H3JA OMRON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 8
Technical content
Economical, Compact, Plug-in Timer ■ Time limit operation with automatic resetting. ■ DIN size (36 × 36 mm), fits standard 8-pin sock- ets. ■ Wide choice of supply voltages: 24, 100 to 120, 200 to 240 VAC, 12, 24 VDC. ■ Dual LED indication for power and output sta- tuses. ■ Large transparent setting knob. ■ Setting error rating almost matches that of a 48 × 48 timer. ■ Conforms to UL and CSA, and meets CE marking requirements.
Ordering Information
Note: Specify the model number, supply voltage, and rated time when ordering. ■ Accessories (Order Separately) Note: 1. Y92A-48G is a finger safe terminal cove r which is attached to the P3G-08 Socket. 2. Hold-down Clips are sold in sets of two. Operation/resetting system Time-limit contact Mounting method Rated time Model Time-limit operation/ self-resetting SPDT Surface mounting, flush mounting, and DIN track mounting 1 s, 3 s, 5 s, 10 s, 30 s, 60 s, 3 min, 5 min, 10 min, 30 min, 60 min, 3 hrs H3JA-8A DPDT H3JA-8C Ex. H3JA-8A 100 to 120 VAC 1 s Rated time Supply voltage Name/specifications Models Flush Mounting Adapter Y92F-31 Mounting Track 50 cm ( l) × 7.3 mm (t) PFP-50N 1 m (l) × 7.3 mm (t) PFP-100N 1 m (l) × 16 mm (t) PFP-100N2 End Plate PFP-M Spacer PFP-S Track Mounting/ Front Connecting Socket 8-pin PF085A Back Connecting Socket 8-pin US08 8-pin P3G-08 8-pin, finger safe type P3G-08 with Y92A-48G (see note 1) Hold-down Clip (see note 2) For PF085A Socket Y92H-6
■ Time Ranges ■ Ratings Rated time Time range Rated time Time range 1 s 0.1 to 1 s 3 min 0.3 to 3 min 3 s 0.3 to 3 s 5 min 0.5 to 5 min 5 s 0.5 to 5 s 10 min 1 to 10 min 10 s 1 to 10 s 30 min 3 to 30 min 30 s 3 to 30 s 60 min 6 to 60 min 60 s 6 to 60 s 3 hrs 0.3 to 3 hrs Rated supply voltage 24, 100 to 120 or 200 to 240 VAC (50/60 Hz); 12, 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption H3JA-8A 100 to 120 VAC: Approx. 2.6 VA (1.1 W) at 120 VAC 200 to 240 VAC: Approx. 5.0 VA (1.5 W) at 240 VAC 24 VAC: Approx. 1.0 VA (0.9 W) at 24 VAC 24 VDC: Approx. 0.8 W at 24 VDC 12 VDC: Approx. 0.5 W at 12 VDC H3JA-8C 100 to 120 VAC: Approx. 2.4 VA (0.9 W) at 120 VAC 200 to 240 VAC: Approx. 4.1 VA (1.1 W) at 240 VAC 24 VAC: Approx. 1.2 VA (1.0 W) at 24 VAC 24 VDC: Approx. 0.8 W at 24 VDC Control outputs H3JA-8A: 7 A at 250 VAC, resistive load H3JA-8C: 5 A at 250 VAC, resistive load
■ Characteristics Note: The surrounding air temperature (operating) is −10 to 40°C. Accuracy of operating time ±2% max. (full scale) Setting error ±7% max. (full scale) ±50 ms at 20°C Influence of voltage ±2% max. (full scale) Influence of temperature ±5% max. (full scale) Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts, and be- tween contact-carrying and control circuit, and between contacts of different poles)
