1-Phase AC Filters / DC Filters FMBB NEOhttps://www.schurter.com /PG84 EMC Products AC Filter 2-Stage, Broad Band Attenuation Quick connect terminals 6.3x0.8 mm Case MB Quick connect terminals 6.3x0.8 mm Case MF Quick connect terminals 6.3x0.8 mm Case 09 See below: Approvals and Compliances
Description
- Line filter in standard and medical version - 2 stages - 3 Designs: C) high symmetrical and asymmetrical noise attenuation D) Excellent high frequency noise attenuation F) Excellent low frequency noise attenuation Unique Selling Proposition - Broad band attenuation - 3 Filter designs for various applications - Compact and fully potted - Optional wire leads Characteristics - Designed for current applications of 1 - 36 A - Protection against interference voltage from the mains Possible interferences generated in the equipment are strongly attenu- ated - Especially designed for industrial applications such as: Frequency Con- verters, Stepper Motor Drives, UPS-Systems, Inverters - Suitable for use in equipment according to IEC/UL 60950 Suitable for use in medical equipment according to IEC/UL 60601-1 Other versions on request - Version with wire connection References Alternative: Standard version Weblinks pdf datasheet, html-datasheet, General Product Information, Distributor- Stock-Check, Detailed request for product, Microsite Caractéristiques techniques Ratings IEC 1 - 36 A @ Ta 40 °C / 250 VAC; 50 Hz Valeurs nominales UL/CSA 1 - 30 A @ Ta 40 °C / 125/250 VAC; 60 Hz Leakage Current standard < 0.5 mA (250 V / 60 Hz) medical (M5) < 5 µA resp. (M80) < 80 µA (250 V / 60 Hz) Résistance diélectrique 1.7 kVDC between L-N 2.75 kVDC between L/N-PE Test voltage (2 sec) Température de fonctionne- ment admissible -25 °C to 100 °C Climatic Category 25/100/21 acc. to IEC 60068-1 IP-Protection from rear-side IP 20 IEC 60529 Protection Class Suitable for appliances with protection class I acc. to IEC 61140 Borne Quick connect terminal 6.3 x 0.8 mm Bolt and nut M4 Matériau: Boîtier Aluminum Line Filter Standard and Medical Version, IEC 60939, UL 1283, CSA C22.2 no. 8 Technical Details MTBF > 200'000 h acc. to MIL-HB-217 F Approvals and Compliances Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about Approvals
1-Phase AC Filters / DC FiltersFMBB NEO https://www.schurter.com /PG84 EMC Products Approvals The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products. Approval Reference Type: FMBB NEO Approval Logo Certificates Certification Body Description VDE Approvals VDE Certificate Number: 40030410 UL Approvals UL UL File Number: E72928 Product standards Product standards that are referenced Organization Design Standard Description Designed according to IEC 60320-1 Appliance couplers for household and similar general purposes Designed according to IEC 60939 Passive filters for suppressing electromagnetic interference Designed according to IEC 60127-6 Miniature fuses. Part 6. Fuse-holders for miniature fuse-links Designed according to UL 498 Standard for Attachment Plugs and Receptacles Designed according to UL 1283 Electromagnetic interference filters Designed according to CSA C22.2 no. 42 General Use Receptacles, Attachment Plugs, and Similar Wiring Devices Designed according to CSA C22.2 no. 8 Electromagnetic interference (EMI) filters Application standards Application standards where the product can be used Organization Design Standard Description Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information technologyequipment. Designed for applications acc. IEC 60601-1 Medical electrical equipment - Part 1: General requirements for basic safety and essential performance Compliances The product complies with following Guide Lines Identification Details Initiator Description CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. RoHS SCHURTER AG EU Directive RoHS 2011/65/EU China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March 2007. It is similar to the EU directive RoHS. REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. Medical Equipment SCHURTER AG Suitable for use in medical equipment according to IEC/UL 60601-1
1-Phase AC Filters / DC Filters FMBB NEOhttps://www.schurter.com /PG84 EMC Products Dimension [mm] Case 09 with quick connect terminals max. 77 max. 52 max. 46 17.527 1) 2) 4.8 (2x) ±0.3 6.3x0.8 (5x) max. 31 7.5 60.4±0.5 1) Line 2) Load Case MB with quick connect terminals max. 156 max. 131 max. 58 15.227 1) 2) 5.3 (2x) ±0.3 6.3x0.8 (5x) max. 46 max. 156 144 ±0.5 140 ±0.5 1) Line 2) Load
1-Phase AC Filters / DC FiltersFMBB NEO https://www.schurter.com /PG84 EMC Products Case MB with bolt and nut M4 1) 2) max. 160 max. 58 max. 131 15.2 max. 46 max. 156 140 ±0.3 ±0.5 144±0.5 5.3 (4x) (2x) 1) Line 2) Load 3) Nut torque 0.8...1 Nm, keep lock-nut fastened 4) Lock-nut do not unscrew Case MC with quick connect terminals max. 90 max. 66 max. 51 11.627 1) 2) 5.3 (2x) ±0.3 6.3x0.8 (5x) max. 31 6.9 75 ±0.5 1) Line 2) Load
1-Phase AC Filters / DC Filters FMBB NEOhttps://www.schurter.com /PG84 EMC Products Case MD with quick connect terminals max. 90 max. 66 max. 51 11.627 1) 2) 5.3 (2x) ±0.3 6.3x0.8 (5x) max.41 75±0.5 1) Line 2) Load Case ME with quick connect terminals max. 112 max. 87 max. 52 1227 1) 2) 5.3 (2x) ±0.3 6.3x0.8 (5x) max. 46 max. 115 104.5 ±0.5 97.5 ±0.5 1) Line 2) Load
1-Phase AC Filters / DC FiltersFMBB NEO https://www.schurter.com /PG84 EMC Products Case MF with quick connect terminals max. 123 max. 98 max. 85 1) 2) 47.5 ±0.5 54.5 ±0.5 6.3x0.8 (5x) max. 59 16.1 max. 120 109 ±0.3 4.4 ±0.3 (4x) 1) Line 2) Load Case MF with bolt and nut M4 max. 130 max. 98 max. 85 1) 2) 47.5 ±0.5 54.5 ±0.5 max. 59 max. 120 109 ±0.3 (4x) 4.4 ±0.3 (4x) 1) Line 2) Load 3) Nut torque 0.8...1 Nm, keep lock-nut fastened 4) Lock-nut do not unscrew
1-Phase AC Filters / DC Filters FMBB NEOhttps://www.schurter.com /PG84 EMC Products Case with wire leads L PE N 1) 2) 1 - 3 A © A WG 20 6 - 10 A © A WG 18 12 - 16 A © A WG 16
20 A © A WG 14
25 - 30 A © A WG 12
36 A © A WG 10
140 ±5 140 ±5 1) Line 2) Load 3) Brown 4) Yellow-Green 5) Blue Diagrams Design C and D 1) 2) 1) Line, 2) Load Bleeding resistor R = 1 MΩ Medical (M5) without Cy Design F 1) 2)
1-Phase AC Filters / DC FiltersFMBB NEO https://www.schurter.com /PG84 EMC Products Standard version
1 A / Design C
3 A / Design C
6 A / Design C
10 A / Design C
12 A / Design C
16 A / Design C
20 A / Design C
30 A / Design C
1 A / Design D
3 A / Design D
6 A / Design D
10 A / Design D
12 A / Design D
16 A / Design D
25 A / Design D
36 A / Design D
1 A / Design F
3 A / Design F
6 A / Design F
10 A / Design F
12 A / Design F
16 A / Design F
1-Phase AC Filters / DC Filters FMBB NEOhttps://www.schurter.com /PG84 EMC Products Medical version (M5)
1-Phase AC Filters / DC FiltersFMBB NEO https://www.schurter.com /PG84 EMC Products Medical version (M80)
1-Phase AC Filters / DC Filters FMBB NEOhttps://www.schurter.com /PG84 EMC Products All Variants Rated current Filter-Type Borne Design L L1 Cx Cy Ri Power Loss Weight Housings Packa- ging Order Number [A] [mH] [mH] [µF] [nF] [mΩ] [W] [g] [ST]
1-Phase AC Filters / DC FiltersFMBB NEO https://www.schurter.com /PG84 EMC Products Rated current Filter-Type Borne Design L L1 Cx Cy Ri Power Loss Weight Housings Packa- ging Order Number [A] [mH] [mH] [µF] [nF] [mΩ] [W] [g] [ST] █ Most Popular. Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER Design C) high symmetrical and asymmetrical noise attenuation D) Excellent high frequency noise attenuation F) Excellent low frequency noise attenuation The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments. Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability and test each product selected for their own applications. 12.03.2018