FLN-EMSS0000105 SICK | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 6
Technical content
A B C D E F H I J K L M N O P Q R S T FLN-EMSS0000105 | Flexi Loop SAFE SERIES CONNECTION
Ordering information
Type Part no. FLN-EMSS0000105 1061711 Other models and accessories www.sick.com/Flexi_Loop Detailed technical data Safety-related parameters Safety integrity level SIL3 (IEC 61508) SILCL3 (EN 62061) Category Category 4 (EN ISO 13849) Performance level PL e (EN ISO 13849) PFHD (mean probability of a dangerous fail- ure per hour) 0.76 x 10-9 (EN ISO 13849) TM (mission time) 20 years (EN ISO 13849) Functions Diagnostic and monitoring functions Cross-circuit Monitoring via Flexi Loop node Short-circuit Monitoring via Flexi Loop node Discrepancy errors Monitoring via Flexi Loop node Sequence errors Monitoring via Flexi Loop node Interfaces Connection usage Safety device connection For dual-channel equivalent electro-mechanical safety switch (EMSS) Flexi Loop input To connect to a Flexi Loop predecessor node or to connect the Flexi Loop line to the Flexi Soft safety controller. Flexi Loop output To connect to a Flexi Loop successor node or to terminate the Flexi Loop line with the Flexi Loop terminator. Connection type Safety device connection Female connector M12, 5-pin Flexi Loop input Male connector M12, 5-pin Flexi Loop output Female connector M12, 5-pin Number of non-safe inputs 0 Number of non-safe outputs 0 Electrical data Operating data Protection class III (EN 61140) Type of supply voltage PELV or SELV
2 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-02-16 09:46:12
Subject to change without notice
FLN-EMSS0000105 | Flexi Loop SAFE SERIES CONNECTION Supply voltage Vs 24 V DC (16.8 V DC ... 30 V DC) Power consumption 55 mA EMSS interface Test pulse interval 40 ms Test pulse width 12 ms Test pulse current via the switch contacts 3 mA ... 6.2 mA Mechanical data Dimensions (W x H x D) 68.15 mm x 48 mm x 18 mm Weight 28 g (± 5 %) Ambient data Enclosure rating IP65 (EN 60529) IP67 (EN 60529) Ambient operating temperature –25 °C ... +55 °C Storage temperature –25 °C ... +70 °C Classifications ECl@ss 5.0 27371990 ECl@ss 5.1.4 27371990 ECl@ss 6.0 27371819 ECl@ss 6.2 27371819 ECl@ss 7.0 27371819 ECl@ss 8.0 27371819 ECl@ss 8.1 27371819 ECl@ss 9.0 27371819 ETIM 5.0 EC001449 ETIM 6.0 EC001449 UNSPSC 16.0901 41113704 Dimensional drawing (Dimensions in mm (inch)) OSSD, EMSS (1.77) 12.4 (0.49) 10.75 (0.42) 11.5 (0.45) M12 x 1 11.5 (0.45) Ø (Ø 0.71) 36.5 (1.44) 48 (1.89) 15.2 (0.6) 2018-02-16 09:46:12 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 3
A B C D E F H I J K L M N O P Q R S T FLN-EMSS0000105 | Flexi Loop SAFE SERIES CONNECTION PIN assignment EMSS FL_OUT FL_IN The FL_IN pin assignment is only relevant for the first loop node in a safe series connection when connected to Flexi Soft. Addition- al Flexi Loop nodes are connected to FL_OUT using standardized cables with M12 plug connectors. Con- nec- tion Pin Sig- nal Description Col- or-cod- ed con- nect- ing cable FL_IN 1 VDC 24 V supply voltage Brown
2 DA-
TA_OUT Out- put to Flexi Soft input In +1 White
3 GND GND
4 SAFE_OUTSafe
nal, out- put to Flexi Soft input In Black
5 DA-
TA_IN Input from Flexi Soft out- put Xn Gray EMSS 1 EMSS1_A Switching contact 1, connection A Brown
2 EMSS1_BSwitch-
tact 1, con- nec- tion B White
3 EMSS2_ASwitch-
tact 2, con- nec- tion A Blue
4 EMSS2_BSwitch-
tact 2, con- nec- tion B Black
5 EMSS2_ASwitch-
tact 2, con- nec- tion A Gray EMSS pin 3 and EMSS pin 5 can be used as alternatives. The colors listed apply when using pre- assembled cables (no guarantee).
4 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-02-16 09:46:12
Subject to change without notice
FLN-EMSS0000105 | Flexi Loop SAFE SERIES CONNECTION Recommended accessories Other models and accessories www.sick.com/Flexi_Loop Brief description Type Part no. Mounting brackets and plates 1 piece, Flexi Loop fixing clip C-Fix bracket 2068830 2018-02-16 09:46:12 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 5
SICK AG | Waldkirch | Germany | www.sick.com SICK At A GlAnCe SICK is one of the leading manufacturers of intelligent sensors and sensor solutions for industrial applica- tions. A unique range of products and services creates the perfect basis for controlling processes securely and efficiently, protecting individuals from accidents and preventing damage to the environment. We have extensive experience in a wide range of industries and understand their processes and require- ments. With intelligent sensors, we can deliver exactly what our customers need. In application centers in Europe, Asia and North America, system solutions are tested and optimized in accordance with customer specifications. All this makes us a reliable supplier and development partner. Comprehensive services complete our offering: SICK lifetime Services provide support throughout the ma- chine life cycle and ensure safety and productivity. For us, that is “Sensor Intelligence.” WOrldWIde preSenCe: Contacts and other locations – www.sick.com