750 VAC, 50/60 Hz for 1 min (betw een non-continuous contacts: H3JA-8A)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts: H3JA-8C) Impulse withstand voltage 3 kV (between power terminals) 4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) Noise immunity ±1.5 kV (between power terminals) and ±1.5 kV (between output terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) Static immunity Destruction: 8 kV Malfunction: 6 kV Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm double amplitude in 3 directions for 1 hour each. Malfunction: 10 to 55 Hz with 0.5-mm double amplitude in 3 directions for 10 minutes each. Shock resistance Destruction: 1,000 m/s 2 Malfunction: 100 m/s 2 Ambient temperature Operating: –10 °C to 55°C Storage: –25 °C to 65°C Ambient humidity Operating: 35% to 85% Life expectancy H3JA-8A Mechanical: 10,000,000 operations min. Electrical: 60,000 operations min. (7 A resistive load at 250 VAC, 360 operations/h) H3JA-8C Mechanical: 10,000,000 operations min. Electrical: 100,000 operations min. (5 A resistive load at 250 VAC, 360 operations/h) EMC (EMI) Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3) 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3) 1 kV differential mode (level 3) Approved standard UL508 (See note.), CSA C22.2 No. 14, conforms to EN61812-1 (Pollution degree 2) Case color Light gray (Munsell 5Y7/1) Degree of protection IP40 (panel surface) Weight H3JA-8A: Approx. 50 g H3JA-8C: Approx. 60 g
■ Timing Chart H3JA-8A Load current (A) H3JA-8C Switching operations (× 10 )3 Load current (A)
30 VDC
120 VAC
250 VAC
L/R = 7 ms 1,000 500 100 0 1234567 5,000Switching operations (× 10 )3 φ cosφ = 0.4 H3JA-8A H3JA-8C 100 ms min. Rt Set time Set time Terminals (2)-(7) (power) (6)-(8) (NO) (5)-(8) (NC) Time UP indicator (Orange) Power ON indicator (Green) 100 ms min. Rt Set time Set time Terminals (2)-(7) (power) (1)-(3) (NO) (6)-(8) (1)-(4) (5)-(8) (NC) Time UP indicator (Orange) Power ON indicator (Green)
Note: All units are in millimeters unless otherwise indicated. ■ Accessories (Order Separately) LED36 607 14.2 0.7 30.5 32.8 Flush Mounting Adapter Y92F-31 Adapter Y92F-31 shown with H3JA-8@ and back connecting socket. Panel Cutout Recommended panel thickness: 1 to 5 mm 4446 40 37.4 91.3 15.5 US08 US08 Connecting Socket Track Mounting/Front Connecting Socket PF085A Mounting HolesTerminal Arrangement (Top View) Mounting Height of Timer with Socket Note: PF085A can be used as a front connecting socket. Eight, M3.5 × 7 sems Two, 4.5 dia. holes Two, M4 or 4.5 dia. holes H3JA Hold-down Clips (Set of Two Clips) Y92H-6 for PF085A Socket
P3G-08 Terminal Arrangement (Bottom View) H3JA Adapter H3JA Adapter 4.9 17 (When Y92A-48G mounted) P3G-08 78.611 85.1 US08 91.311 Finger Safe Terminal Cover Conforming to VDE0106/P100 Y92A-48G (Attachment for P3G-08 Socket) Twelve, 6.4 dia. holes 34 47.7 × 47.7 48 × 48 47.4 16.5 24.6 27.6 Mounting Track PFP-100N, PFP-50N PFP-100N2 4.5 15 25 25 25 25 10 10 7.3±0.15 35±0.3 27±0.15 4.5 15 25 25 25 25 15 10 10 35±0.3 27 24 29.2 1 1.5 1,000 (500) (see note) 15 (5) (see note) Note: The values shown in parentheses are for the PFP-50N. 1,000
■ Terminal Arrangement End Plate PFP-M Spacer PFP-S 11.5 M4 × 8 pan head screw 6.2 1.8 35.5 35.3 1.8 1.3 4.8 44.3 34.8 16.5 H3JA-8A H3JA-8C
In the interest of product improvement, specifications are subject to change without notice. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. L110-E1-01A 0707 OMRON Corporation Industrial Automation Company Control Devices Division H.Q. Analog Controller Division Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan