7506447 TURCK | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 3

Technical content

Edition • 2023-07-21T16:27:27+02:00 Isolating transducer 1-channel IM33-11-HI/24VDC The 1-channel HART isolating transducer IM33-11-HI/24VDC is designed to operate HART 2-wire transducers (III) and to trans- mit galvanically isolated signals. In addi- tion to the analog signals, also the digital HART communication signals can be transmit- ted bidirectionally. Alternatively, active 2-wire HART transmitters (II) and passive 3-wire HART transmitters (I) can be operated. The device features one input and one output circuit, each with 0/4…20 mA. A green LED indicates operational readiness. The input signals are transmitted 1:1 without interference and made available at the output. The removable terminal blocks feature test sockets (Ø 2 mm) for connection of a HART handheld. ■ Power supply of 2-wire measuring trans- ducers with HART communication as well as connection to active 2-wire and passive 3-wire transmitters ■ Input circuit: 0/4…20 mA ■ Output circuit: 0/4…20 mA ■ SIL2 ■ Removable terminal blocks, screwable, with 2 mm test box ■ Complete galvanic isolation ■ Input reverse-polarity protected ■ TR CU

Edition • 2023-07-21T16:27:27+02:00 Type IM33-11-HI/24VDC ID 7506447 Nominal voltage 24 VDC Operating voltage 19…29 VDC Power consumption ð 2.2 W Transmitter connection Supply voltage ï 17 V / 20 mA Current 25 mA Input current 0/4...20 mA Input resistance (current) ð 250 ò Output circuits Output current 0/4…20 mA Load resistance current output ð 0.5 kò Response characteristic Rise time (10…90 %) ð 50 ms Fall time (90…10 %) ð 50 ms Measuring accuracy (including linearity, hysteresis and repeatability) ð 0.1 % of full scale Reference temperature 23 °C Temperature drift ð 0.005 % of full scale/K Galvanic isolation Test voltage 2.5 kV RMS Important note If the device is used in applications to achieve func- tional safety according to IEC 61508, the safety manual must be used. Information in the data sheet are not valid for functional safety. Approval SIL 2 acc. to EXIDA FMEDA Use in SIL safety circuits SIL 2 acc. to IEC 61508 Displays/Operating elements Operational readiness Green Mechanical data Protection class IP20 Flammability class acc. to UL 94 V-0 Ambient temperature -25…+70 °C Storage temperature -40…+80 °C Dimensions 110 x 18 x 110 mm Weight 161 g Mounting instructions DIN rail (NS35) or panel Housing material Polycarbonate/ABS Electrical connection 4 × 3-pin removable terminal blocks with test socket, reverse polarity protected, screw terminal Terminal cross-section 1 × 2.5 mm²/2 × 1.5 mm² Tightening torque 0.5 Nm Dimensions

Edition • 2023-07-21T16:27:27+02:00 Accessories Type code Ident-No. Dimension drawing IM-CC-3X2BK/2BK 7541218 Cage clamp terminals for IM modules ( Ex-devices with 18 mm overall width); includes: 4 pcs. of 3-pin black terminals