H3DE-M OMRON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 34
Technical content
Solid-state Timer H3DE B-51 Timers Solid-state Timer H3DE DIN Track Mounted, Standard 22.5-mm Width Timer Range A wide AC/DC power supply range (24 to 230 VAC/DC) reduces the number of timer models kept in stock. (except for H3DE-H) 12-VDC model available for a specific application. (H3DE-M2) Nameplate provided for easy timer identification and management. Terminal clamp left open when delivered. Finger protection terminal block to meet VDE0106/P100. Enables easy sequence checks through instantaneous outputs for a zero set value at any time range. Incorporates environment-friendly, cadmium-free contacts. (except for H3DE-H) High immunity to inverter noise. Approved by UL and CSA. Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Voltage, and EMC Directives. ■ Broad Line-up of H3DE Series
Contents
H3DE-M/S H3DE-F H3DE-G H3DE-H H3DE-M H3DE-S
52 Solid-state Timer H3DE
Solid-state Multi-functional Timer H3DE-M/-S B-53 Timers Solid-state Multi-functional Timer H3DE-M/-S Eight operating modes (H3DE-M) and four operating modes (H3DE-S) cover a wide range of applications. Programmable contact enables the building of a self-holding re- lay circuit (-@2 models). A wide time setting range of 0.10 s to 120 h. Model Number Structure ■ Model Number Legend
Ordering Information
■ List of Models ■ Accessories (Order Separately) H3DE - 1 2 1. M: Multi-function type S: Standard type 2. 2: DPDT 1: SPDT Supply voltage Control output Model Multi-function type Standard type
12 VDC Contact output: DPDT (time-limit output SPDT and switchable
SPDT (time-limit ←→ instantaneous)) H3DE-M2 (see note) --- 24 to 230 VAC/DC Contact output: DPDT (time-limit output SPDT and switchable SPDT (time-limit ←→ instantaneous)) H3DE-M2 (see note) H3DE-S2 Contact output: SPDT (time-limit output SPDT) H3DE-M1 H3DE-S1 Supply voltage Note: Specify both the model number and supply voltage when ordering H3DE-M2. Example: H3DE-M2 24 to 230 VAC/DC Mounting Track 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.3 mm (t) PFP-100N 1 m (l) x 16 mm (t) PFP-100N2 End Plate PFP-M Spacer PFP-S
B-54 Solid-state Multi-functional Timer H3DE-M/-S Specifications ■ General Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm. ■ Time Ranges Note: When the main dial is set to “0” for all settings, the output will operate instantaneously. ■ Ratings Note: 1. DC ripple rate: 20% max. 2. Since an inrush current of 0.25 A will occur when using the power supply voltage at 24 VDC, pay careful attention when turning on or off the power supply to the Timer with a solid-state output such as a sensor. 3. The power consumption is for mode A after the Timer counts the time-up time and for the AC input at 50 Hz. The power consumption of the H3DE-M@ includes the input circuit with the B1 and A1 terminals short-circuited. Item H3DE-M2 H3DE-M1 H3DE-S2 H3DE-S1 Operating mode A: ON-delay (Signal or Power) B: Flicker OFF start (Signal or Power) B2: Flicker ON start (Signal or Power) C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval (Signal or Power) G: Signal ON/OFF-delay J: One-shot (Signal or Power) A: ON-delay B2: Flicker ON start E: Interval J: One-shot Terminal block Clamps two 2.5 mm 2 max. bar terminals without sleeves. Terminal screw tightening torque 0.98 N·m max. {approx. 10 kgf·cm max.} Input type Voltage input --- Output type Relay: DPDT Relay: SPDT Relay: DPDT Relay: SPDT Mounting method DIN track mounting (see note) Attachment Nameplate Approved standards UL508, CSA 22.2 No.14 Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)Time scale display Time unit display sec min hrs 10 h x 1 1 to 12 s 1 to 12 min 1 to 12 h 10 to 120 h Rated supply voltage (see notes 1 and 2) 24 to 230 VAC/DC (50/60 Hz)
12 VDC (H3DE-M2 model only)
Operating voltage range 85% to 110% of rated supply voltage Power reset Minimum power-off time: 0.1 s Reset voltage 2.4 VAC/DC max. Power consump- tion (see note 3) H3DE-M1 AC: approx. 4.3 VA (2.2 W) at 230 VAC DC: approx. 0.7 W at 24 VDC H3DE-M2 AC: approx. 4.8 VA (2.4 W) at 230 VAC DC: approx. 1.0 W at 24 VDC H3DE-S1 AC: approx. 2.7 VA (1.6 W) at 230 VAC DC: approx. 0.7 W at 24 VDC H3DE-S2 AC: approx. 3.2 VA (1.9 W) at 230 VAC DC: approx. 1.0 W at 24 VDC Voltage input Max. permissible capacitance between input lines (terminals B1 and A2): 2000 pF Load connectable in parallel with inputs (terminals B1 and A2) H-level: 20.4 to 253 VAC/DC L-level: 0 to 2.4 VAC/DC Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 30 VDC with resistive load (cosφ = 1)
Ambient temperature Operating: −10°C to 55°C (with no icing) Storage: −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85%
