Features

  • DIN Rail Mountable Single Point Input Modules
  • AC Inputs (Yellow Top), DC Inputs (White Top)
  • UL, cUL Recognized, CE Compliant
  • 4kV Optical isolation
  • Input and Output Barrier Strips Accept 14 to 28 AWG Wire
  • Open-Collector Output, with LED Status Indicator Part Number 84115501 84115502 84115503 Voltage Range 90-140 VAC/DC 180-280 VAC/DC 4-32 VDC Minimum Current mA 7 2 27 Maximum Current mA 14 5 35 Drop-out Current mA 3 1 1 Voltage for No Output (4) 50 VAC/DC 50 VAC/DC 2.2 VDC Allowable Current [mA] (4) 2.5 0.7 1 Part Number 84115501 84115502 84115503 Logic Supply Voltage Range [VDC] 4.5 to 30 4.5 to 30 4.5 to 30 Maximum Logic Supply Voltage [VDC] 30 30 30 Maximum Logic Supply Current mA 32 32 32 Maximum Supply Idle Current (5) 7 7 7 Maximum Current mA 50 50 50 Maximum Logic Leakage Current [µA] 10.0 10.0 10.0 Maximum Voltage Drop [VDC] 0.2 0.2 0.2 Maximum Turn-On Time [msec] (7) 20 20 5 Maximum Turn-Off Time [msec] (7) 30 30 10

www.sensata.comCopyright © 2018 Sensata Technologies, Inc. General Input/Output Isolation Voltage (8) 4000 Vrms Input/Output Capacitance 8 pF Operating Temperature Range -30 to 80°C Storage Temperature Range -40 to 100°C Line Frequency Range 47 to 63 Hz Weight 1.1 oz. (31.2g) GENERAL NOTES (1) Specifications apply to an ambient temperature of -30 to 80 °C unless otherwise noted. (2) Measured at maximum specified input voltage, 25°C. (3) Defined as the maximum current allowed through the module’s input to guarantee that the output will switch from “on” to “off”. Higher currents may result in the output remaining in the “on” state. (4) Defined as the maximum current allowed through the module’s input that will not switch the module’s output state from “off” to”on”. (5) At maximum specified logic voltage and 25°C. (6) Maximum allowable sinking current through the open collector output transistor. (7) At 15 VDC logic, 30 VDC output, 50 mA, 25°C and nominal input voltage. (8) At 25°C for 1 second maximum duration. EQUIVALENT CIRCUIT DIAGRAM / MECHANICAL SPECIFICATIONS All dimensions are in millimeters [inches] Tolerance: ±0.020 (±0.50)

+1 (877) 502 5500 – Option 2 sales.crydom@sensata.com Europe, Middle East & Africa +44 (1202) 416170 ssr-info.eu@sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 Rev:06/07/18 _ ECN 20395 FDE-07-01 Rev. B www.sensata.com CONTACT USCopyright © 2018 Sensata Technologies, Inc. Sensata Technologies, Inc. (“Sensata”) data sheets are solely intended to assist designers (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, evaluation and judgment in designing Buyer’s systems and products. Sensata data sheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular data sheet. Sensata may make corrections, enhancements, improvements and other changes to its data sheets or components without notice. Buyers are authorized to use Sensata data sheets with the Sensata component(s) identified in each particular data sheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATA SHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATA SHEETS OR USE OF THE DATA SHEETS, EXPRESS, IMPLIED OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATA SHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA. AGENCY APPROVALS & CERTIFICATIONS E46203 WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE

  • The product’s side panels may be hot, allow the product to cool before touching
  • Follow proper mounting instructions including torque values
  • Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Disconnect all power before installing or working with this equipment
  • Verify all connections and replace all covers before turning on power Failure to follow these instructions will result in death or serious injury.