HS103DR SENSATA | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 4

Technical content

Features

Output (1)

  • 55 amp AC output @ 40°C
  • Single Channel or 3 Phase output
  • 3 to 32 VDC input control voltage
  • DIN Rail mounted
  • UL, CSA, VDE, CE approved SSRs
  • Epoxy free design Description HS103DR-D2490 HS103DR-HD6090 Operating Voltage (47-63Hz) [Vrms] 24-280 48-660 Transient Overvoltage [Vpk] 600 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 1.0 1.0 Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2) 500 500 Maximum Load Current [Arms] 55 55 Minimum Load Current [Arms] 150 150 Maximum Surge Current (16.6ms) [Apk] 1200 1200 Maximum On-State Voltage Drop @ Rated Current [Vac] 1.15 1.15 Maximum I²t for Fusing (8.3 msec) [A² sec] 6000 6000 Minimum Power Factor (with Maximum Load) 0.5 0.5

www.sensata.comCopyright © 2018 Sensata Technologies, Inc. Input (1) General Description HS103DR-D2490 HS103DR-HD6090 Control Voltage Range 3-32 VDC 4-32 VDC Minimum Turn-On Voltage 3.0 VDC 4.0 VDC Minimum Turn-Off Voltage 1.0 VDC 1.0 VDC Maximum Reverse Voltage -32 VDC -32 VDC Minimum Input Current 7.0 mA 7.0 mA Maximum Input Current 12 mA 12 mA Nominal Input Impeadance Curent Regulated Curent Regulated Maximum Turn-On Time [msec] 1/2 Cycle 1/2 Cycle Maximum Turn-Off Time [msec] 1/2 Cycle 1/2 Cycle Description 55A 55A 3-32 VDC Control HS103DR-D2490 HS103DR-HD6090 Description HS103DR-Dxx90 Dielectric Strength, Input/Output/Base (50/60Hz)

4000 Vrms

Minimum Insulation Resistance (@ 500 V DC) 10 9 Ohms Maximum Capacitance, Input/Output 8 pF Ambient Operating Temperature Range -40 to 80˚C Ambient Storage Temperature Range -40 to 125˚C Status Indicator Display None Weight (typical) 1.36 lb. (619 g) Recommended Terminal Screw Torque Range: (in-lbs/Nm) 6-32 Screws - 13-15/1.5-17. 8-32 Screws - 18-20/2-2.2. (Screws dry without grease) Thermal pad installed Yes (1) All parameters at 25°C unless otherwise specified. (2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 GENERAL NOTES PRODUCT SELECTION

www.sensata.comCopyright © 2018 Sensata Technologies, Inc. THERMAL DERATE INFORMATION DIMENSIONS 3.21 3.00 5.20 1.70 3.65 2.73 2.37 1.70 Load Current (Amps) Ambient Temperature (ºC) HS103DR w/90A SSR or 1-25A 3-Phase SSR 02 010 30 40 50 60 70 80 AGENCY APPROVALS & CERTIFICATIONS E116949 LR81689 10143 UG (Not Applicable: -B and 4D) Designed in accordance with the requirements of IEC 62314 Agency approvals are for relay only.

+1 (877) 502 5500 – Option 2 sales.crydom@sensata.com Europe, Middle East & Africa +44 (1202) 416170 ssr-info.eu@sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 Rev:06/05/18_ ECN 20395 FDE-07-01 Rev. B www.sensata.com CONTACT USCopyright © 2018 Sensata Technologies, Inc. Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes to its data sheets or components without notice. Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA. WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE

  • The product’s side panels may be hot, allow the product to cool before touching
  • Follow proper mounting instructions including torque values
  • Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Disconnect all power before installing or working with this equipment
  • Verify all connections and replace all covers before turning on power Failure to follow these instructions will result in death or serious injury.