JKS EATON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- Provides 10X better current limitation to help prevent equipment damage caused by short- circuit events.
- 200kA Interrupting rating complies with NEC® Section 110.9 for today’s large capacity systems.
- Fast-acting fuse helps prevent equipment damage caused by short-circuit events.
- Ideal for critical industrial or commercial applications that have specific current limitation requirements. Recommended blocks and holders Fuse amps 1-pole 2-pole 3-pole Modular open blocks Up to
30 JM60030-1_ JM60030-2_ JM60030-3_
35-60 JM60060-1_ JM60060-2_ JM60060-3_ Modular power distribution fuse blocks* 0-30 JM60030-1MW_ JM60030-2MW_ JM60030-3MW_ 35-60 JM60060-1MW_ JM60060-2MW_ JM60060-3MW_ “Pyramid” block Up to 30 — — JP60030-3_ CH DIN-Rail modular fuse holders Up to
30 CH30J1_ CH30J2_ CH30J3_
35-60 CH60J1_ CH60J2_ CH60J3_ Safety J™ modular panel/DIN-Rail mount holders Up to
30 JT60030_ — —
35-60 JT60060_ — — * Combines fuse block and power distribution block into one assembly. Modular construction allows ganging blocks for the desired number of poles. For more information on the recommended blocks and holders, see the following data sheets. Product Data sheet no. Modular blocks 10488 Modular power distribution blocks 10192 Pyramid block 1108 CH holders 2144 Safety J holders 1152
JKS fast-acting Class J fuses, up to 60 A Eaton.com/bussmannseries Dimensions — in Class J fuse reducers Equipment fuse clips Desired fuse (case size) Catalog no. (pairs)
60 A 30 A J-63
100 A 30 A J-13
60 A J-16
200 A 60 A J-26†
† Not for bolt-in applications. 2.38 0.63 35 to 60 A 1.06 0.5 Up to 30 A 0.81 2.25 Time-currect curves — average melt These curves apply to both the 600 V Class J and the 700 V versions. AMP RATING CURRENT IN AMPS TIME IN SECONDS
JKS fast-acting Class J fuses, up to 60 A Eaton.com/bussmannseries Current-limiting effects — 600 Vac fuses only Prosp. S.C.C. Let-through current (apparent RMS Sym. vs. fuse rating) — 30A 60A 5000 1000 1000 10,000 1000 2000 15,000 1000 2000 20,000 1000 2000 25,000 2000 3000 30,000 2000 3000 35,000 2000 3000 40,000 2000 3000 50,000 2000 3000 60,000 2000 3000 70,000 2000 3000 80,000 2000 3000 90,000 2000 4000 100,000 2000 4000 150,000 2000 5000 200,000 3000 5000 Current-limitation curves — applies only to 600 Vac fuses AMP RATING 1000 10,000 100,000 200,000 400,000 100,000 10,000 1000 RMS SYMMETRICAL CURRENT IN AMPS A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS) B A INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS
Eaton.com/bussmannseries JKS fast-acting Class J fuses, up to 60 A Technical Data 1026 Effective July 2017 Follow us on social media to get the latest product and support information. The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton, Bussmann, Limitron and Safety J are valuable trademarks of Eaton in the U.S. and other countries. Y ou are not permitted to use the Eaton trademarks without prior written consent of Eaton. CSA is a registered trademark of the Canadian Standards Group. NEC is a registered trademark of the National Fire Protection Association. UL is a registered trademark of the Underwriters Laboratories, Inc. Eaton
1000 Eaton Boulevard
Cleveland, OH 44122 Eaton.com Bussmann Division
114 Old State Road
Ellisville, MO 63021 United States Eaton.com/bussmannseries © 2017 Eaton All Rights Reserved Printed in USA Publication No. 1026 — BU-SB13735 July 2017
700 Vac JKS-700 fast-acting fuses
Catalog symbol:
- JKS-_-700 Description: The JKS-700 is a fast-acting, current-limiting fuse that is UL Recognized and has CSA Component Acceptance for applications up to 700 Vac. The JKS-700 is available in ratings up to 60 amps with the same dimensions as a standard Class J fuses; but its voltage rating places it outside the standard Class J fuse class. The time- current curves shown for the 600 Vac fuses apply to the 700 Vac versions, but the current let-through curves do not. Bussmann recommends the JM70100 modular fuse block and the JM70100-MW power distribution fuse block for the 30 amp case size JKS-700 fuses. Ratings
- Volts 700 Vac (or less)
- Amps 25-60 A
- IR
- Minimum 6In
- 200 kA RMS Sym. Operating class aR Agency information
- UL Recognized, 248-13 Semiconductor Fuses, File E56412
- CSA Component Acceptance, C22.2 No 248.13 Semiconductor Fuses, Class 1422-30
- Current limitation for non-inductive circuits provides current-limiting response to maximum ground fault and short-circuit conditions
- 200 kA interrupting rating provides protection at all circuit locations
- Economical circuit protection for high-fault current circuits T ypical applications
- Power panelboards up to 700 Vac
- Machinery disconnects up to 700 Vac Catalog no. (amps) JKS-25-700 JKS-30-700 JKS-35-700 JKS-60-700