© 2015 Bel Power Solutions, Inc. North America +1-866.513.2839 Asia-Pacific +86.755.29885888 Europe, Middle East +353 61 225 977 tech.support@psbel.com BCD.00371_AB  Three-Phase AC Input  Suitable for 3U or 5U Height Mounting  Single-Wire Current Share or Droop Current Share  Remote Voltage Adjust and Current Monitoring  Overtemperature, Overload and Overvoltage Protection  LED Supply Status Indicators  Current-Share Control for up to 30 Units  Front Panel Selectable-Input-Range  RoHS Compliant The FXC7000 Series of standalone or rack - mounted power systems provides true AC front-end capability to automatic test equipment, telecom, data communications, and other distributed power designs. The FXC systems may be paralleled up to 210 kW of output power and are intended for chassis - mounted installations with bolted connections. These power supplies provide excellent protection against input voltage transients. The FXC has its fan located at the front of the supply, and voltage adju st, indicator lights, output busbars, and connectors on the rear. Airflow is from the front through the rear. Alarm, monitoring, and control signals are floating from the main output and can be referenced to the positive or negative output or sense line of the power supply. The output is floating with respect to the chassis and may be used as a positive or negative polarity supply. The FXC7000 Series meets international safety requirements and is CE Marked to the Low Voltage Directive. This series operates on three-phase European voltages as well as (up to) 480 VAC, delta or wye.

© 2015 Bel Power Solutions, Inc. +1.866.513.2839 tech.support@psbel.com BCD.00371_AB MODEL OUTPUT VOLTAGE INPUT VOLTAGE RANGE 3-PHASE ADJUSTMENT RANGE MAXIMUM OUTPUT CURRENT LINE REGULATION LOAD REGULATION1 INITIAL SETTING ACCURACY FXC7000-48-SG2,3 48 V 180 to 264 VAC All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted. PARAMETER CONDITIONS / DESCRIPTION MIN NOM MAX UNITS Input Voltage-AC 3-phase delta low input range, nominal 200 240 VAC 3-phase delta high input range, nominal 380 480 VAC Continuous deviation from the above nominals -10 +10 % Input Current Per phase at full rated load FXC7000 at 180 VAC 30 Arms Inrush Surge Current Internally limited Vin = 264 VAC (one cycle). 25°C 30 Apk Vin = 528 VAC (one cycle). 25°C 15 Apk Input Frequency AC input 47 63 Hz Hold-up Time After last AC line peak at full power

208 VAC 17 ms

400 VAC 13 ms

Operating Frequency Switching frequency, fixed 100 kHz Power Factor 0.9 W/VA PARAMETER CONDITIONS / DESCRIPTION MIN NOM MAX UNITS Output Voltage Adjustment Range An additional 1.0 Volt is provided to the output terminals to provide for load lead losses 45.6 48 50.4 V Output Power Continuous duty rating 7000 W Output Current Continuous duty rating 145 A Efficiency Full rated load (208 VAC) 88 91 % Regulation Load, Maximum deviation with 0 to 100% load change: With Remote Sense connected: With Remote Sense not connected: Utilizing Droop Current Share: Line, Under all specified operating conditions. 0.2 0.75 2.0 0.2 Ripple & Noise Measured at mating connector w/ 0.01μF + 10μF Tant

20 MHz BW

100 MHz BW

% p-p Overshoot / Undershoot Output voltage overshoot/undershoot at turn-on 0 % Minimum Loads Minimum loading required to maintain regulation 0 A Transient Response Maximum recovery time, to within 1% of initial set point due to a 25% load change, 1A/μS. Time 800 μs Deviation 3.2 % Turn-On Delay Time required for initial output voltage stabilization after power-up 3 s Turn-on Rise Time Time required for output voltage to rise from 10% to 90% 100 ms 1 With Remote Sense connected.

