The Airpax™ IAR/IUR/IER/CUR/CER series is a snap-acting hydraulic-magnetic circuit breaker / protector that combines power switching and accurate, reliable circuit protection in one aesthetically pleasing, “1U” or “1RU” sized package. Designed for rack mount applications, the IAR/IUR/IER/CUR/CER series allows efficient use of rack space without sacrificing performance via proven hydraulic-magnetic technology that provides consistent operation from -40°C to 85°C, with a circuit interrupt capacity up to 5,000 AIC at 80VDC and 2,000 AIC at 250VAC. Available in series trip and mid-trip configurations, with auxiliary alarm switch options to provide monitoring of critical circuits. The CER series circuit breaker provides the necessary ratings for wireless and wired applications while meeting UL489A and TÜV requirements for approval.

  • UL1077, TÜV, UL489A approved
  • Designed to fit in a “1RU” application
  • 5000 AIC (80VDC), 2000 AIC (250VAC) interrupt capacity
  • Series or mid-trip with auxiliary switch alarm options
  • Various delays including motor start
  • 1 to 2 poles, multiple termination options POLES & TERMINALS The Airpax™ IAR/IUR/IER/CUR/CER series is available with one or two poles with various bullet, stud and screw terminals. Engineered for safe, sure operation, the toggle handles may be specified in blue, white, red, orange, green, yellow or black.

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. DIMENSIONS Tolerance, unless otherwise noted: All dimensions are in millimeters [inches] Single Pole Panel Mounting Detail, Single Pole Panel Mounting Detail, Two Pole, One Handle Panel Mounting Detail, Two Pole, Two Handles Two Pole (with or without two handles)

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. 1/4” Bullet 4.778 [121.35] 5.019 [127.48] Ø 0.251 ± 0.001 Ø [6.38 ± 0.03] 10-32 0.545 [13.84] 0.622 [15.81] 5/16” Bullet 4.851 [123.22] 5.092 [129.35] Ø 0.312 ± 0.001 Ø [7.92 ± 0.03] M5 0.510 [12.95] 0.588 [14.92]

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. CONFIGURATIONS The most popular configuration for magnetic protectors is the series trip where the sensing coil and the contacts are in series with the load being protected. In addition to providing conventional overcurrent protection, it is simultaneously used as an on-off switch. This is furnished as an integral part of a series pole in single or, multi-pole assemblies. Isolated electrically from the protectors circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector’s ON-OFF status. This is furnished as an integral part of a series pole in single or, multi-pole assemblies. Isolated electrically from the protectors circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector’s ON-OFF status. Series Trip Mid-Trip Auxiliary Switch

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 51 MAY TRIP 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 52 MAY TRIP 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 59 MA Y TRI PMAY TRIP 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 61 MAY TRIP 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 62 MAY TRIP 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 63 MAY TRIP 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 700 800 900 1000 PERCENT OF RATED CURRENT 125 TIME IN SECONDS DELAY 69 MAY TRIP

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. DELAY CURVES & SPECIFICATIONS OPERATING CHARACTERISTICS DC, 50/60Hz Delay Curves (typ) A choice of delays is offered for DC and 50/60Hz applications. Delays 59 and 69 provide fast-acting, instantaneous trip and are often used to protect sensitive electronic equipment (not recommended where known inrush exists). Delays 51 and 61 have a short delay for general purpose applications. Delays 52 and 62 are long enough to start certain types of motors and most transformer and capacitor loads. Trip Free Will trip open on overload, even when forcibly held on. This prevents operator from damaging the circuit by holding handle in the ON position. Trip Indication The operating handle moves forcibly and positively to the OFF position on overload. Ambient Operation Operates normally in temperatures between –40° C and +85°C. Insulation Resistance Not less than 100 megaohms at 500Vdc. Dielectric Strength Shall withstand AC voltage 60 Hz, for 60 seconds between all electrically isolated terminals as described below Series, switch only: 3,750 VAC Auxiliary switches: 600 VAC Series w/ auxiliary switch: 3,750 between main circuit breaker terminal and auxiliary switch terminal. Shock Shall not trip when tested per MIL-STD-202, method 213, test condition 1 with 100% rated current applied to delayed units, except 90% current in plane 4, (i.e. handle down). Instantaneous units shall have 80% rated current applied in all planes. Vibration Shall not trip when vibrated per MIL-STD-202, method 204, test condition A with 100% rated current applied to delayed units and 80% rated current to instantaneous units. Endurance In many applications contact wear due to the electrical load determines unit life. At maximum electrical ratings, the IAR/UR/IER/CUR/CER can per- form 10,000 operations at rated current and voltage at a maximum rate of 6 operations per minute. Inrush Pulse Tolerance Many circuit protector applications involve a transformer turn-on, an incandescent lamp load, or a capacitor charge from a DC source. Each of these applications has one common factor: a steep transient of very high current amplitude and short duration. This takes the form of a spike or a single pulse and is the cause of most nuisance tripping associated with magnetic circuit breakers. The IAR/IUR/IER/CUR/CER series will withstand, without tripping, a single pulse of 8 milliseconds duration half sine wave configuration) and peak amplitude of 10 times its rating.

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. Current Ratings (Amps) DC Resistance (Ohms) 51, 52, 53, 59 50/60Hz Impedance (Ohms) 61, 62, 63, 69 2.0 0.027 0.038 3.0 0.074 0.098 5.0 0.037 0.048 7.5 0.025 0.029 15.0 0.010 0.011 32.0 0.003 0.003 40.0 0.003 0.003 50.0 0.0024 0.0025 65.0 0.0021 — Auxiliary Switch Rating 10.0 amps @ 250 VAC, 60 Hz 3.0 amps @ 50 VDC 1.0 amps @ 80 VDC Approximate Weight Per Pole 1 pole 134 grams 2 pole 263 grams Pulse Tolerance Delay 134 grams 2 pole 263 grams Percentage of Rated Current vs Trip Time in Seconds at +25°C (Approximate Values) Delay 100% 125% 150% 200% 400% 600% 800% 1000% HARDWARE Handle Lock A handle lock option is available to prevent accidental actuation of the handle. The handle lock may be used in the ON or OFF position. Use of the handle lock on breakers with alarm style auxiliary switches may defeat he alarm feature on electrical trip. This option is available separately or pre- assembled (on single pole constructions only). Handle Lock Retainer (required for single pole only) 386-000-0930 Single Pole: RED = 762-600-7651 BLACK = 762-600-7650 Handle lock installed in factory will be mounted from the case side with logo on single pole MAXIMUM DCR AND IMPEDANCE (APPROXIMATE VALUES) Tolerance: 2 to 2.5 amps ±20%; 2.6 to 20 amps ± 25%; 21 to 50 amps ±50% *Consult factory for special values and for coil impedance of delays not shown

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. Mid-Trip The handle position indicates the status of the circuit breaker. In addition to full ON and full OFF positions, there is a middle “MID-TRIP” position indicating that the breaker has electrically tripped from an overload. It is available in single pole and multi-pole (handle per pole only) series constructions. Switch only configuration is not available in mid-trip build. An auxiliary switch can be furnished as an integral part of the mid-trip breaker. The switch provides an indication at a remote location when the circuit breaker has electrically tripped and handle is in the mid-trip position. ON Position Mid-Trip Position OFFPosition Barrier (-B) 1.715 [43.56] 1.460 [37.08] Bullets 0.510 [12.95] 0.725 [18.42] 0.375 [9.53] 0.251 ± 0.001 [6.38 ± 0.03]Ø Socket 1/4-20 UNC-2A Order # 641-480-5032 (silver plated copper) 0.251 ± 0.001 [6.38 ± 0.03]Ø 0.375 [9.52]Ø Socket 1/4-20 UNC-2A Order # 641-480-5030 (silver plated copper) 0.510 [12.95] 0.725 [18.42] 0.438 [11.13] Socket 1/4-20 UNC-2A Order # 641-480-5022 (silver plated copper) 0.312 ± 0.001 [7.92 ± 0.03]Ø 0.510 [12.95] 0.725 [18.42] Nut 1/4-20 UNC-2B Order # 388-899-5010 (silver plated copper) 0.156 [3.96] 0.438 [11.13] Example : IER1-1REC4C-52-20.0-AD-01-TORDERING OPTIONS The ordering code for these circuit breakers / protectors may be determined by following the steps in the decision tables shown here. The example shown is the code for a UL1077 & TÜV approved circuit protector with series trip, one handle per unit, single pole circuit protector with 10-32 terminal screws standard and a mechanical auxiliary switch. This unit is designed with a slow DC time delay and a rating of 20 amperes with optional metric threads and optional 80VDC capability. Handle color is black with white markings, and is has been met all the selection criteria to obtain the TÜV approval. To determine the ordering code for your particular unit, simply follow the steps shown, then fill in the letters and/or numbers in the boxes. Space is available on the circuit breaker label for your part number (up to 12 digits). You may then use your own part number to place an order or as a reference for further questions you may have. This option does require a factory assigned part number for traceability to your drawing or internal part number.

www.sensata.comCopyright © 2020 Sensata Technologies, Inc. Type IAR: Magnetic circuit protector, one handle per unit IARH: Magnetic circuit protector, one handle per pole IER: UL1077 & TÜV, series trip, one handle per unit IERH: UL1077 & TÜV, series trip, one handle per pole IUR: UL1077, series trip, one handle per unit IURH: UL1077, series trip, one handle per pole IMR: UL1077 & TÜV, mid trip, one handle per unit IMRH: UL1077 & TÜV, mid trip, one handle per pole CER: UL489A & TÜV, series trip, one handle per unit CERH: UL489A & TÜV, series trip, one handle per pole CUR: UL489A, series trip, one handle per unit CURH: UL489A, series trip, one handle per pole CMR: UL489A & TÜV, mid trip, one handle per unit CMRH: UL489A & TÜV, mid trip, one handle per pole Terminal 10-32 screw terminal, standard (no entry) K: 10-32 stud terminal B: 0.250” bullet terminal The shaded areas denote TÜV approval options. This approval requires the addition of a “T” at the end of the part number (8th decision). The “T” will automatically be added to any part number formed entirely from these shaded decisions. If non-shaded areas are selected, the unit will not be TÜV approved, but other approvals (if applicable) will still apply Number of Poles 1: Single pole 11: Two pole Internal Configuration -1: Series trip -1REC4C: Mechanical trip auxiliary switch* -1RS4C: Electrical trip auxiliary switch* -1RLS4C: Electrical trip auxiliary witch* (mid-trip only) -1REG4C: Series trip with auxiliary switch* 0.110 quick-connects (gold contacts) -1REC40: Mechanical trip auxiliary switch** -1RS40: Electrical trip auxiliary switch* -1RLS40: Electrical trip auxiliary switch* (mid-trip only) -1REG40: Series trip with auxiliary switch* 0.110 quick-connects (gold contacts) *Alarms when circuit breaker closes **Alarms when circuit breaker opens Only one auxiliary switch is normally supplied on two pole units. Switch is located in the right hand pole (viewed from terminal end) unless otherwise specied. Frequency & Delay -51: DC short delay -52: DC long delay -59: DC 125% instant trip -61: 50 - 60 Hz short delay -62: 50 - 60 Hz Long Delay -63: 50 - 60 Hz motor start / extra long delay (30A max) -69: 50 - 60 Hz 125% instant trip Rated Current Use three numbers to print required current value between 2.00 amps minimum and 50.0 amps maximum. Optional -A: Metric thread mounting (M3) & terminals (M5) -B: Barrier (AC only) -C: 65 VDC -D: 80VDC -E: 0.312” diameter bullet (standard is 0.250” when prex with “B” is chosen in rst decision) -F: 250VAC -L: Handle Lock Notes: 1. One or more descriptions may be used as required (for example, to get a barrier, 250VAC and handle lock, put -BFL) 2. When the sixth decision is not required, the seventh decision may be substituted and U.S. thread will be supplied Handle Color & Markings -00: Black -10: Yellow -20: Red -30: Blue -40: Green -60: Orange -90: White -01: Black w/ white markings (standard) -11: Yellow w/ black markings -21: Red w/ white markings -31: Blue w/ white markings -41: Green w / white markings -61: Orange w/ black markings -91: White w/ black markings TÜV Approval Per first decision’s description: The shaded areas denote TÜV approval options. This approval requires the addition of a “T” at the end of the part number (8th decision). IER 1 1REC4C - 52 - 20.0 - AD - 01 - T

electrical-protection-sales@ sensata.com Europe, Middle East & Africa +31743578156 info-sse@list.sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 Rev:01/17/20 www.sensata.com CONTACT USCopyright © 2020 Sensata Technologies, Inc. Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes to its data sheets or components without notice. Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA. AGENCY APPROVALS & CERTIFICATIONS WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE

  • The product’s side panels may be hot, allow the product to cool before touching
  • Follow proper mounting instructions including torque values
  • Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Disconnect all power before installing or working with this equipment
  • Verify all connections and replace all covers before turning on power Failure to follow these instructions can result in death or serious injury Ratings Voltage A.I.C. Agency Approvals Poles 2 to 65 amps 80VDC 5,000 UL489A, TÜV EN60947-2 & C-UL 1 2 to 50 amps 80VDC 5,000 UL1077, TÜV EN60943 & C-UL 2 2 to 50 amps 250VAC 2,000 UL1077, TÜV EN60943 & C-UL 2