Solid-state Multi-functional Timer H3DE-M/-S B-55 Timers ■ Characteristics Note: 1. With the H3DE-M@, if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes: Accuracy of operating time: ±1% ±50 ms max. at 1.2-s range Setting error: ±10% +100/−50 ms max. Signal input time: 100 ms min. 2. For reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1). A maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). Accuracy of operating time ±1% max. of FS (±1% ±10 ms max. at 1.2-s range) (see note 1) Setting error ±10% ±50 ms max. of FS (see note 1) Signal input time 50 ms min. (see note 1) Influence of temperature ±2% max. of FS (±2%±10 ms max. at 1.2-s range) Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min. Between control output terminals and operating circuit: 2,000 VAC for 1 min. Between contacts of different polarities: 2,000 VAC for 1 min. Between contacts not located next to each other: 1,000 VAC for 1 min. Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz Destruction: 0.75-mm single amplitude at 10 to 55 Hz Shock resistance Malfunction: 100 m/s Destruction: 1,000 m/s 2 Contact material AGNi+gold plating (Use the G6RN-1 at 12 VDC.) Impulse withstand volt- age 3 kV (between power terminals) 4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV Static immunity Malfunction: 4 kV Destruction: 8 kV Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) (see note 2) EMC (EMI) EN61812-1 Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MH z to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3) 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3) 1 kV differential mode (level 3) Degree of protection IP30 (Terminal block: IP20) Weight 120 g
B-56 Solid-state Multi-functional Timer H3DE-M/-S Connections ■ Block Diagram ■ I/O Functions Note: When the output type selector switch on the bottom of the Timer is set to the instantaneous side, the relay R2 (terminal numbers 21/25, 22/ 26, and 24/28) becomes an instantaneous contact and turns ON/OFF in synchronization with the changes in the power supply. H3DE-M1/-M2 AC (DC) input Output circuit Start input Input circuit Power supply circuit Zero setting detection circuit Oscillation circuit Time scale/ unit selectors Counting circuit Operating mode selector Indicator circuit Power-ON indicator Output indicator AC (DC) input Output circuit H3DE-S1/-S2 Power supply circuit Zero setting detection circuit Oscillation circuit Time scale/ unit selectors Counting circuit Operating mode selector Indicator circuit Power-ON indicator Output indicator Item H3DE-M1/-M2 H3DE-S1/-S2 Input Start Starts operation. No input is available. Output Control output Outputs are turned ON according to designated out- put mode when preset value is reached. (See note.) Outputs are turned ON according to designated out- put mode when preset value is reached. (see note.)
Solid-state Multi-functional Timer H3DE-M/-S B-57 Timers ■ Terminal Arrangement Note: 1. The relay R2 can be set to either instantaneous or time-limit contact using the switch located on the bottom of the Timer. 2. DC supply voltage does not require the designation of polarity. 3. The contact symbol for the H3DE is indicated with because it offers multiple operating modes and is different from the delayed contact for conventional timers. ■ Input Connections The inputs of the H3DE-M1/-M2 are voltage (voltage imposition or open) inputs. R1 R2 18 16 18 16 A2 A1 15 R1 R2 18 16 18 16 A2 A1 15 18 16 18 16 A2 A1 15 18 16 18 16 A2 A1 15 28/24 26/22 28/24 26/22 28/2426/22 28/24 26/22 (see note 1)(see note 1) H3DE-M1 H3DE-S1 H3DE-M2 H3DE-S2 (see note 2) (see note 2) (see note 2) (see note 2) (DIN notation) (DIN notation) (DIN notation) (DIN notation) A1B1
24 VDC
(+) (−) A1B1 (+) (−) No-contact Input (Connection to PNP output sensor.) Contact Input Voltage Input Signal Levels Sensor Start Start Operates with PNP transistor ON Operates with relay ON TimerTimer No-contact Input (Connection to NPN output sensor.) Sensor Operates with NPN transistor ON Timer No-contact input Contact input 1. Transistor ON Residual voltage: 1 V max. (Voltage between terminals B 1 and A2 must be more than the rated "H-level" voltage (20.4 VDC min.).) 2. Transistor OFF Leakage current: 0.01 mA max. (Voltage between terminals B 1 and A2 must be less than the rated "L-level" voltage (2.4 VDC max.).) Use contacts that can adequately switch 0.1 mA at each voltage to be imposed. (When the contacts are ON or OFF , voltage between terminals B 1 and A2 must be within the following ranges: When contacts are ON: 20.4 to 253 VAC/DC When contacts are OFF: 0 to 2.4 VAC/DC
B-58 Solid-state Multi-functional Timer H3DE-M/-S Operation ■ Basic Operation Setting of Selector The selectors can be turned clockwise and counterclockwise to select the desired time unit, time scale, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting. Selection of Operating Mode The H3DE-M/-S can be set to any one of the operating modes A to J. Turn the operating mode selector with a screwdriver until the desired operating mode (A, B, C, B2, D, E, J, or G for the H3DE-M and A, E, J, or B2 for the H3DE-S) appears in the operating mode display win- dow located below the selector. Selection of Time Unit and Time Scale The desired time unit (s, m, h, or 10h) can be displayed in the time unit display window above the time setting dial by turning the time unit selector located at the upper right corner of the front panel. Time scale (0.1 or 1) is selected with the time scale selector at the upper left corner of the front panel, it appears in the time scale display win- dow above the selector. Operating mode selector Operating mode display window Time scale selector Time unit selector Time scale display window Time unit display window
Solid-state Multi-functional Timer H3DE-M/-S B-59 Timers ■ Timing Chart Note: 1. The minimum power reset time is 0.1 s and the minimum signal input time is 0.05 s. 2. The letter “t” in the timing charts stands for the set time and “t–a” means that the period is less than the time set. 3. There is no start input with H3DE-S@ models. Operation starts when the power is turned ON. 4. There is no instantaneous output with H3DE-M1/-S1 models. Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement) Operating mode Timing chart A: ON-delay Flicker OFF start B2: Flicker ON start Signal ON/ OFF- delay t t t−a t Power Output Basic operationPower (A1 and A2) Power indicator Start (B1 and A2) (see note) Time-limit contacts: NC 15 and 16 (25 and 26) Time-limit contacts: NO (output indicator) 15 and 18 (25 and 28) Start * For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. ** Start input is invalid while the Timer is in opera- tion. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28 t t t t tt ttt t−at −a Basic operation Power Output Power (A1 and A2) Power indicator Start (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) Start * For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. ** Start input is invalid while the Timer is in opera- tion. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28 t t t t tt ttt t−at −a Basic operation Power Output Power (A1 and A2) Power indicator Start (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) Start * For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. ** Start input is invalid while the Timer is in opera- tion. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28 ttt t t ttt t−at −a Basic operation Power Start Output Power (A1 and A2) Power indicator Start (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) * Start input is valid and re-triggerable while the Timer is in operation. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28
B-60 Solid-state Multi-functional Timer H3DE-M/-S Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement). Operating mode Timing chart Signal OFF- delay E: Interval Signal ON/ OFF- delay One-shot out- put (ON delay) t tt t−at −at −a Power (A1 and A2) Power indicator Basic operation Power Start Output Start (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) * Start input is valid and re-triggerable while the Timer is in operation. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28 t tt t−at−a t Power Output Basic operationPower (A1 and A2) Power indicator Start (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) Start * For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. ** Start input is valid and re-triggerable while the Timer is in operation. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28 t t t t t ttt t−at −a Power (A1 and A2) Power indicator Power Start Output Basic operationStart (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) * Start input is valid and re-triggerable while the Timer is in operation. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28 t tt t−at−a t Power (A1 and A2) Power indicator Power Output Basic operation Start (B1 and A2) (see note) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) Approx. 1+0.6 s (fixed) Approx. 1+0.6 s (fixed) Approx. 1+0.6 s (fixed) Start Approx. 1+0.6 s (fixed) * For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. ** Start input is valid and re-triggerable while the Timer is in operation. Instantaneous contacts: NC 25 and 26 Instantaneous contacts: NO 25 and 28
Solid-state Multi-functional Timer H3DE-M/-S B-61 Timers Nomenclature Setting Output type Output Type Selector Switch Settings (Bottom View) Main dial (for setting a time value) Time scale display window Time unit display window Operating mode display window (Front View) Time scale selector (select 0.1 or 1) Output indicator (orange) (Lit while Timer gives output.) Operating mode selector (select a mode from A, B, C, B2, D, E, J, and G for the H3DE-M1/-M2, from A, E, J, and B2 for the H3DE-S1/S2) Power-on indicator (green) (Lit while the power is on.) Nameplate for user use (20 x 5.4 mm white panel) Time unit selector (select one from sec, min, hrs, and 10 h) Output type selector switch for H3DE-M2/-S2 (default setting is time-limit output) Time-limit output (terminal numbers 25, 26 and 28) (default setting) Instantaneous output (terminal numbers 21, 22 and 24)
B-62 Solid-state Multi-functional Timer H3DE-M/-S Dimensions Note: All units are in millimeters unless otherwise indicated. H3DE-M/-S Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON) Terminal block (black) Output type selector switch (default setting: Time-limit output)
