FRN-R-70 EATON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Fusetron™ FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses Catalog symbols:
- FRN-R-_ Description: Eaton Bussmann® series advanced protection, energy efficient FRN-R Class RK5 dual element, current-limiting, time-delay fuses. Time-delay – 10 seconds (minimum) at 500% of rated current. Specifications: Ratings
- Volts
- 250Vac
- 125Vdc (110-200A)
- 250Vdc (225-600A)
- Amps 70-600A
- Interrupting rating
- 200kA Vac RMS Sym.
- 20kA Vdc Agency information
- UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
- CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
- CE Catalog numbers (amps) FRN-R-70 FRN-R-125 FRN-R-350 FRN-R-75 FRN-R-150 FRN-R-400 FRN-R-80 FRN-R-175 FRN-R-450 FRN-R-85 FRN-R-200 FRN-R-500 FRN-R-90 FRN-R-225 FRN-R-600 FRN-R-100 FRN-R-250 FRN-R-110 FRN-R-300 Carton Quantity: Amp rating Carton qty. 70 – 100 5 110 – 600 1 Features:
- Provides motor overload, ground fault and short-circuit protection
- Helps protect motors against burnout from overloads and single-phasing when sized properly
- Simplifies and improves blackout prevention (selective coordination)
- Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection
- The overload element provides protection against low level overcurrent of overloads and will hold on inrush current which is five times greater than the amp rating of the fuse for a minimum of ten seconds
FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses Eaton.com/bussmannseries Recommended fuse blocks: Fuse amps 1-pole 2-pole 3-pole 70-100 RM25100-1CR RM25100-2CR RM25100-3CR 110-200 RM25200-1CR RM25200-2CR RM25200-3CR 225-400 RM25400-1CR RM25400-2CR RM25400-3CR 450-600 RM25600-1CR RM25600-2CR RM25600-3CR For additional information on the RM 250 volt fuse blocks, see product brochure no. 3192. use reducers for Class R fuses Fuse size Amp size of fuse block or disconnect switch Catalog no. (pairs) 65 to 100A 400A No.2641-R* 110 to 200A No.242-R* 65 to 100A 600A No.2661-R* 110 to 200A No.2662-R* 225 to 400A No.2664-R*† * These reducers are not CSA Certified. † Single reducer only (pair not required) For additional information on Class R fuse reducers, see data sheet no 1118. 5.88” 1.06” 7.13” 1.56” 8.63” ± 0.09 2.38” ± 0.02 10.38” ± 0.09 2.88” ± 0.02 70 to 100A 110 to 200A 225 to 400A 450 to 600A Dimensions - in:
FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses Eaton.com/bussmannseries Amp rating Current in amps Time in seconds 100 200 400 600 Time-current curves — average melt:
FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses Technical Data 1020 Effective February 2016 Eaton, Bussmann and Fusetron are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use the Eaton trademarks without prior written consent of Eaton. Eaton
1000 Eaton Boulevard
Cleveland, OH 44122 Eaton.com Bussmann Division
114 Old State Road
Ellisville, MO 63021 United States Eaton.com/bussmannseries © 2016 Eaton All Rights Reserved Printed in USA Publication No. 1020 — BU-SB13731 February 2016 Follow us on social media to get the latest product and support information. The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Current-limiting effects: Prosp. S.C.C. Let-through current (apparent RMS Sym. vs. fuse rating) — 100A 200A 400A 600A 5000 3000 5000 5000 5000 10,000 4000 7000 10,000 10,000 15,000 5000 8000 11,000 15,000 20,000 5000 8000 12,000 16,000 25,000 6000 9000 13,000 17,000 30,000 6000 10,000 14,000 18,000 35,000 6000 10,000 15,000 19,000 40,000 7000 11,000 15,000 20,000 50,000 7000 11,000 17,000 21,000 60,000 8000 12,000 18,000 22,000 70,000 8000 13,000 19,000 23,000 80,000 8000 13,000 19,000 24,000 90,000 9000 14,000 20,000 25,000 100,000 9000 14,000 21,000 26,000 150,000 10,000 16,000 24,000 29,000 200,000 11,000 18,000 26,000 32,000 400000 9000 8000 7000 7000 6000 6000 300000 200000 100000 5000 4000 4000 90000 3000 2000 1000 3000 70000 80000 70000 60000 B A 50000 60000 200000 20000 2000 40000 100000 50000 10000 5000 1000 30000 90000 80000 40000 9000 8000 30000 20000 10000 600A 400A 200A 100A AMP RATING RMS SYMMETRICAL CURRENT IN AMPS A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS) INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS Current-limitation curves: