HRPG-300 MEANWELL | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

HRPG-300-3.3 HRPG-300-5 HRPG-300-7.5 HRPG-300-12 HRPG-300-15 HRPG-300-24 HRPG-300-36 HRPG-300-48MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER RIPPLE & NOISE (max.) Note.2 OUTPUT VOLTAGE ADJ. RANGE VOLTAGE TOLERANCE Note.3 LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) VOLTAGE RANGE Note.5 FREQUENCY RANGE POWER FACTOR (Typ.) EFFICIENCY (Typ.)INPUT ENVIRONMENT INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVER TEMPERATURE SAFETY STANDARDS SAFETY & EMC (Note 4) WITHSTAND VOLTAGE ISOLATION RESISTANCE WORKING TEMP. DC OK SIGNAL REMOTE CONTROL WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION MTBF DIMENSIONOTHERS NOTE PACKING OVERLOAD OVER VOLTAGEPROTECTION AC CURRENT (Typ.) 3.3V 5V 7.5V 12V 15V 24V 36V 48V 60A 60A 40A 27A 22A 14A 9A 7A 0 ~ 60A 0 ~ 60A 0 ~ 40A 0 ~ 27A 0 ~ 22A 0 ~ 14A 0 ~ 9A 0 ~ 7A 198W 300W 300W 324W 330W 336W 324W 336W 80mVp-p 90mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 250mVp-p 250mVp-p 1000ms, 50ms/230VAC 2500ms, 50ms/115VAC at full load 16ms/230VAC 16ms/115VAC at full load 85 ~ 264VAC 120 ~ 370VDC 47 ~ 63Hz PF>0.95/230VAC PF>0.99/115VAC at full load 80% 82% 3.5A/115VAC 1.8A/230VAC 35A/115VAC 70A/230VAC <1.2mA / 240VAC 105 ~ 135% rated output power 3.96 ~ 4.62V Protection type : Constant current limiting, recovers automatically after fault condition is removed Protection type : Shut down o/p voltage, re-power on to recover Shut down o/p voltage, recovers automatically after temperature goes down UL60950-1, TUV EN60950-1 approved Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, heavy industry level, criteria A I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH -40 ~ +70℃ (Refer to "Derating Curve") RC+ / RC-: 4 ~ 10V or open = power on ; 0 ~ 0.8V or short = power off PSU turns on : 3.3 ~ 5.6V ; PSU turns off : 0 ~ 1V 20 ~ 90% RH non-condensing ±0.03%/℃ (0 ~ 50℃) 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes 176K hrs min. MIL-HDBK-217F (25℃) 199*105*41mm (L*W*H) File Name:HRPG-300-SPEC 2017-07-14 HRPG - 3 0 0 s e ri e s300W Single Output with PFC Function FUNCTION 0.95Kg;15pcs/15.3Kg/0.69CUFT 5V STANDBY 5VSB : 5V@0.3A ; tolerance±5%, ripple : 50mVp-p(max.) FAN CONTROL (Typ.) Load 35±15% or RTH2≧50℃ Fan on EMC IMMUNITY EMC EMISSION Bauar Sicherheit egel gema t gepruft od be www. ID 2000000000 tuv.com wac g o s

AMBIENT TEMPERATURE (℃) LOAD (%) -40 10 20 30 40 50 60 70 (HORIZONTAL) Mechanical Specification Case No.980A Unit:mm Terminal Pin No. Assignment Pin No. Pin No. 4,5 6,7 Assignment Assignment DC OUTPUT -V DC OUTPUT +V FG AC/L AC/N HRS DF11-8DP-2DS or equivalent Connector Pin No. Assignment (CN100) : Pin No. Assignment Mating Housing HRS DF11-8DS or equivalent Terminal HRS DF11-**SC or equivalent AUXG AUX DC-OK RC- GND RC+ 1812.5

8 CN100

18 12.5 119.2 105 7515 Air flow direction 17max. 167.5 168.5 199 4-M4 L=5 FAN 120 LED SVR 12.25 168.5 12.25 12.25 4-M4 L=6 12.25167.5 4-M4 L=6 42.5 125 The 5V standby must be connected with a minimum load of 0.03A. -20 300W Single Output with PFC Function Derating Curve Output Derating VS Input Voltage INPUT VOLTAGE (V) 60Hz 85 100 125 135 155 264 100 LOAD(%) Block Diagram PWM fosc : 70KHz EMI INRUSH ACTIVE FILTER CURRENT LIMITING RECTIFIERS PFC I/P FG PWMPFC CIRCUIT DETECTION POWER AUX SWITCHING POWER FILTER FILTER RECTIFIERS RECTIFIERS AUX CONTROLCONTROL O.V.P. REMOTE CONTROL DC-OK AUXG RC+ RC- HRPG -300 seri es 100 File Name:HRPG-300-SPEC 2017-07-14

The remote sensing compensates voltage drop on the load wiring up to 0.5V. 1.Remote Sense Fig 1.1 Fig 2.1 CN100 CN100 Sense lines should be twisted in pairs AUX AUX AUXG AUXG DC-OK DC-OK GND GND RC- RC- RC+ RC+ 300W Single Output with PFC Function Function Description of CN100 Function Manual Between DC-OK(pin3) and GND(pin5) 3.3 ~ 5.6V 0 ~ 1V Output Status ON OFF 2.DC-OK Signal DC-OK signal is a TTL level signal. High when PSU turns on. HRPG -300 seri es Pin No. Function Description CN100 CN100 LOAD - + (Pin7) (Pin8) RC+ Turns the output on and off by electrical or dry contact between pin 4 (RC-), Short: Power OFF, Open: Power ON. Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V. "remote ON/OFF control". 8 -S Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V. 4 RC- Remote control ground. 5 GND This pin connects to the negative terminal(-V). Return for DC-OK signal output. 3 DC-OK DC-OK signal is a TTL level signal, referenced to pin5(DC-OK GND). High when PSU turns on. 2 AUXG Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V). File Name:HRPG-300-SPEC 2017-07-14

Fig 3.1 1 7 2 8 CN100 AUX AUXG DC-OK GND RC- RC+ Between RC+(pin6) and RC-(pin4) SW ON (Short) SW OFF (Open) Output Status OFF ON 3.Remote Control SW The PSU can be turned ON/OFF by using the "Remote ON/OFF" function 1 2 3 4 5 6 7 CN100 300W Single Output with PFC Function HRPG -300 seri es File Name:HRPG-300-SPEC 2017-07-14