Solid-state Twin Timer H3DE-F B-63 Timers Solid-state Twin Timer H3DE-F Operates in flicker-OFF or flicker-ON start mode with one Unit. Independent ON- and OFF-time settings. Combinations of long ON- or OFF-time and short OFF- or ON- time setting are possible. Long time range from 0.1 s to 12 h for both ON and OFF time settings. Model Number Structure ■ Model Number Legend ■ List of Models ■ Accessories (Order Separately) H3DE - 1. F: Twin timers Operating mode Supply voltage Model Flicker-OFF/Flicker-ON start 24 to 230 VAC/VDC H3DE-F Mounting Track 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.3 mm (t) PFP-100N 1 m (l) x 16 mm (t) PFP-100N2 End Plate PFP-M Spacer PFP-S
B-64 Solid-state Twin Timer H3DE-F Specifications ■ General Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm. ■ Time Ranges Note: 1. Time scale display is applied commonly for ON and OFF time. 2. When the main dial is set to “0” for all settings, the output will operate instantaneously. ■ Ratings Note: DC ripple rate: 20% max. Item H3DE-F Operating mode Flicker-OFF/Flicker-ON start Operating/Reset method Time-limit operation/Time-limit reset or self-reset Terminal block Clamps two 2.5 mm2 max. bar terminals without sleeves Terminal screw tightening torque 0.98 N·m max. {approx. 10 kgf·cm max.} Output type Relay: SPDT Mounting method DIN track mounting (see note) Attachment Nameplate Approved standards UL508, CSA 22.2 No.14 Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P 100 Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)Time scale display (see note 1) Time unit display sec 10 s min hrs x 1 1 to 12 s 10 to 120 s 1 to 12 min 1 to 12 h Rated supply voltage (see note) 24 to 230 VAC/VDC (50/60 Hz) Operating voltage range 85% to 110% of rated supply voltage Power reset Minimum power-off time: 0.1 s Reset voltage 2.4 VAC/DC max. Power consumption AC: Approx. 3.1 VA (1.8 W) at 230 VAC DC: Approx. 0.8 W at 24 VDC Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1) Ambient temperature Operating: −10°C to 55°C (with no icing) Storage: −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85%
Solid-state Twin Timer H3DE-F B-65 Timers ■ Characteristics Note: For reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1). A maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). Accuracy of operating time ±1% max. of FS (±1% ±10 ms max. at 1.2-s range) Setting error ±10% ± 0.05 s max. of FS Influence of temperature ±2% max. of FS (±2% ± 10 ms max. at 1.2-s range) Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1 min. Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min. Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min. Impulse withstand voltage 3 kV (between power supply terminals) 4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV Static immunity Malfunction: 4 kV Destruction: 8 kV Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz Destruction: 0.75-mm single amplitude at 10 to 55 Hz Shock resistance Malfunction: 100 m/s Destruction: 1,000 m/s 2 Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) EMC (EMI) EN61812-1 Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV po wer port and output port (level 3) 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3) 1 kV differential mode (level 3) Degree of protection IP30 (IP20 for terminal block) Weight Approx. 110 g
B-66 Solid-state Twin Timer H3DE-F Connections ■ Block Diagram ■ I/O Function ■ Terminal Arrangement Note: DC supply voltage does not require the designation of polarity. ROM RAM Clock One-chip microcomputer AC (DC) input Power supply circuit ON indicator OFF indicator Indicator circuit ON/OFF start selector Time unit selector Output circuit Inputs --- Outputs Control output Outputs are turned ON/OFF according to the time set by the ON-and OFF-time setting dial. A1 15 1816 (DIN notation)
Solid-state Twin Timer H3DE-F B-67 Timers Operation ■ Basic Operation Time Unit Selection The time unit display window for output ON is located on the upper- right side of the front panel above the corresponding time unit selec- tor. The time unit display window for output OFF is located on the lower- right side of the front panel below the corresponding time unit selec- tor. According to the setting of each time unit selector, “sec” for seconds, “10s” for 10 seconds, “min” for minutes, or “hrs” for hours will appear in the corresponding time unit display window. Time Scale Selection The time scale selector on the upp er-left side of the front panel can be set to 0.1 or 1 as a magnification coefficient. Time Setting Use the ON/OFF-time setting dial to set the ON/OFF time. ■ Timing Charts Note: 1. The reset time requires a minimum of 0.1 s. 2. When power is supplied in flicker-ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance of the Timer. ON-time unit display window OFF-time unit display window ON-time unit selector (select one from sec, 10s, min, or hrs) OFF-time unit selector (select one from sec, 10s, min, or hrs) Time scale display window Time scale selector OFF-time setting dial ON-time setting dial Operating mode Timing chart Flicker-OFF start Flicker-ON start ON OFF 0.1 s min. ON OFF ON OFF ON OFF Power (A1 and A2) OFF indicator Output relay: NO 15 and 18 (ON indicator) Output relay: NC 15 and 16 t ON: ON set time tOFF: OFF set time 0.1 s min. ON OFF ON OFF ON OFF ON OFF Power (A1 and A2) OFF indicator Output relay: NO 15 and 18 (ON indicator) Output relay: NC 15 and 16 t ON: ON set time tOFF: OFF set time
B-68 Solid-state Twin Timer H3DE-F Nomenclature Dimensions Time scale display window Output ON indicator (orange) Output OFF indicator (green) Nameplate for user use (20 x 5.4 mm white panel) ON-time unit display window ON-time setting dial OFF-time setting dial OFF-time unit display window (Front View) (Bottom View) ON/OFF Start Selector Switch Settings Setting Operating mode Flicker-ON start Flicker-OFF start Time scale selector (select 0.1 or 1) Time unit selector (select one from s, 10s, min, or h for output ON) OFF-time unit selector (select one from s, 10s, min, or h) ON/OFF start selector (default is flicker-OFF start) H3DE-F Terminal block (black) Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON)
Solid-state Star-delta Timer H3DE-G B-69 Timers Solid-state Star-delta Timer H3DE-G A wide star-time range (up to 120 seconds) and star-delta trans- fer time range (up to 0.5 seconds) Model Number Structure ■ Model Number Legend ■ List of Models ■ Accessories (Order Separately) H3DE - 1. G: Star-delta timer Supply voltage Model 24 to 230 VAC/VDC H3DE-G Mounting Track 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.3 mm (t) PFP-100N 1 m (l) x 16 mm (t) PFP-100N2 End Plate PFP-M Spacer PFP-S
B-70 Solid-state Star-delta Timer H3DE-G Specifications ■ General Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm. ■ Time Ranges ■ Ratings Note: DC ripple rate: 20% max. Item H3DE-G Operating mode Star-delta operation Operating/Reset method Time-limit operation/Self-reset Terminal block Clamps two 2.5 mm2 max. bar terminals without sleeves Terminal screw tightening torque 0.98 N·m max. {approx. 10 kgf·cm max.} Output type (Star operation circuit) Relay: SPDT (Delta operation circuit) Relay: SPDT Mounting method DIN track mounting (see note) Attachment Nameplate Approved standards UL508, CSA 22.2 No.14 Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)Time scale display Star operation time ranges x 1 1 to 12 s x 10 10 to 120 s Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s Rated supply voltage (see note) 24 to 230 VAC/VDC (50/60 Hz) Operating voltage range 85% to 110% of rated supply voltage Power reset Minimum power-off time: 0.5 s Reset voltage 24 VAC/DC max. Power consumption AC: Approx. 3 VA (1.8 W) at 230 VAC DC: Approx. 0.8 W at 24 VDC Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1) Ambient temperature Operating: −10°C to 55°C (with no icing) Storage: −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85%
Solid-state Star-delta Timer H3DE-G B-71 Timers ■ Characteristics Note: For reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1). A maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). Accuracy of operating time ±1% max. of FS Setting error ±10% ± 0.05 s max. of FS Total tolerance of transfer time ± (25% FS + 5 ms) max. Influence of voltage ±0.5% max. of FS Influence of temperature ±2% max. of FS Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1 min. Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min. Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min. Impulse withstand voltage 3 kV (between power supply terminals) 4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV Static immunity Malfunction: 4 kV Destruction: 8 kV Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz Destruction: 0.75-mm single amplitude at 10 to 55 Hz Shock resistance Malfunction: 100 m/s Destruction: 1,000 m/s 2 Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) EMC (EMI) EN61812-1 Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV po wer port and output port (level 3) 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3) 1 kV differential mode (level 3) Degree of protection IP30 (IP20 for terminal block) Weight Approx. 120 g
B-72 Solid-state Star-delta Timer H3DE-G Connections ■ Block Diagram ■ I/O Functions ■ Terminal Arrangement Note: DC supply voltage does not require the designation of polarity. AC (DC) input Star operation Delta operation Power supply circuit Star opera- tion time oscillation circuit Star operation time scale selector Star opera- tion time counting circuit Star-delta transfer time selection Star-delta transfer time oscilla- tion circuit Star-delta transfer time counting circuit Output circuit Indicator circuit Star operation indicator Delta operation indicator Inputs --- Outputs Control output Star output is turned OFF when the dial set value is reached and delta output is ON after the preset transfer time elapses 18 16 2628 2628 A1 15 1816 2826 Star contact Delta contact (DIN notation)
