Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 7

Technical content

  • Ratings from 25A to 125A @ 48-660 VAC
  • SCR output for heavy industrial loads
  • Zero Voltage or instantaneous turn-on outputs
  • UL/CSA/VDE Approved, CE Compliant to EN60950-1
  • Improved SEMS screw and washer
  • Redesigned housing with anti-rotation barriers For Generation 3 datasheet click here
  • AC or DC control
  • Direct bond copper substrate
  • EMC compliant to Level 3
  • Direct power lead frame
  • Epoxy free design PRODUCT SELECTION 125A90A50A25AControl Voltage 4-32 VDC HD6025 HD6050 HD6090 HD60125 90-280 Vrms HA6025 HA6050 HA6090 HA60125 18-36 Vrms HA6025E HA6050E HA6090E HA60125E AVAILABLE OPTIONS Operating Voltage 60: 48-660 VAC Series Rated Load Current 25: 25 Amps 50: 50 Amps 90: 90 Amps 125: 125 Amps Termination Blank: Screw F: Quick Connect (Up to 50 Amps models) K: Hex standoffs Input Status LED Blank: Not Included G: Included Overvoltage Protection Blank: Not Included P: Included

25 KEAH P G60

A: 90-280 VAC D: 4-32 VDC AxxxxE: 18-36 VAC Thermal Pad Blank: Not Included H: Included Switching Type Blank: Zero Voltage Turn-On -10: Instantaneous Turn-On H -10 OUTPUT SPECIFICATIONS (5) Descrption 25A 50A 90A 125A Operating Voltage (47-440Hz) [Vrms] 48-660 48-660 48-660 48-660 Transient Overvoltage [Vpk] 1200 1200 1200 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 1.0 1.0 1.0 1.0 Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] 500 500 500 500 Maximum Load Current [Arms] (2)(6) 25 50 90 125 Minimum Load Current [mArms] 150 150 150 150 Maximum 1 Cycle Surge Current (50/60Hz) [Apk] 235/250 597/625 1145/1200 1670/1750 Maximum On-State Voltage Drop @ Rated Current [Vrms] 1.15 1.15 1.15 1.15 Thermal Resistance Junction to Case (Rjc) [°C/W] 0.8 0.45 0.27 0.22 Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec] 285/259 1770/1629 6560/5976 13950/12709 Minimum Power Factor ( at Maximum Load) (3) 0.5 0.5 0.5 0.5 (4) (3) (1) (2) Required for valid part number For options only and not required for valid part number Not all part number combinations are available. Contact Crydom Technical Support for informacion on the availability of a specific part number. Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount

INPUT SPECIFICATIONS (5) HA60xxEHA60xxHD60xxDescription Control Voltage Range 4-32 VDC 90-280 Vrms 18-36 Vrms Minimum Turn-On Voltage 4.0 VDC (7) 90 Vrms 18 Vrms Must Turn-Off Voltage 1.0 VDC 10 Vrms 4.0 Vrms Maximum Reverse Voltage -32 VDC - - Minimum Input Current 7.0 mA 5 mA 16 mA Maximum Input Current 12 mA 10 mA 20 mA Nominal Input Impedance Current Regulated Maximum Turn-On Time [msec] 1/2 Cycle (8) 20 20 Maximum Turn-Off Time [msec] 1/2 Cycle 30 30 GENERAL SPECIFICATIONS (5) Description Parameters Dielectric Strength, Input/Output/Base (50/60Hz) 4000 Vrms Minimum Insulation Resistance (@ 500 VDC) 109 Ohm Maximum Capacitance, Input/Output 8 pF Ambient Operating Temperature Range -40 to 80 °C Ambient Storage Temperature Range -40 to 125 °C Weight (typical) 2.6 oz (74.9 g) Housing Material UL94 V-0 Baseplate Material Aluminum Input Terminal Screw Torque Range (in-lb/Nm) 13-15 /1.5-1.7 Load Terminal Screw Torque Range (in-lb/Nm) 18-20 / 2.0-2.2 SSR Mounting Screw Torque Range (in-lb/Nm) 18-20 / 2.0-2.2 Humidity per IEC60068-2-78 93% non-condensing LED Input Status Indicator w/”G” option (green) MTBF (Mean Time Between Failures) at 40°C ambient temperature (9) 11,641,553 hours (1,328 years) MTBF (Mean Time Between Failures) at 60°C ambient temperature (9) 7,210,376 hours (823 years) WIRING DIAGRAM S OLI D S T A T E R ELA Y OUTPUT INPUT Load (10) V 4 (– / ) 3 (+ / ) 1 ( ) 2 ( ) AC Input Output 24 AWG (0.2 mm 2) / 0.2 [minimum] 2 x 12 AWG (3.3 mm 2) / 3.3 [maximum] 20 AWG (0.5 mm 2) / 0.518 [minimum] 2 x 10 AWG (5.3 mm 2) / 5.3 2 x 8 AWG (8.4 mm 2) / 8.4 [maximum] 10 [44.5] 90 [400] 30 [133] 110 [490] 90 [400] Wire Size (Solid / Stranded)Terminals Wire Pull-Out Strength (lb)[N] Recommended Wire Sizes 0 5 10 15 20 25 30 DC Input Voltage Input Current (mA) Input Current vs Input Voltage Standard Regulated DC Input EQUIVALENT CIRCUIT BLOCK DIAGRAMS Diagram: HD60xx +DC -DC AC Trigger Circuit Current Limiter AC (11) (12) Diagram: HAxxxx AC AC AC Trigger Circuit Current Limiter AC AC/DC Converter (11) (12) Input/Load terminal Screw Torque Range (in-lb/Nm) (2) w/”K” option 8-10 / 0.9-1.13 Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount Input/Output Terminal Screw Thread Size #6-32 UNC / #8-32 UNC

MECHANICAL SPECIFICATIONS (5) GENERAL NOTES For additional information or specific questions, contact Crydom Technical Support. Screw Termination

1 OUTPUT 2

4 INPUT 3

1.1 [27.9] 0.49 [12.4] Mounting Hole/Slot 0.19 [4.9] DIA. 0.89 [22.6] 1.88 [47.6] 1.7 [43.2] 2.25 [57.3] 1.0 [25.4] 1.75 [44.5] Hex Standoff Termination (“K” Option) 1.1 [27.9] 0.49 [12.4] Mounting Hole/Slot 0.19 [4.9] DIA. 1.04 [26.4] 1.88 [47.6] 1.70 [43.2] 2.25 [57.3] 1.0 [25.4] 1.75 [44.5] 0.93 [23.6] (4 places) 1.0 [25.4] (2 places) (2) Quick Connect Termination (“F” Option) - Up to 25 Amp (1) 0.19 [4.9] DIA. 1.58 [40.2] 0.49 [12.4] Faston Terminal(13) 0.25 x 0.032 (2 places) 1.31 [33.4] 1.88 [47.6] 1.7 [43.2] 2.25 [57.3] 1.40 [35.6] 1.75 [44.5] Faston Terminal(13) 0.187 x 0.020 (2 places) 1.25 [31.8] Quick Connect Termination (“F” Option) - Up to 50 Amp (1) S OLI D S T A T E R ELA Y OUTPUT INPUT Mounting Hole/Slot 0.19 [4.9] DIA. 1.58 [40.2] 0.49 [12.4] Faston Terminal(13) 0.25 x 0.032 (4 places) 1.31 [33.4] 1.88 [47.6] 1.7 [43.2] 2.25 [57.3] 1.40 [35.6] 1.75 [44.5] Faston Terminal(13) 0.187 x 0.020 (2 places) 1.25 [31.8] 0.63 [16.0] 0.45 [11.4] (2 places) Tolerances: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount (1) Single pair (up to 25A) Double pair* (up to 50A). *Caution: User must connect both pairs. (2) Option “K” is designed and tested for use with printed circuit boards or ring/fork terminals having a thickness between 0.031 and 0.093 inches (0.79 to 2.36 mm), and loads rated up to 50 Amps. For higher load currents, the “K” standoff temperature must not exceed 105°C. For additional application assistance please contact Crydom Technical Support. (3) Output will self trigger between 900-1200Vpk, Min. power factor 0.7 or higher, not suituable for capacitive loads. (4) Instantaneous turn-on version is not recomended for capacitive loads. Use zero turn-on only. (5) All parameters at 25°C unless otherwise specified. (6) Heat sinking required, see derating curves. (7) Increase minimum voltage by 1V for operations from -20 to -40°C. (8) Turn-on time for Instantaneous turn-on versions is 0.02 msec (DC Control Models). (9) Al parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report). (10) Load can be wired to either SSR output terminal 1 or 2. (11) Elective Input Status LED, “G” option. (12) Elective Overvoltage Protection, “P” option. (13) Mechanical dimensions vary from G3 models.

0.01 0.1 1 10 Surge Current (Amp) Surge Duration (Secs) 25 A 100 200 300 400 500 600 0.01 0.1 1 10 Surge Current (Amp) Surge Duration (Secs) 50 A 150 450 300 600 750 900 1200 1050 0.01 0.1 1 10 Surge Current (Amp) Surge Duration (Secs) 90 A 200 400 800 600 1000 1200 1400 1800 1600 0.01 0.1 1 10 Surge Current (Amp) Surge Duration (Secs) 125 A Non repetitive peak surge current at Tj initial 40ºC. THERMAL DERATE INFORMATION 20 30 40 50 60 70 80 Ambient Temperature (ºC) Load Current (Amps) 25 A 1.5ºC/W 2ºC/W 3ºC/W 20 30 40 50 60 70 80 Ambient Temperature (ºC) Load Current (Amps) 50 A 0.7ºC/W 1ºC/W 1.5ºC/W 2ºC/W 20 30 40 50 60 70 80 Ambient Temperature (ºC) Load Current (Amps) 90 A 0.5ºC/W 0.7ºC/W 1ºC/W 1.5ºC/W 100 120 20 30 40 50 60 70 80 Ambient Temperature (ºC) Load Current (Amps) 125 A 0.5ºC/W 0.7ºC/W 1ºC/W Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount

Designed in accordance with the requirements of IEC 62314 IEC 61000-4-2 : Electrostatic Discharge – Level 3 IEC 61000-4-4 : Electrically Fast Transients – Level 3 IEC 61000-4-5 : Electrical Surges – Level 3 IEC 600068-2-6: Vibration 0.33mm and 0.75mm Amplitude over 10-55 Hz IEC 600068-2-27: Shock Resistance 15g/11ms E116950 LR 81689 REG.- Nr. 10143 (exept 125A models) Rev. 090417 ECN 20312 Part number: KS101 Clear plastic cover compatible with all new S1 designs. Safety covers provide added protection from electric shock when installing or checking equipment. Protective Cover Hardware Kit Part number: HK4 Bag with 2 square brass accessories and 2 screw 8-32 x 5/8 for output. Used to mount TMR1 lug terminals. New Accessories! Protective Cover & Hardware Kits Recommended Accessories Cover Hardware Kit Heat Sink Part No. Thermal Resistance [ºC/W] Lug Terminal Thermal Pad KS101 HK1 HK4 TRM1 TRM6 HSP-1 HSP-2 HS501DR HS301 / HS301DR HS251 HS202 / HS202DR HS201 / HS201DR HS172 HS151 / HS151DR HS122 / HS122DR HS103 / HS103DR HS101 HS073 HS072 HS053 HS033 HS023 5.0 3.0 2.5 2.0 2.0 1.7 1.5 1.2 1.0 1.0 0.7 0.7 0.5 0.36 0.25 ACCESORIES Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount

Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH.

