www.schurter.com/pg80 EMC Products 1-stage filter for 3-phase systems with neutral conductor

Description

  • Terminals for three phases, neutral conductor and ground - Very high symmetrical and asymmetrical attenuation loss - In the frequency range from 10kHz up to 300MHz Standards - IEC 60939 - UL 1283, Edition 5, CSA 22.2 No. 8-M1986, @ Ta 75 °C

Applications

  • Voltage rating 480 VAC for world wide acceptance - Protection against interference voltage from the mains - For standard and industrial applications - Qualified for use in equipment according IEC/EN 60950 References General Product Information Weblinks Approvals, RoHS, CHINA-RoHS, e-Store, Distributor-Stock-Check T echnical Data Rated Current 6 - 550 A Rated voltage 275 - 480 VAC, 50/60 Hz Approval for 6 - 550 A @ 40 (75) °C / 275/480 VAC Overload Current 1.5 x Ir Leakage Current industrial < 5 mA (440 V / 50 Hz) Dielectric Strength for 480 VAC 2.25 kVDC between L-L 1.7 kVDC between L-N 3 kVDC between L-PE 2.7 kVDC between N-PE Test voltage (2 sec) Number of Filter Stages 1 Weight 0.95 - 24.5 kg Material: Housing Metal Sealing Compound UL 94V-0 Mounting Screw-on mounting on chassis, from top Terminal Screw Clamp Operating Temperature [°C] -25 °C to 100 °C Climatic Category 25/100/21 acc. to IEC 60068-1 Degree of Protection IP 20 acc. to IEC 60529 Protection Class Suitable for appliances with protection class 1 acc. to IEC 61140 MTBF > 200'000 h acc. to MIL-HB-217 F Dimensions Case 24-3 51±0.3 5.3 ±0.3 max. 137 (7) max. 106 max. 100 max. 86 max. 58 (29.5) (17) 1) 2) 1) Line 2) Load 3) Nut torque 3...4 Nm Case 31-4 115 ±0.3 max. 217 max. 116 max. 181 (30) 100 max. 61 (7) (17) max. 86 6.5±0.3 1) 2)

www.schurter.com/pg80 EMC Products Case 32-4 115 ±0.3 237 max. 151 max. (41) 135 66 max. (7) (17) 6.5±0.3 1) 2) 201 max. 121 max. Case 32-8 6.5 ±0.3 1) 2) 237 max. 201 max. 115 ±0.3 135 151 max. (41) 121 max. 66 max. (2) (17) Case 34-4 6.5 ±0.3 1) 2) 250 max. 201 max. 115 ±0.3 135 151 max. (41) 121 max. 66 max. (10) (17) Case 37-4 6.5x15 1) 2) M10 378 max. 301 max. 325±1 110 150 max. (42) 81 max. (15) (58) ±0.3 3)3) Case 53-4 1) 2) 308 max. 231 max. 115 ±0.3 135 151 max. (45) 66 max. (13) (34) 6.5±0.3 121 max. 1) Line 2) Load 3) Tightening torque 3...4 Nm 4) Tightening torque 10...17 Nm 5) Do not unscrew lock-nut Case 54-4 1) 2) M10 387 max. 301 max. 325 ±1 110 150 max. (45) 81 max. (14) (58) 6.5x15 ±0.3 5)5)

www.schurter.com/pg80 EMC Products Case 55-4 1) 2) M12 591 max. 400 max. 280 ±0.5 200 232 max. 171 max. 169 max. (50) 9±0.5(30) 1) Line 2) Load 3) Nut torque 14...30 Nm 4) Do not unscrew lock-nut Case 56-4 1) 2) M12 615 max. 400 max. 280 ±0.5 200 232 max. 171 max. 169 max. (50) 9±0.5(30) Case KQ max. 340 max. 258 max. 158 (4x) max. 300 278 6.4 ±0.3 130 ±0.3 max. 150 max. 25 Nm (4x) 303±1 (4x) 10.5 ±0.3 (4x) 33 92 2)1) 1) Line 2) Load 3) Torsional stress at flat copper max. 25 Nm T echnical data to the filter components Rated Current L [mH] C [μF] C [μF] C3 [nF] C4 [nF] C5 [μF] C6 [μF] R [MΩ] R [MΩ] R3 [MΩ] R4 [MΩ] 8 (5) 8 1.0 - 100 10 2.2 - - - 1 2.2 25 (13) 2.6 4.4 1 10 47 4.4 1 - 1 1 2.2 36 (19) 1.8 4.4 1 10 47 4.4 1 2.2 1 1 - 50 (32) 0.8 4.4 1 10 100 4.4 1 2.2 1 1 - 80 (43) 0.9 6.6 1 47 100 6.6 1 2.2 1 1 - 64 (34) 0.6 4.4 1 10 100 4.4 1 2.2 1 1 - 110 (66) 0.5 6.6 1 47 100 6.6 1 2.2 1 1 -

www.schurter.com/pg80 EMC Products Diagrams 1) Power Line Derating Curves Permissible Working Current as a Function of Ambient TemperatureAdmissible operating current in % of In 100 0 20 40 60 75 100 UL Listet Ambient air temperature Ta °C Attenuation Loss - - - - differential mode _____ common mode Industrial Version 6A (FMAD-0924-0610) 8A (FMAD-0931-0810) 16A (FMAD-0931-1610) 16A (FMAD-0932-1610) 25A (FMAD-0932-2510) 36A (FMAD-0934-3610) 50A (FMAD-0934-5010) 64A (FMAD-0953-6410) 80A (FMAD-0937-8010) 110A (FMAD-0954-H110) 180A (FMAD-0955-H210) 250A FMAD-0956-H310 550A FMAD-09KQ-H650

www.schurter.com/pg80 EMC Products Variants Rated Current Rated Voltage [VAC] Tripped Power Dissi- pation [W] Contact Resi- stance [mΩ] Weight [kg] Clamps [mm] Housing Order Number 6 (4.8) 275 - 480 3.9 27 0.95 4 24-4 FMAD-0924-0610 8 (5) 275 - 480 9 35 1.9 4 31-4 FMAD-0931-0810 16 (9.5) 275 - 480 15.4 15 2.1 4 31-4 FMAD-0931-1610 16 (9.5) 275 - 480 15.4 15 3.1 4 32-4 FMAD-0932-1610 25 (13) 275 - 480 11.5 4.6 3.35 6 32-8 FMAD-0932-2510 36 (19) 275 - 480 21 4 3.4 10 34-4 FMAD-0934-3610 50 (32) 275 - 480 20 2 3.4 10 34-4 FMAD-0934-5010 80 (43) 275 - 480 39 1.5 7.35 25 37-4 FMAD-0937-8010 64 (34) 275 - 480 27 1.6 4.3 25 53-4 FMAD-0953-6410 110 (66) 275 - 480 58 1.2 7.25 50 54-4 FMAD-0954-H110 180 (95) 275 - 480 51 0.39 22 95 55-4 FMAD-0955-H210 250 (120) 275 - 480 62.5 0.25 24.5 240 56-4 FMAD-0956-H310 1) Connection straps for M10 6A version: packing unit 2 pcs. Packaging unit 1 Pcs The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments.