Technical content

Features

  • Three-phase AC input
  • Suitable for 3U or 5U height mounting
  • Single-wire current share or droop current share
  • Remote voltage adjust and current monitoring
  • Overtemperature, overload, and overvoltage protection
  • LED supply status indicators
  • Current share control for up to 30 units
  • Front panel selectable-input-range The FXC6000 Series of standalone or rack-mounted power systems provides true AC front-end capability to automatic test equipment, telecom, data commun- ications, and other distributed power designs. The FXC systems may be paralleled up to 180 kW of output power and is intended for chassis-mounted installations with bolted connections. These power supplies provide excellent protection against input voltage transients. The FXC has its fan located at the front of the supply, and voltage adjust, indicator lights, output bussbars, and connectors on the rear. Airflow is from the front through the rear. Alarm, monitoring, and control signals are floating from the main output and can be referenced to the positive or negative output or sense line of the power supply. The output is floating with respect to the chassis and may be used as a positive or negative polarity supply. The FXC6000 Series meets international safety requirements and is CE Marked to the Low Voltage Directive. This series operates on three-phase European voltages as well as (up to) 480VAC, D or Y. FXC6000 Front & Rear Views Chassis-Mountable Model MODEL OUTPUT INPUT VOLTAGE RANGE ADJUSTMENT MAXIMUM OUTPUT LINE LOAD INITIAL SETTING VOLTAGE 3-PHASE (VAC) RANGE CURRENT REGULATION REGULATION (NOTE 1) ACCURACY NOTES: 1) With Remote Sense connected. 2) User-selectable input voltage ranges. Input Specifications PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS Input Voltage - AC 3-phase delta low input range, nominal. 200 240 3-phase delta high input range, nominal. 380 480 Continuous deviation from the above nominals. -10 +10 % Input Current Per phase at full rated load. FXC6000 at 180 VAC: 28 A RMS Inrush Surge Current Internally limited. Vin = 264VAC (one cycle). 25° C: 38 APK Vin = 528VAC (one cycle). 25° C: 38 Input Frequency AC input. 50 60 Hz Hold-up Time After last AC line peak at full power. 208 VAC: 20 ms415 VAC: 20 Operating Frequency Switching frequency, fixed. 100 kHz Power Factor 0.90 W/VA

Description

Distributed Power Front-End

AUG 25, 2004 revised to JAN 09, 2007 Page 2 of 4 www.power-one.com FXC6000 AC-DC Series Data Sheet Output Specifications PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS Output Voltage An additional 1.0 Volt is provided to the output terminals to provide for 45.6 48 50.4 V Adjustment Range load lead losses. Output Power Continuous duty rating. 6000 Watts Output Current Continuous duty rating. 125 A Efficiency Full rated load (208Vac). 88 91 % Regulation Load, Maximum deviation with 0 to 100% load change: With Remote Sense connected: 0.2 With Remote Sense not connected: 0.75 % Utilizing Droop Current Share: 2.0 Line, Under all specified operating conditions. 0.2 Ripple & Noise Measured at mating connector w/ 0.01µF + 10µF Tant.

20 MHz BW: 1 % p-p

100 MHz BW: 2

Overshoot / Undershoot Output voltage overshoot/undershoot at turn-on. 0 % Minimum Loads Minimum loading required to maintain regulation. 0 A Transient Response Maximum recovery time, to within 1% of initial set Time: 400 µs point due to a 25% load change, 1A/µS. Deviation: 3 % Turn-On Delay Time required for initial output voltage stabilization after power-up. 3 s Turn-on Rise Time Time required for output voltage to rise from 10% to 90%. 100 ms Interface Signals and Internal Protection PARAMETER (NOTE 1,2) DESCRIPTION/CONDITIONS MIN NOM MAX UNITS AC Power Fail Warning Warning provided prior to Vout dropping 5% after loss of AC input. 5 ms Output current. 500 mA Current Monitor Monitor output current over a compliance range of 0~10V. Nominal full load output: 12.5 mA 50~100% load tolerance: -315 0 315 µA/A <50% load tolerance: -250 0 500 µA/A Current Share Static sharing deviation as a percent of full-load rating Active: 5 % for loads >10%. Passive: 10 Input Range Select Status Maximum signal resistance in high input voltage range selection. 0.10 /H9024 Loss of Phase Warning Warning provided prior to protective reduction in current limit. 500 ms Output Inhibit Voltage required to enable supply (0.5 mA sink). (NOTE 3) 1.0 V Output Interlock Voltage required to enable supply (6 mA sink). (NOTE 3) 1.0 V Output Overload Protection Straight line current limit (above approx. 5V Vout). 129 134 A Output Overload Warning Signal level on overload. 2.2 V Output Short Circuit Protection Occurs on overload when Vout is below approx. 5V. Iavg: 21 65 A May operate in burst-mode. Output Voltage Fault Signal Deviation from adjusted Vout that is considered as a fault. ±3 ±4 ±5 % Output Voltage Margin Output voltage swing available from Margin pin (analog). ±4.8 ±5.0 ±5.2 % Overtemperature/ Time between fault warning and shutdown. 100 ms Fan Failure Warning Latching shutdown. Overvoltage Protection Latch style overvoltage protection. 55.2 57.6 60.0 V Power Supply Present Signal Resistance to logic ground upon insertion of supply. 1000 /H9024 Remote Sense Maximum load lead loss compensation (round trip). 1.0 V NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V. 2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC ph ase imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED’s indicating output loading. 3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable. Contact factory for additional design details.

FXC6000 AC-DC Series Data Sheet AUG 25, 2004 revised to JAN 09, 2007 Page 3 of 4 www.power-one.com Safety, Regulatory, and EMI Specifications PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS Agency Approvals UL60950/CSA60950-00 (cULus), IEC60950-1, EN60950 (TÜV), CE marked for the Low Voltage Directive Electromagnetic Interference FCC CFR title 47 Part 15 Sub-Part B - Conducted. A EN55022 / CISPR 22 Conducted. A Class ESD Susceptibility Per EN61000-4-2, level 4. 8 kV Radiated Susceptibility Per EN61000-4-3, level 3. 10 V/M EFT/Burst Per EN61000-4-4, level 4. ±4 kV Input Transient Protection Per EN61000-4-5. Line-to-Line: 4 kVLine-to-Ground: 3 Voltage Sag Immunity Per SEMI F47-0200 FXC/FXP6000 Pending Leakage Current Per UL60950 and FXC6000 at 240 VAC, 60 Hz: 5 EN60950: FXC6000 at 400 VAC, 50 Hz: 7 mA FXC6000 at 480 VAC, 60 Hz: 10 Environmental Specifications PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS Altitude Operating. 10k ASL Ft. Non-Operating. 40k Operating Temperature At 100% load: 0 50 °C At 60% load: 70 Storage Temperature -40 85 °C Temperature Coefficient 0°C to 70°C (after 15-minute warm-up). .02 %/°C Relative Humidity Non-Condensing. 95 %RH Shock Operating: half-sine 10 ms, 3 axis +20 GPK Non-operating: half-sine 10 ms, 3 axis +40 Vibration Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02îDA, 32-2000 Hz 1 G PK Non-operating: random 10-2000 Hz 6.15 Grms Airflow Airflow provided through the supply from front to rear. 135 cfm 3.8 m 3/min 483 lfm 2.5 m/s Weight 27 lb 12 kg NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change dependin g on the date manufactured. Specifications are subject to change without notice.

AUG 25, 2004 revised to JAN 09, 2007 Page 4 of 4 www.power-one.com FXC6000 AC-DC Series Data Sheet 2 PL 2 PL 15.17" (385.3mm) INSULATOR BLOCK 10.260" (260.6mm)7.705" (195.7mm)3.510" (89.2mm)0.955" (24.3mm) 6.850" (174mm) 4.24" (107.6mm) 0.53" (13.4mm) 0.480" (12.2mm) 1.22" (31.1mm) 4.480" (113.8mm) DIA 0.25" (6.4mm) 0.70" (17.9mm) 0.955" (24.3mm) 3.510" (89.2mm) 13.455" (341.8mm) 0.20" (5.1mm) 7.705" (195.7mm) 1.10" (28mm)

2 PL 2 PL

3.60" (91.5mm) 1.100" (27.9mm) 5.42" (137.7mm) A A A AA A A AAA A AA AA A MAINTAIN 25 SQ IN MIN FREE AREA (FRONT AND REAR) FOR AIR COOLING BOTTOM VIEW SIDE VIEW 5.00" (127mm) 8.00" (203.2mm) FRONT VIEWREAR VIEW FOR MOUNTING, USE M4 X 0.7 SCREWS, 8PL (MARKED A) ON SIDE OR BOTTOM WITH MAXIMUM PENETRATION 3.8mm. RECOMMENDED MOUNTING TORQUE 10.5 INCH LBS. (0.64N/M) <--AIRFLOW INPUT VOLTAGE RANGE SELECT MODULE ROTATE 180 DEGREES FOR 240 VAC INPUT VOLTAGE DISPLAY CUTOUT 480VAC 0.85" (21.6mm) 1.10" (27.9mm) SIGNAL Vadj DC OUTPUT POS NEG PE AC INPUT T DC AC VOLTAGE ADJUST POT M4 THREAD 10mm 13mm 26-PIN CONNECTOR AMP PN: 749030-1 PIN 1 0.06 (1.7) 2 PL

5 LED INDICATORS

MATING CONNECTOR: CONNECTOR SHELL... AMP PN 748365-1 CONTACTS... AMP PN 748333-2