FPBBRAIL SCHURTER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 7
Technical content
1-Phase AC Filters / DC Filters FPBB RAILhttps://www.schurter.com /PG84 EMC Products AC/DC Filter 2-Stage, DIN Rail Mounting, Overcurrent and Overvoltage Protection Housing RI Housing RI with Circuit Breaker Housing TI See below: Approvals and Compliances
Description
- Single-phase line filter in standard and medical versions - 2-Stages filter - Very high attenuation - broadband - Fuseholder - Thermal circuit breaker - Surge protection Unique Selling Proposition - Slim filter for DIN-rail mounting or chassis mounting - With fuse holder or circuit breaker for equipment - With overvoltage protection - Quick wiring with cage clamp terminals Characteristics - Protection against interference voltage from the mains Possible interferences generated in the equipment are strongly attenu- ated - Especially designed for electric switch and control cabinets - Suitable for use in equipment according to IEC/UL 60950 Suitable for use in medical equipment according to IEC/UL 60601-1 Weblinks pdf datasheet, html-datasheet, General Product Information, Distributor- Stock-Check, Detailed request for product, Microsite, Landing Page Technical Data Ratings IEC 1 - 16 A @ Ta 40 °C / 250 VAC; 50 Hz ␣ 48/250 VDC Ratings UL/CSA 1 - 16 A @ Ta 40 °C / 125/250 VAC; 60 Hz ␣ 48/250 VDC Leakage Current standard < 1 mA (250 V / 50 Hz) Dielectric Strength 1.7 kVDC between L-N 2.7 kVDC between L/N-PE Test voltage (2 sec) Allowable Operation Tempe- rature -40 °C to 100 °C Climatic Category 40/100/21 acc. to IEC 60068-1 IP-Protection IP 20 IEC 60529 Protection Class Suitable for appliances with protection class I acc. to IEC 61140 Terminal Spring cage terminals , 0.2 - 2.5 mm², 24 - 12 AWG Material: Housing Plastics, black, UL 94V-0 Circuit Breakers Acc. IEC/EN 60934, UL 1077, CSA 22.2 no. 235 3 - 15 A Short circuit capacity Icn: 2000 A ␣ Climatic Category 05 / 060 / 21 acc. to IEC 60068-1 Fuseholder 1-pole, Shocksafe category PC2 acc. to IEC 60127-6 for fuse-links 5 x 20 mm Rated Power Acceptance @ Ta 23 °C 5 x 20: 2.5 W Power Acceptance @ Ta > 23°C Admissible power acceptance at higher ambient temperature see derating cur- ves ␣ Climatic Category 40 / 085 / 21 acc. to IEC 60068-1 Surge protection 320 VAC , 420 VDC , 0.4 W ␣ Climatic Category 40 / 085 / 21 acc. to IEC 60068-1 Line Filter Standard and Industrial Version, IEC 60939, UL 60939-3, CSA C22.2 no. 8 Technical Details MTBF > 200'000 h acc. to MIL-HB-217 F Approvals and Compliances Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about Approvals
1-Phase AC Filters / DC FiltersFPBB RAIL https://www.schurter.com /PG84 EMC Products Approvals The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products. Approval Reference Type: FPBB Rail Approval Logo Certificates Certification Body Description VDE Approvals VDE Certificate Number: 40047767 UL Approvals UL UL File Number: E495089 Product standards Product standards that are referenced Organization Design Standard Description Designed according to IEC 60320-1 Appliance couplers for household and similar general purposes Designed according to IEC 60939 Passive filters for suppressing electromagnetic interference Designed according to IEC 60127-6 Miniature fuses. Part 6. Fuse-holders for miniature fuse-links Designed according to UL 498 Standard for Attachment Plugs and Receptacles Designed according to UL 60939-3 Electromagnetic interference filters Designed according to CSA C22.2 no. 42 General Use Receptacles, Attachment Plugs, and Similar Wiring Devices Designed according to CSA C22.2 no. 8 Electromagnetic interference (EMI) filters Application standards Application standards where the product can be used Organization Design Standard Description Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information technology equipment. Designed for applications acc. IEC 60601-1 Medical electrical equipment - Part 1: General requirements for basic safety and essential performance Compliances The product complies with following Guide Lines Identification Details Initiator Description CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. RoHS SCHURTER AG EU Directive RoHS 2011/65/EU China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March 2007. It is similar to the EU directive RoHS. REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. Medical Equipment SCHURTER AG Suitable for use in medical equipment according to IEC/UL 60601-1
1-Phase AC Filters / DC Filters FPBB RAILhttps://www.schurter.com /PG84 EMC Products Dimension [mm] Housing RI Ø 10.3 85 25 78.9 89.5 Housing TI 82.6 3.6 85 25 104 Ø 4.9Ø 10.3
1-Phase AC Filters / DC FiltersFPBB RAIL https://www.schurter.com /PG84 EMC Products Diagrams Diagram S1 LINE LOADVDR L N L R L ECx Cx Cy Cy 1) Line, 2) Load VDR only for versions with overvoltage protection Diagram S2 LINE LOADVDR L N L R LF ECx Cx Cy Cy 1) Line, 2) Load VDR only for versions with overvoltage protection Diagram S3 LINE LOADVDR L N L R L CB ECx Cx Cy Cy 1) Line, 2) Load VDR only for versions with overvoltage protection Diagram S4 LINE LOADVDR L N L R L Cx Cx 1) Line, 2) Load VDR only for versions with overvoltage protection Diagram S5 LINE LOADVDR L N L R LF Cx Cx 1) Line, 2) Load VDR only for versions with overvoltage protection Diagram S6 LINE LOADVDR L N L R L CB Cx Cx 1) Line, 2) Load VDR only for versions with overvoltage protection Attenuation Loss - - - - 50Ω differential mode _____ 50Ω common mode Standard version 1 A 3 A 6 A 10 A 12 A 16 A
1-Phase AC Filters / DC Filters FPBB RAILhttps://www.schurter.com /PG84 EMC Products Medical version (M5) 1 A 3 A 6 A 10 A 12 A 16 A Medical version (M80) 1 A 3 A 6 A 10 A 12 A 16 A All Variants Rated current Rated vol- tage Rated vol- tage Filter-Type Lea- kage Current Ri Power Loss Fuse holder Circuit- breaker for equipment Surge protection Dia- gram Housings Weight Order Number [A] [VAC] [VDC] [mA] [mΩ] [W] [g] 1 250 250 Standard Version 0.5 770 1.3 - S1 RI 115 3-103-673 █ 1 250 250 Standard Version 0.5 770 1.3 - S1 TI 115 3-103-714 1 250 250 Standard Version 0.5 780 1.3 l - S2 RI 115 3-103-679 1 250 250 Standard Version 0.5 770 1.3 VDR S1 RI 115 3-103-699 1 250 250 Standard Version 0.5 780 1.3 l VDR S2 RI 115 3-103-705 █ 1 250 250 Standard Version 0.5 780 1.3 l VDR S2 TI 115 3-103-736 1 250 250 Medical Version (M5) 0.005 770 1.3 - S4 TI 115 3-103-980 1 250 250 Medical Version (M5) 0.005 780 1.3 l - S5 TI 115 3-103-986 3 250 250 Standard Version 0.5 88 1.3 - S1 RI 115 3-103-674 █
1-Phase AC Filters / DC FiltersFPBB RAIL https://www.schurter.com /PG84 EMC Products Rated current Rated vol- tage Rated vol- tage Filter-Type Lea- kage Current Ri Power Loss Fuse holder Circuit- breaker for equipment Surge protection Dia- gram Housings Weight Order Number [A] [VAC] [VDC] [mA] [mΩ] [W] [g] 3 250 250 Standard Version 0.5 88 1.3 - S1 TI 115 3-103-715 █ 3 240 48 Standard Version 0.5 250 1.3 l - S3 RI 120 3-103-693 3 250 250 Standard Version 0.5 88 1.3 VDR S1 RI 115 3-103-700 3 250 250 Standard Version 0.5 98 1.3 l VDR S2 RI 115 3-103-706 █ 3 250 250 Standard Version 0.5 98 1.3 l VDR S2 TI 115 3-103-737 3 240 48 Standard Version 0.5 250 1.3 l VDR S3 RI 120 3-103-709 █ 3 240 48 Standard Version 0.5 250 1.3 l VDR S3 TI 120 3-103-720 3 250 250 Medical Version (M5) 0.005 88 1.3 - S4 TI 115 3-103-981 3 250 250 Medical Version (M5) 0.005 98 1.3 l - S5 TI 115 3-103-987 6 250 250 Standard Version 0.5 30 1.73 - S1 RI 115 3-103-675 █ 6 250 250 Standard Version 0.5 30 1.73 - S1 TI 115 3-103-716 6 250 250 Standard Version 0.5 40 1.73 l - S2 RI 115 3-103-681 █ 6 250 250 Standard Version 0.5 30 1.73 VDR S1 RI 115 3-103-701 6 250 250 Standard Version 0.5 40 1.73 l VDR S2 RI 115 3-103-707 █ 6 250 250 Standard Version 0.5 40 1.73 l VDR S2 TI 115 3-103-738 6 240 48 Standard Version 0.5 60 1.3 l VDR S3 RI 120 3-103-710 █ 6 240 48 Standard Version 0.5 60 1.73 l VDR S3 TI 120 3-103-721 6 250 250 Medical Version (M5) 0.005 30 1.73 - S4 TI 115 3-103-982 6 250 250 Medical Version (M5) 0.005 40 1.73 l - S5 TI 115 3-103-988 10 250 250 Standard Version 0.5 25 2.64 - S1 RI 115 3-103-676 █ 10 250 250 Standard Version 0.5 25 2.64 - S1 TI 115 3-103-717 █ 10 240 48 Standard Version 0.5 30 2.64 l - S3 RI 120 3-103-695 █ 10 250 250 Standard Version 0.5 25 2.64 VDR S1 RI 115 3-103-702 10 250 250 Standard Version 0.5 35 2.64 l VDR S2 RI 115 3-103-708 █ 10 250 250 Standard Version 0.5 35 2.64 l VDR S2 TI 115 3-103-739 10 240 48 Standard Version 0.5 30 2.64 l VDR S3 RI 120 3-103-711 █ 10 240 48 Standard Version 0.5 30 2.64 l VDR S3 TI 120 3-103-752 10 250 250 Medical Version (M5) 0.005 25 2.64 - S4 TI 115 3-103-983 10 250 250 Medical Version (M5) 0.005 35 2.64 l - S5 TI 115 3-103-989 12 250 250 Standard Version 0.5 12 1.6 - S1 RI 115 3-103-677 █ 12 250 250 Standard Version 0.5 12 1.6 - S1 TI 115 3-103-718 12 250 250 Standard Version 0.5 12 1.6 VDR S1 RI 115 3-103-703 12 240 48 Standard Version 0.5 25 1.6 l VDR S3 RI 120 3-103-712 █
1-Phase AC Filters / DC Filters FPBB RAILhttps://www.schurter.com /PG84 EMC Products Rated current Rated vol- tage Rated vol- tage Filter-Type Lea- kage Current Ri Power Loss Fuse holder Circuit- breaker for equipment Surge protection Dia- gram Housings Weight Order Number [A] [VAC] [VDC] [mA] [mΩ] [W] [g] 12 240 48 Standard Version 0.5 25 1.6 l VDR S3 TI 120 3-103-753 12 250 250 Medical Version (M5) 0.005 12 1.6 - S4 TI 115 3-103-984 15 240 32 Standard Version 0.5 20 1.55 l VDR S3 RI 120 3-103-713 █ 15 240 32 Standard Version 0.5 20 1.55 l VDR S3 TI 120 3-103-754 16 250 250 Standard Version 0.5 8 1.55 - S1 RI 115 3-103-678 █ 16 250 250 Standard Version 0.5 8 1.55 - S1 TI 115 3-103-719 █ 16 250 250 Standard Version 0.5 8 1.55 VDR S1 RI 115 3-103-704 16 250 250 Medical Version (M5) 0.005 8 1.55 - S4 TI 115 3-103-985 █ Most Popular. Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER Packaging unit 20 Pcs The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments. Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability and test each product selected for their own applications. 11.06.2018