Solid-state Star-delta Timer H3DE-G B-73 Timers Operation ■ Basic Operation Time Unit Setting The star-delta transfer time is set to 0.05, 0.1, 0.25 or 0.5 with the star-delta transfer time selector on the lower-right side of the front panel and the set value appears in the star-delta transfer time display window below the selector. Time Scale Selection The star operation time scale selector on the upper-left side of the front panel can be set to 1 or 10 as a magnification. Time Setting The operation time of the Timer is set with the time setting dial. ■ Timing Charts Note: The reset time requires a maximum of 0.5 s. Nomenclature Star-delta transfer time selector Star-delta transfer time display window Time setting dial Star operation time scale display window Star operation time scale selector 0.5 s Power (A1 and A2) ON OFF ON OFF ON OFF ON OFF ON OFF Star contact 15 and 18 (star indicator) Star contact 15 and 16 Delta contact 25 and 28 (delta indicator) Delta contact 25 and 26 t 1: Star operation time setting t2: Star-delta transfer time Star operation indicator (green) Delta operation indicator (orange) Time setting dial (for setting star operation time) Star-delta transfer time selector Star-delta transfer time display window Time scale display window Nameplate for user use (20 x 5.4 mm white panel) (Front View) Star operation time scale selector (select 1 or 10)
B-74 Solid-state Star-delta Timer H3DE-G Dimensions H3DE-G Terminal block (black) Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON)
Solid-state Power OFF-delay Timer H3DE-H B-75 Timers Solid-state Power OFF-delay Timer H3DE-H Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure ■ Model Number Legend ■ List of Models ■ Accessories (Order Separately) H3DE - 1. H: Power OFF-delay timer Supply voltage Model S Series (time range: 0.1 to 12 s) L Series (time range: 1 to 120 s) 100 to 120 VAC H3DE-H H3DE-H 200 to 230 VAC
24 VAC/VDC
48 VAC/VDC
Note: Specify both the model number and supply voltage when ordering. Example: H3DE-H 24 VAC/DC S Mounting Track 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.3 mm (t) PFP-100N 1 m (l) x 16 mm (t) PFP-100N2 End Plate PFP-M Spacer PFP-S
B-76 Solid-state Power OFF-delay Timer H3DE-H Specifications ■ General Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm. ■ Time Ranges Note: The Timer will not operate if the specified power-on time is not kept. Be sure to supply power for at least the period specified. ■ Ratings Note: The ripple in DC power supply must be 20% max. A single-phase, full-wave rectifying power supply can be connected if the ripple output of the power supply is a maximum of 20% of the whole output. Item H3DE-H Operating mode Power OFF-delay Operating/Reset method Instantaneous operation/Time-limit reset Terminal block Clamps Two 2.5 mm2 max. bar terminals without sleeves Terminal screw tightening torque 0.98 N·m max. {approx. 10 kgf·cm max.} Output type Relay: SPDT Mounting method DIN track mounting (see note) Attachment Nameplate Approved standards UL508, CSA 22.2 No.14 Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)Time scale display Time ranges Min. power ON time S series x 0.1 s 0.1 to 1.2 s 0.1 s minimum x 1 s 1 to 12 s L series x 1 s 1 to 12 s 0.3 s minimum x 10 s 10 to 120 s Rated supply voltage (see note) 100 to 120 VAC (50/60 Hz) 200 to 230 VAC (50/60 Hz)
24 VAC/VDC (50/60 Hz)
48 VAC/VDC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage Power consumption 24 VAC/VDC Type AC: Approx. 0.3 VA (0.2 W) at 24 VAC DC: Approx. 0.2 W at 24 VDC 48 VAC/VDC Type AC: Approx. 0.5 VA (0.5 W) at 48 VAC DC: Approx. 0.5 W at 48 VDC 100 to 120 VAC Type AC: Approx. 0.8 VA (0.7 W) at 120 VAC 200 to 230 VAC Type AC: Approx. 1.6 VA (1.0 W) at 230 VAC Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1) Ambient temperature Operating: −10°C to 55°C (with no icing) Storage: −25°C to 65°C (with no icing) Ambient humidity Operating: 35% to 85%
Solid-state Power OFF-delay Timer H3DE-H B-77 Timers ■ Characteristics Note: For reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1). A maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 100 mA at 5 VDC (failure level: P). Accuracy of operating time ±1% max. of FS (±1% ±10 ms max. at 1.2-s range) Setting error ±10% ± 0.05 s max. of FS Influence of temperature ±2% max. of FS (±2% ± 10 ms max. at 1.2-s range) Insulation resistance 100 MΩ min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1 min. Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min. Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min. Impulse withstand voltage 3 kV (or 1 kV for 24/48 VAC/VDC models) (between power supply terminals) 4.5 kV (or 1.5 kV for 24/48 VAC/VDC models) (between current-carrying metal parts and exposed non-current- carrying metal parts) Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV (between power supply terminals) Static immunity Malfunction: 4 kV Destruction: 8 kV Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz Destruction: 0.75-mm single amplitude at 10 to 55 Hz Shock resistance Malfunction: 100 m/s Destruction: 1,000 m/s 2 Life expectancy Mechanical: 10 million operations min. (under no load at 1,200 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) EMC (EMI) EN61812-1 Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3) 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3) 1 kV differential mode (level 3) Degree of protection IP30 (IP20 for terminal block) Weight Approx. 120 g
