Edition • 2023-07-21T16:28:01+02:00 Temperature measuring amplifier 1-channel IM34-11EX-CI/K60

Edition • 2023-07-21T16:28:01+02:00 The 1-channel temperature measuring am- plifier IM34-11Ex-CI/K60 is designed to eval- uate the temperature-dependent changes of Ni100/Pt100 (RTD), thermocouples (TC) types B, E, J, K, L, N, R, S and T or low voltages in a range of -160…+160 mV and to output them as temperature-linear current signals of 0/4… 20 mA. Alternatively, RTDs in 2, 3 or 4-wire technology can be operated at the input circuit of the measuring amplifier. The Ni100/Pt100 input can either be used as external cold junc- tion compensation for the thermocouple or as independent measuring input. If the thermocouple leads are led up to a tem- perature measurement amplifier, we recom- mend to use the cold junction compensation module IN IM 3-CJT from TURCK (ident-No.: 6900524). This way the maximum possible accuracy is achieved. In order to increase the measurement speed with fast temperature changes on thermocouples, the device switch- es into the "Fast Mode" after 200 ms at the very latest after a gradient of 200 µV/s has been exceeded. Thereafter the cycle time of the thermal voltage measurement is < 80 ms. This means that no wire-break monitoring and no measurement of the cold junction tempera- ture will occur. After the gradient drops below 80 µV/s the device will switch back to "Normal Mode“. Thermocou- ple Tempera- ture range „Fast Mode“ 200 µV/s „Normal Mode“ 80 µV/s Type B 20 K/s 8 K/s 1100 °C Type E 2.6 K/s 1 K/s 0…1000 °C Type J 3.5 K/s 1.5 K/s 0…1200 °C Type K 5 K/s 1.6 K/s 0…1372 °C Type L 3.5 K/s 1.5 K/s 0…900 °C Type N 5.7 K/s 2.3 K/s 100…1300 Type R 20 K/s 8 K/s 400…1768 Type S 18 K/s 7 K/s 400…1768 Type T 4 K/s 1.5 K/s 150 °C The following table shows the approximate temperature gradients for the corresponding thermocouples. NOTE: The temperature gradients in the table are only approximate values for defined tem- perature ranges. For the precise determina- tion of the temperature gradient the character- istic of the sensor in question and the associ- ated operating point must be included. The devices are parametrized and configured via PC with the software tool "Device Type Manager" (DTM). For this, connect the tem- perature measuring amplifier to the PC with the 3.5 mm jack plug on the front. The ready- made transmission cable can be ordered from TURCK under the type name IM-PROG (ident no. 6890422). The following settings can be made with the DTM: ■ Measurement mode (RTD, TC, low volt- age, line compensation) ■ Measuring point (32 freely selectable char- acters) ■ Temperature (°C or °F) ■ RTD connection mode (2, 3 and 4-wire technology) ■ Cold-junction compensation (internla or via external RTD) NOTE: If the thermo- couple leads are led up to a temperature measurement amplifier, we recommend to use the cold junction compensation mod- ule IN IM 3-CJT from TURCK (ident-No.: 6900524). ■ Measuring range mapped on the power source ■ Output current (0/4…20 mA) ■ Fault current (0 resp. < 20 mA) The signals are transformed according to ITS 90/IEC 584 for thermocouples and according to IEC 751 for Pt100 RTDs and provided tem- perature linear at the current output. ■ Input for Pt100/ Ni100 resistors, thermo- couples and millivolt signals in 2, 3 or 4- wire technology ■ Suitable for fast temperature changes, starting with a thermal gradient of 200 µV/s ■ Parameterized using PACTware ■ Output: 0/4…20 mA ■ Complete galvanic isolation ■ Input reverse-polarity protected ■ ATEX, IECEx, CFMUS, UL, TR CU, IN- METRO, CCOE ■ Installation in zone 2

Edition • 2023-07-21T16:28:01+02:00 Type IM34-11EX-CI/K60 ID 7506636 Operating voltage 20…250 VAC Frequency 40…70 Hz Operating voltage 20…125 VDC Input circuits Intrinsically safe acc. to EN 60079 Thermocouple Pt100 Ni100 mV signals Pt100 (IEC 751), 2, 3 and 4-wire technology Ni100 (DIN 43760), 2, 3 and 4-wire technology Probe current ð 0.2 mA Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L (DIN 43710) Voltage input -0.160…+0.160 VDC Output circuits Output current 0/4…20 mA Fault current 0 / 22 mA adjustable Switching frequency ð 1 Hz Output Adjustable output mode Response characteristic Reference temperature 23 °C Measuring accuracy current output (including linearity, hysteresis and repeatability) ± 5 µA Temperature drift analog output 0.0025 %/K Measuring accuracy RTD input (including linearity, hys- teresis and repeatability) ± 50 mò Temperature drift RTD input ± 3 mò/K Measuring accuracy TC input (including linearity, hys- teresis and repeatability) ± 15 µV Temperature drift TC input ± 3.2 µV/K (of 320 mV) Cold junction compensation error 2-wire < 100mò after line compensation 3-wire < 100mò with asymmetrical wiring 4-wire < 50mò with cold junction compensation < 2 K with IM-3-CJT < 1K Galvanic isolation Test voltage 2.5 kV RMS Important note For Ex-applications the values specified in the corre- sponding Ex certificates (ATEX, IECEx, UL, etc.) ap- ply. Ex approval acc. to conformity certificate TÜV 02 ATEX 1898 Application area II (1) G, II (1) D Ignition protection category [Ex ia Ga] IIC ; [Ex ia Da] IIIC ; Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X Application area II 3 G Ignition protection type Ex nA [ic Gc] IIC T4 Characteristic linear

Edition • 2023-07-21T16:28:01+02:00 Mechanical data Protection class IP20 Flammability class acc. to UL 94 V-0 Ambient temperature -25…+70 °C -25 ... +60 °C für UL, FM Storage temperature -40…+80 °C Dimensions 104 x 18 x 110 mm Weight 133 g Mounting instructions DIN rail (NS35) or panel Housing material Polycarbonate/ABS Electrical connection 4 × 3-pin removable terminal blocks, reverse polarity protected, screw terminal Terminal cross-section 1 × 2.5 mm²/2 × 1.5 mm² Tightening torque 0.5 Nm

Edition • 2023-07-21T16:28:01+02:00 Accessories Type code Ident-No. Dimension drawing IM-3-CJT 6900524 Cold junction compensation module for IM 34 temperature measuring amplifiers, width 18 mm IM-CC-3X2BU/2BK 6900475 Cage clamp terminals for IM modules (Ex-devices with 18 mm overall width); includes: 2 pcs. 3-pin blue terminals and 2 pcs. 3-pin black terminals. IM-PROG III 7525111 USB-compatible programming adapter for the FDT/DTM- based parametrization of HART-capable Turck devices; gal- vanic separation between the device to be parametrized and the PC