2 User-selectable input voltage ranges

3 Please contact Bel Power Solutions for availability, if non-RoHS version FXC7000-48-S is needed

© 2015 Bel Power Solutions, Inc. +1.866.513.2839 tech.support@psbel.com BCD.00371_AB PARAMETER4, 5 CONDITIONS / DESCRIPTION MIN NOM MAX UNITS AC Power Fail Warning Warning provided prior to Vout dropping 5% after loss of AC input 4 ms Auxiliary Power Output voltage - diode isolated. Inclusive of line, load, and initial tolerances. 11.6 12.0 12.4 V Output current: 500 mA Current Monitor Monitor output current over a compliance range of 0~10 V. Normal output: 0.10 mA/A Total error current: 0.5 0.5 mA Current Share Static sharing deviation as a percent of full-load rating for loads >10%. Active 5 % Passive 10 % Input Range Select Status Maximum signal resistance in high input voltage range selection. 0.10 Ω Loss of Phase Warning Warning provided prior to protective reduction in current limit. 500 ms Output Inhibit Voltage required to enable supply (0.5 mA sink)6 1.0 V Output Interlock Voltage required to enable supply (6 mA sink) 5 1.0 V Output Overload Protection Straight line current limit (above approx. 5V Vout). 149 156 A Output Overload Warning Signal level on overload. 2.2 V Output Short Circuit Protection Occurs on overload when Vout is below approx. 5V. May operate in burst-mode. Iavg: 25 90 A Output Voltage Fault Signal Deviation from adjusted Vout that is considered as a fault. ±3 ±4 ±5 % Output Voltage Margin Output voltage swing available through Margin pin (analog). ±4.8 ±5.0 ±5.2 % Overtemperature/ Fan Failure Warning Time between fault warning and shutdown. Latching shutdown 100 ms Overvoltage Protection Latch style overvoltage protection 55.2 57.6 60.0 V Power Supply Present Signal Resistance to logic ground upon insertion of supply. 1000 Ω Remote Sense Maximum load lead loss compensation (round trip). 1.0 V PARAMETER CONDITIONS / DESCRIPTION MIN NOM MAX UNITS Agency Approvals Approved to the latest edition of the following standards: UL/CSA60950-1, IEC60950-1 and EN60950-1. CE marked for the Low Voltage Directive. Electromagnetic Interference FCC CFR title 47 Part 15 Sub-Part B - Conducted A Class EN55022 / CISPR 22 Conducted A Class ESD Susceptibility Per EN61000-4-2, level 4 8 kV Radiated Susceptibility Per EN61000-4-3, level 3 10 V/M EFT/Burst Per EN61000-4-4, level 4 ±4 kV Input Transient Protection Per EN61000-4-5 Line-to-Line 4 kV Line-to-Ground 3 kV Voltage Sag Immunity Per SEMI F47-0200 FXC/FXP6000 Pending Leakage Current Per UL60950 and EN60950 FXC7000 at 240 VAC, 60 Hz 5 mA FXC7000 at 400 VAC, 50 Hz 7 mA FXC7000 at 480 VAC, 60 Hz 10 mA 4 All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V. 5 In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature / fan fault, AC phase imbalance, output good, interlock open, and supply inhibited. The FXC also provides 4 LED’s indicating output loading. 6 Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable. Contact factory for additional design details.

© 2015 Bel Power Solutions, Inc. +1.866.513.2839 tech.support@psbel.com BCD.00371_AB PARAMETER CONDITIONS / DESCRIPTION MIN NOM MAX UNITS Altitude Operating 10k ASL Ft. Non-Operating 40k ASL Ft. Operating Temperature At 100% load: 0 40 °C At 50% load: 70 °C Storage Temperature -40 85 °C Temperature Coefficient 0°C to 70°C (after 15-minute warm-up) .02 %/°C Relative Humidity Non-Condensing 95 %RH Shock Operating: half-sine 10 ms, 3 axis +20 Gpk Non-operating: half-sine 10 ms, 3 axis +40 Vibration Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02îDA, 32-2000 Hz 1 Gpk Non-operating: random 10-2000 Hz 6.15 Grms Airflow Airflow provided through the supply from front to rear. 155 cfm 4.4 m3/min 555 lfm 2.8 m/s PARAMETER CONDITIONS / DESCRIPTION MIN NOM MAX UNITS Weight 27 lb (12 kg) Figure 1 - Rear and Front Views for FXC7000 5.00" (127mm) 8.00" (203.2mm) FRONT VIEWREAR VIEW INPUT VOLTAGE RANGE SELECT MODULE ROTA TE 180 DEGREES FOR 240 V AC INPUT VOLTAGE DISPLA Y CUTOUT 480VAC SIGNAL V adj DC OUTPUT P O S N E G PE AC INPUT T DC AC VOLTAGE ADJUST POT M4 THREAD 10mm 13mm 26-PIN CONNECTOR AMP PN: 749030-1 PIN 1 0.06 (1.7) 2 PL

5 LED INDICA TORS

MA TING CONNECTOR: CONNECTOR SHELL... AMP PN 748365-1 CONTACTS... AMP PN 748333-2

© 2015 Bel Power Solutions, Inc. +1.866.513.2839 tech.support@psbel.com BCD.00371_AB Figure 2 - FXC7000 Overall Size 2 PL 2 PL 15.17" (385.3mm) INSULA TOR BLOCK 10.260" (260.6mm)7.705" (195.7mm)3.510" (89.2mm)0.955" (24.3mm) 6.850" (174mm) 4.24" (107.6mm) 0.53" (13.4mm) 0.480" (12.2mm) 1.22" (31.1mm) 4.480" (113.8mm) DIA 0.25" (6.4mm) 0.70" (17.9mm) 0.955" (24.3mm) 3.510" (89.2mm) 13.455" (341.8mm) 0.20" (5.1mm) 7.705" (195.7mm) 1.10" (28mm)

2 PL 2 PL

3.60" (91.5mm) 1.100" (27.9mm) 5.42" (137.7mm) A A A A A A A AAA A AA AA A MAINTAIN 25 SQ IN MIN FREE AREA (FRONT AND REAR) FOR AIR COOLING BOTTOM VIEW SIDE VIEW FOR MOUNTING, USE M4 X 0.7 SCREWS, 8PL (MARKED A) ON SIDE OR BOTTOM WITH MAXIMUM PENETRATION 3.8mm. RECOMMENDED MOUNTING TORQUE 10.5 INCH LBS. (0.64N/M) <--AIRFLOW 0.85" (21.6mm) 1.10" (27.9mm) NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.