B-78 Solid-state Power OFF-delay Timer H3DE-H Connections ■ Block Diagram ■ I/O Functions ■ Terminal Arrangement Note: DC supply voltage does not require the designation of polarity. AC (DC) input Power supply circuit Power failure detection circuit Indicator circuit Oscillation circuit Time scale selector Counting circuit Output circuit Inputs --- Outputs Control output The Timer operates instantaneously when the Timer is turned ON. The Timer is in counting operation after the Timer is turned OFF and the output of the Timer is turned OFF when the preset time elapses. A1 15 1816 (DIN notation)
Solid-state Power OFF-delay Timer H3DE-H B-79 Timers Operation ■ Basic Operation Time Scale Selection The time scale selector on the upper left-hand side of the front panel of the S Series can be set to 0.1 or 1 and that of the L Series can be set to 1 or 10 as magnification coefficients. Time Setting The operating time of the Timer is set with the time setting dial. ■ Timing Charts Nomenclature Time scale display window Time scale selector Time setting dial ON OFF ON OFF ON OFF Power indicator ON OFF Power supply (A1 and A2) Output relay: NC 15 and 16 Output relay: NO 15 and 18 t: Set time Rt: Minimum power-on time (S-series: 0.1 s min.; L-series: 0.3 s min.) (The output may never turn ON if this time or more is not ensured.) (Front View) Time scale display window Time scale selector S Series: Set to 0.1 or 1 L Series: Set to 1 or 10 Power indicator (green) Lit when the Timer is turned ON. Nameplate for user use (20 x 5.4 mm white panel) Time setting dial (for setting power OFF-delay time)
B-80 Solid-state Power OFF-delay Timer H3DE-H Dimensions H3DE-H Terminal block (black) Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON)
Solid-state Timer H3DE (Common) B-81 Timers Accessories (Order Separately) (Common) Note: The undermentioned is common for all H3DE models. Note: All units are in millimeters unless otherwise indicated. ■ Dimensions Mounting Track 1 m 50 cm 1 m 4.5 15 25 25 25 25 * 10 10 L 7.3±0.15 35±0.3 27±0.15 4.5 15 25 25 25 25 15 10 10 L 35±0.3 27 24 29.2 1 1.5 11.5 6.2 1.8 35.5 35.31.8 1.3 4.8 44.3 16.5 34.8 PFP-100N, PFP-50N PFP-100N2 L: Length PFP-100N PFP-50N PFP-100N2 End Plate PFP-M Spacer PFP-S M4 x 8 pan head screw
B-82 Solid-state Timer H3DE (Common) Precautions (Common) Note: The undermentioned is common for all H3DE models. ■ Changing of Setting !Caution Do not change the time unit, time scale, operating mode, or output type selector switch while the Timer is in operation or malfunction could result. ■ Mounting and Dismounting The H3DE should be mounted as horizontally as possible. When mounting the H3DE on a socket mounting track, hook portion (A) of the Timer to an edge of the track first, and then depress the Timer in the direction of (B). When dismounting the H3DE, pull out portion (C) with a flat-blade screwdriver and remove the Timer from the mounting track. The H3DE can be mounted and dismounted with ease if a distance of 30 mm or more is kept between the H3DE and the top surface of other equipment located below the H3DE. ■ Power Supplies The H3DE Series is provided with a transformerless power supply system. An electric shock may be received if the input terminal or the output type selector switch is touched while power is being supplied. Use the bar terminal for wiring the H3DE. Using a stranded-wire ter- minal may cause a short-circuit due to a stray wire entering into the Timer. Both AC and DC power supplies can be connected to the power input terminals without regarding polarity. With the H3DE only, a DC power supply must be connected to the power input terminals as designated according to the polarity of the terminals. A DC power supply can be connected if its ripple factor is 20% or less and the mean voltage is within the rated operating voltage range of the Timer. Connect the power supply voltage through a relay or switch in such a way that the voltage reaches a fixed value at once or the Timer may not be reset or a timer error could result. For the power supply of an input device, use an isolating transformer, of which the primary and secondary windings are mutually isolated and the secondary winding is not grounded. The H3DE-H has a large inrush current; provide sufficient power supply capacity. If the power supply capacity is too small, there may be delays in turning ON the output. ■ Installation If the load current is continuously being supplied to the Timer for a long period of time, be sure to provide the mounting clearance as shown in the figure below. If used under the conditions other than those specified below, the life of internal components may be short- ened due to an excessive rise in the internal temperature. (A) (B) (C) 30 mm min. Rail stopper H3DE Power supply Circuit Isolation transformer is required. Rectifier circuit Start input tt DIN track t: Mounting clearance (mm) H3DE H3DE H3DE
Solid-state Timer H3DE (Common) B-83 Timers Switching Current vs. Ambient Temperature (When Mounting Two or More H3DE Units Side-by-Side) ■ Input/Output Relationship between Input and Power Supply Circuits Since the input circuit and the po wer supply circui t are configured independently, the input circuit can be turned on or off irrespective of the on/off state of the power supply. It must be noted that a voltage equivalent to the power supply voltage is applied to the input circuit. When connecting a relay or a transis tor as an external signal input device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply. If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminal s will be short-circuited to one another (refer to the figures below). The H3DE Series is provided wi th a transformerless power supply system. ■ Input Wires The input wires must be as short as possible. If the floating capacity of wires exceeds 2,000 pF (approx. 17 m for cables with 120 pF/m), the operation will be affected. Pay particular attention when using shielded cables. ■ Wiring (H3DE-H) The H3DE has a high impedance circuit. Therefore, the H3DE may not be reset if the H3DE is influenced by inductive voltage. In order to eliminate any influence of inducti ve voltage, the wires connected to the H3DE must be as short as possible and should not be installed alongside power lines. If the H3DE is influenced by inductive voltage that is 30% or more of the rated voltage, connect a CR filter with a capacitance of approximately 0.1 µF and a resistance of approxi- mately 120 Ω or a bleeder resistor between the power supply termi- nals. If there is any residual voltage due to current leakage, connect a bleeder resistor between the power supply terminals. 01 2 34 5 Ambient temperature (°C) Load current (A) Mounting clearance: 50 mm Mounting clearance: 10 mm Maximum range of operating ambient temperature Mounting clearance: 5 mm Mounting clearance: 0 mm A1B1 Input circuit AC/DC power supply Power supply circuit H3DE Power supply H3DE Incorrect Correct H3DE Power supply H3DE Contact or transistor for external input signal Contact or transistor for external input signal Short-circuit current Short-circuit current
B-84 Solid-state Timer H3DE (Common) ■ Operation (H3DE-H) An interval of 3 s minimum is required to turn on the H3DE after the H3DE is turned off. If the H3DE is turned on and off repeatedly with an interval of shorter than 3 s, the internal parts of the H3DE may deteriorate and the H3DE may malfunction. If it is required that the output be turned on repeatedly with an inter- val of shorter than 3 s, consider use of the H3DE-M2/-M1 in mode D (signal OFF-delay). ■ Precautions for EN61812-1 Conformance The H3DE as a built-in timer conforms to EN61812-1 provided that the following conditions are satisfied: The output section of the H3DE is provided only with basic isolation. To ensure reinforced isolation required by the EN61812-1, provide supplementary basic isolation on the load side connected to the out- put. The H3DE itself is designed according to the following: Overvoltage category III Pollution degree 2 On the above basis: Operation parts on the front and bottom: Reinforced isolation − With clearance of 5.5 mm and creepage distance of 5.5 mm at
230 VAC
Output: Basic isolation − With clearance of 3 mm and creepage distance of 3 mm at ■ Environment When using the Timer in an area with excess electronic noise, sepa- rate the Timer, wiring, and the equipment which generates the input signals as far as possible from the noise sources. It is also recom- mended to shield the input signal wiring to prevent electronic interfer- ence. Organic solvents (such as paint thin ner), as well as very acidic or basic solutions can damage the outer casing of the Timer. Do not use the Timer in places where it is exposed to dust, corrosive gas, or direct sunlight. When storing the Timer, make sure that the ambient temperature and humidity are within the rated values. Leave the Timer at room temperature for at least three hours before using the Timer if it has been stored at an ambient temperature of –10°C or below. ■ Others If the Timer is mounted on a contro l board, dismount the Timer from the control board or s hort-circuit the circuitry of the power board before carrying out a voltage withstand test between the electric cir- cuitry and non current-carrying metal part of the Timer, in order to prevent the internal circuitry of the Timer from damage. It must be noted that although the electrical life expectancy of the H3DE Timer shown in the catalog is the same as the H3DR Timer shown in the catalog, the actual performance varies because the built-in relays are different as follows: Built-in relay for the H3DR: G2R; 100,000 operations min. (10 A for SPDT and 5 A for DPDT at
250 VAC, resistive load at
1,800 operations/h.) Built-in relay for the H3DE: G6RN; 50,000 operations min. (8 A at 250 VAC, resistive load at 360 operations/h.) Power 3 s min. Output state 1 Output state 2 In the interest of product improvement, specifications are subject to change without notice. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. L092-E1-05