  • Disconnect all power before installing or working with this equipment.
  • Verify all connections and replace all covers before turning on power. Failure to follow these instructions will result in death or serious injury. RIESGO DE DESCARGA ELECTRICA O EXPLOSION.
  • Desconectar todos los suministros de energia a este equipo antes de trabajar con este equipo.
  • Verificar todas las conexiones y colocar todas las tapas antes de energizer el equipo. El incumplimiento de estas instrucciones puede provocar la muerte o lesiones serias. RISQUE DE DESCHARGE ELECTRIQUE OU EXPLOSION
  • Eteindre toutes les sources d'énergie de cet appareil avant de travailler dessus de cet appareil
  • Vérifier tous connections, et remettre tous couverts en olace avant de mettre sous De non-suivi de ces instructions provoquera la mort ou des lésions sérieuses sérieuses. GEFAHR EINES ELEKTRISCHE N SCHLAGES ODER EINER EXPLOSION.
  • Stellen Sie jeglichen Strom ab, der dieses Gerät versorgt, bevor Sie an dem Gerät Arbeiten durchführen
  • Vor dem Drehen auf Energie alle Anschlüsse überprüfen und alle Abdeckungen ersetzen. Unterlassung dieser Anweisungen können zum Tode oder zu schweren Verletzungen führen. RISCHIO DI SCOSSA ELETTRICA O DELL’ESPLOSIONE.
  • Spenga tutta l'alimentazione che fornisce questa apparecchiatura prima di lavorare a questa apparecchiatura
  • Verificare tutti i collegamenti e sostituire tutte le coperture prima dell’accensione L'omissione di queste istruzioni provocherà la morte o lesioni serie 存在电击、 爆炸或电弧 闪烁危险
  • 在操作此设 备之前请先 关闭电源。 若不遵守这些说明, 可能会导致严重的 人身伤害甚至死亡。 WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告 RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
  • The product's side panels may be hot, allow the product to cool before touching.
  • Follow proper mounting instructions including torque values.
  • Do not allow liquids or foreign objects to enter this product. Failure to follow these instructions can result in serious injury, or equipment damage. RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER
  • Les panneaux latéraux du produit peuvent être chauds. Laisser le produit refroidir avant de le toucher.
  • Respecter les consignes de montage, et notamment les couples de serrage.
  • Ne pas laisser pénétrer de liquide ni de corps étrangers à l'intérieur du produit. Le non-respect de cette directive peut entraîner, des lésions corporelles graves ou des dommages matériels. Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben. GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG
  • Die Seitenwände können heiß sein. Lassen Sie das Produkt abkühlen, bevor Sie es berühren.
  • Beachten Sie die Montageanweisungen,
  • Führen Sie keine Flüssigkeiten oder Fremdkörper in das Produkt ein. Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales. RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD
  • Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfríe antes de tocarlo.
  • Respetar las instrucciones de montaje, y en particular los pares de apretado.
  • No dejar que penetren líquidos o cuerpos extraños en el producto. La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature. RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO
  • I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo.
  • Seguire le istruzioni di montaggio corrette.
  • Non far entrare liquidi o oggetti estranei in questo apparecchio. 如不能正确执行这些操作说明, 极有可能造成严重人体伤害或者设备的损坏。 材料损坏和高温外壳的危险性
  • 产品的一侧面板可能很热,在其冷却前请 不要触碰。
  • 遵照正确的安装说明,包括扭矩值。
  • 请勿让液体及其他异物进入本产品。

ANNEX - ENVIRONMENTAL INFORMATION The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products. Part Name Toxic or hazardous Substance and Elements Lead Mercury Cadmium Hexavalent Polybrominated Polybrominated (Pb) (Hg) (Cd) Chromium (Cr (VI)) biphenyls (PBB) diphenyl ethers (PBDE) Semiconductor die Solder 附件 - 环保信息 此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006, 电子信息产品污染控制标识要求。 有毒有害物质或元素件部 名称 铅 汞 镉 六价铬 多溴联苯 多溴二苯醚 (Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE) 半导体芯片 焊接点 Do not forget to visit us at: www.crydom.com Copyright © 2017 Crydom Inc. Specifications subject to change without notice. DatasheetPanel Mount