D
I/O Modbus Holding Register I/O Type I/O Range Holding Register Representation (Dec.) Color # Gateway Any Node Min. Max. Min. Max. 1 1 1 + (Node# × 16) Touch Input 1 0 1 0 1 7 7 7 + (Node# × 16) Reserved 8 8 8 + (Node# × 16) Device Message 9 9 9 + (Node# × 16) Discrete OUT 9 0 1 0 1 Color 1 10 10 10 + (Node# × 16) Discrete OUT 10 0 1 0 1 Color 2 11 11 11 + (Node# × 16) Discrete OUT 11 0 1 0 1 Color 3 15 15 15 + (Node# × 16) Control Message 16 16 16 + (Node# × 16) Reserved Use the User Configuration Tool (UCT) software to define unique synchronous flash patterns for the lights. Specifications Touch Button Supply Voltage 12 to 30 V dc ( Outside the USA: 12 to 24 V dc, ± 10%) 1
900 MHz Consumption: Maximum current draw is < 40 mA and typical
current draw is < 30 mA at 24 V dc. (2.4 GHz consumption is less.) Supply Current < 220 mA maximum current at 12 V dc < 110 mA maximum current at 30 V dc Supply Protection Circuitry Protected against transient voltages Construction Polycarbonate Connections Integral 5-pin M12/Euro-style male quick disconnect (QD) ; 150 mm (6 in) pigtail PVC cable with a 5-pin M12/Euro-style male quick disconnect (QD); or a 2 m (6.5 ft) unterminated 5-wire cable depending on the model ordered Operating Conditions 95% at +50 °C maximum relative humidity (non-condensing) Environmental Rating IEC IP65 Vibration and Mechanical Shock Vibration 10 Hz to 55 Hz 0.5 mm p-p amplitude per IEC 60068-2-6 Shock 15G 11 ms duration, half sine wave per IEC 60068-2-27 Certifications Indicator Response Time Off Response: 150 µs (maximum) at 12 to 30 V dc On Response: 180 ms (maximum) at 12 V dc; 50 ms (maximum) at 30 V dc Indicators 1 to 3 colors depending on model: Green, Red, Yellow, Blue, and White LEDs are independently selected Required Overcurrent Protection WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations. Overcurrent protection is required to be provided by end product application per the supplied table. Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply. Supply wiring leads < 24 AWG shall not be spliced. For additional product support, go to http:// www.bannerengineering.com. Supply Wiring (AWG) Required Overcurrent Protection (Amps) 20 5.0 22 3.0 24 2.0 26 1.0 28 0.8 30 0.5 1 For European applications, power this device from a Limited Power Source as defined in EN 60950-1. EZ-LIGHT® K70 Wireless Touch Button P/N 189843 Rev. D www.bannerengineering.com - Tel: +1-763-544-3164 5
900 MHz, 1 Watt (Internal antenna): Up to 3.2 km (2 miles)
2.4 GHz, 65 mW (Internal antenna): Up to 1000 m (3280 ft) with line
Minimum Separation Distance 900 MHz, 1 Watt: 4.57 m (15 ft) 2.4 GHz, 65 mW: 0.3 m (1 ft)
900 MHz Compliance (1 Watt)
FCC ID UE3RM1809: This device complies with FCC Part 15, Subpart C, 15.247 IC: 7044A-RM1809
2.4 GHz Compliance
FCC ID UE300DX80-2400 - This device complies with FCC Part 15, Subpart C, 15.247 ETSI EN 300 328 V1.8.1 (2012-06) IC: 7044A-DX8024 Radiated Immunity HF
10 V/m (EN 61000-4-3)
Spread Spectrum Technology FHSS (Frequency Hopping Spread Spectrum) Link Timeout Gateway: Configurable via User Configuration Tool (UCT) software Node: Defined by Gateway Dimensions 49.7 [1.96] 20.9 [.82] 24.9 [.98] 8.0 [.32] 70.0 [2.76] 63.5 [2.50] R31.8 [1.25] M30 x 1.5-6g M12 x 1-6g All measurements are listed in millimeters (inches), unless noted otherwise. Accessories Cordsets 5-Pin Threaded M12/Euro-Style Cordsets—Single Ended Model Length Style Dimensions Pinout (Female) MQDC1-501.5 0.50 m (1.5 ft) Straight 44 Typ. ø 14.5 M12 x 1 1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray MQDC1-506 1.83 m (6 ft) MQDC1-515 4.57 m (15 ft) MQDC1-530 9.14 m (30 ft) 2 Radio range significantly decreases without line of sight. Always verify your wireless network's range by running a site survey. EZ-LIGHT® K70 Wireless Touch Button 6 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 189843 Rev. D
5-Pin Threaded M12/Euro-Style Cordsets—Single Ended Model Length Style Dimensions Pinout (Female) MQDC1-506RA 1.83 m (6 ft) Right-Angle 32 Typ. [1.26"] 30 Typ. [1.18"] ø 14.5 [0.57"] M12 x 1 MQDC1-515RA 4.57 m (15 ft) MQDC1-530RA 9.14 m (30 ft) All measurements are listed in millimeters, unless noted otherwise. Mounting Brackets SMB30A Right-angle bracket with curved slot for versatile orientation
- Clearance for M6 (¼ in) hardware
- Mounting hole for 30 mm sensor
- 12-ga. stainless steel A B C Hole center spacing: A to B=40 Hole size: A=ø 6.3, B= 27.1 x 6.3, C=ø 30.5 SMB30MM 12-ga. stainless steel bracket with curved mounting slots for versatile orientation
- Clearance for M6 (¼ in) hardware
- Mounting hole for 30 mm sensor A B C Hole center spacing: A = 51, A to B = 25.4 Hole size: A = 42.6 x 7, B = ø 6.4, C = ø 30.1 SMBAMS30P Flat SMBAMS series bracket
- 30 mm hole for mounting sensors
- Articulation slots for 90°+ rotation
- 12-ga. 300 series stainless steel 93 A C B Hole center spacing: A=26.0, A to B=13.0 Hole size: A=26.8 x 7.0, B=ø 6.5, C=ø 31.0 SSA-MBK-EEC1 Single 30 mm hole
- 8 gauge steel, black finish (zinc-plated)
- Front surface for customer applied labels 85 60 B A Hole size: A = ø 7 , B = ø 30 All measurements are listed in millimeters, unless noted otherwise. EZ-LIGHT® K70 Wireless Touch Button P/N 189843 Rev. D www.bannerengineering.com - Tel: +1-763-544-3164 7
Banner Engineering Corp. Limited Warranty Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product. THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE. This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE. Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com. EZ-LIGHT® K70 Wireless Touch Button © Banner Engineering Corp. All rights reserved