DESCRIPTION

The FC-73 Series Fire Alarm Control panel is a proven, versatile conventional zoned unit which meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, Auxiliary, Remote and Proprietary Supervising Station Fire Alarm Systems. It is listed to UL Stan- dard 864; inherently power limited, and has all necessary circuitry to meet the UL tran- sient immunity requirements. The system is housed in a heavy-duty steel enclosure finished in red, with pan- els displaying the status of vital functions. The surface mounted enclosure, with its slim appearance (4-inch depth), is designed to blend with any environment. The cabi- net can house up to 7AH batteries while the system’s power supply can maintain batteries of up to 33 AH batteries (enclosed in the separately available BC-1R, 1100- 0654). The many features of the FC-73 pro- vide a cost effective approach to system design, and allow a great degree of flex- ibility in one enclosure. The panel provides ten (10) Class "B" (Style B) or five (5) Class "A" (Style D) zones, expandable to twenty (20) Class "B" or ten (10) Class "A" zones with the addition of the ZDM-FC73 Mod- ule. The FC-73 also provides four (4) Class "B" (Style Y) or two (2) Class "A" (Style Z) notification appliance circuits. Standard on all FC-73 control panels are a City Master Box output, Polarity Rever- sal signaling connections, and Integrated DACT. The combination of a conventional fire alarm control panel with a micropro- cessor design allows for programming of many unique features such as time limit cutoff, programmed verification, pre-alarm delay, and cross-zoning. Individual zones can be assigned specific outputs and zone types such as alarm, supervisory or waterflow. In addition, up to eight (8) se- lectable/programmable notification appli- ance circuit output patterns are available for alternate styles of warnings. Program- ming is achieved through the LCD-FC73 annunciator module or through the Field Configuration Program (FCP-73). FC-73 www.firecontrolinstruments.com Supervision of vital components, modules, functional switches, and standby batter- ies is provided. The integral Digital Alarm Communica- tor Transmitter supports all standard re- porting formats including:  3/1, 1400 Hz  3/1, 2300 Hz  SK 4/2, 1400 Hz  SIA 8  SIA 20  Contact ID Optional modules include an LCD remote annunciator, a zone expander module used to expand the system and a status dis- play module which provides outputs and control functions for each zone as well as program access.

FEATURES

  • Individual Zone Disconnect Switches Supports up to six (6) Remote LCD Displays  Supports up to six (6) Remote LED Annunciators  Integral Digital Communicator Transmitter  Expandable to Twenty (20) Class B or Ten (10) Class A Zones  Field Programmable Configuration  Eight (8) Selectable/Programmable Output Patterns Including Temporal Pattern Output per ANSI S3.41 "Walk Test" Capability provided by the LCD-FC73 optional Remote Annunciator  Programmable Alarm Verification and Cross-Zoning  Four (4) Class B or Two (2) Class A Notification Appliance Circuits  Six (6) Amp power Supply  Three integral progammable relays  Provides Municipal Circuit or Reverse Polarity output  Reverse Polarity or Municipal Circuit output Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no respon- sibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2001 All Rights Reserved 9020-0523 Rev. B Page 1 of 4 An ISO 9001 CompanyAn ISO 9001 CompanyAn ISO 9001 CompanyAn ISO 9001 CompanyAn ISO 9001 Company S1869

www.firecontrolinstruments.com 9020-0523 Rev. B / Page 2 of 4 FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood MA 02090 USA  Tel: 781-471-3000  Fax: 781-471-3099  www.firecontrolinstruments.com Specifications are provided for information only, and are not intened to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2001 All Rights Reserved OPTIONAL ACCESSORIES LCD-FC73 The LCD-FC73 supervised remote annunciator performs all system operations. It can be used for programming and provides access to the Walk Test feature and trouble and alarm information. The control panel can support up to six (6) annunciators. Total distance is up to 3000 feet away over two pair of two-conductor wire. ZONE EXPANDER (ZDM-FC73) The ZDM-FC73 Zone Expander provides the FC-73 with ten (10) additional Class "B" (Style B) or five (5) Class "A" (Style D) initiating circuits. Mounts in main cabinet or in FC-2190 Accessory Cabinet. STATUS DISPLAY MODULE (FC-5280) The FC-5280 Status Display Module provides out- puts and control functions for remote annunciation of alarm, trouble, and supervisory indications for each zone. The system can supervise up to eight (8) mod- ules. The FC-5280 has ten (10) outputs for alarm and ten (10) for trouble annunciation. These outputs are “active low” (become negative when activated). Each output can provide up to 0.100 amp current, with a total of 0.700 amp available. The module has four (4), Form "C" relays that can be wired to operate with any of the outputs. The FC-5280 can be used to interface with an LED annunciator. It can be programmed to indicate alarm and trouble status for Zones 1 - 10, 11 - 20, or system status outputs. The FC-5280 mounts inside the FC73 cabinet. RIN G TI P 61 60T1 RING TI P RING TI P RING TI P 59 58P 1 57 56 55 54T2 P2

1234 Z1 AB CD

591 3 1 7 610 14 18 711 15 19 812 16 20 AAAA BBBB CCCC DDDD Z2 Z3 Z4 Z521 22 23 BE A R T HW GND +2 4 D C 26 27 AB 28 29 GNDPWR 30 31 32 33 34 + NAC4– + NAC3– 35 36 37 38 39 40 41 42 + NAC2– + NAC1– + PR – + 43 44 45 46 47 48 49 NO COM NC NO COM NC NO COM NC FIRE C O NTRO L INSTRUM ENTS FIRE ALARM C O NTRO L MODE L FC-73 ALARM SUPERVISO RY TRO UBLE SILENC ED PO WER ACK SILENCE RESET DRILL T EST MB RESET ACK ENTER 1 2 3 4 5 6 7 8 9 0* # SILENCE ALARM SUPERVISORY TROUBLE SILENCED AC FIRE ALARM ANNUNCIATOR MODEL LCD-FC73 A B SBUS ON 1234 +24GND

1234 Z1A+ B– C– D+

5678 Z3A+ B– C – D+

91 0 1 1 1 2Z3A+ B– C – D+ 13 14 15 16Z4A+ B– C– D+ 17 18 19 20Z5A+ B– C– D+ – + A B SBUS ON 1 234 C1 C2 A1 A2 A3 A4 A5 A6 A7 A8 A9 T 1A10 T 2T 4T3T 5T 7T6T 8 T10T9C 3 C 4 NONO 3C1C NCNC NONO 4C2C NCNC thethethethethe BASIC FC-73 ASSEMBLY

3 amps. @ 60 Hz

3 Programmable Form C Relay Outputs

2.5 amps. @ 24 VDC/ 24 VAC (inductive) 5 amps. @ 24 VDC (resistive) Non power-limited Mounting Location for ZDM-FC73 or FC-5280 (ZDM-FC73 can mount remotely in FC-2190 Accessory Cabinet) Integral DACT Connections

10 Style B or 5 Style D

Initiating Device Circuits Max. Voltage- 25.5 VDC Max. Circuit Resistance- 50 Ohms Total Alarm Current for all Circuits- 1.0 amp. Supervisory Current per Zone- 0.003 amp. Alarm Current per Zone- 0.095 amp. Power-Limited & Supervised with 3.9KW EOL (not required for Style D circuits) SBUS & Auxliary Power 1.0 amp. max. @ 24 VDC

4 Style Y or 2 Style Z

Notification Appliance Circuits Power-limited & Supervised with 3.9KW EOL resistor(Style Y only) 3.0 amps. max. out of any one circuit Reverse Polarity Output Municipal Circuit Output FC-73 www.firecontrolinstruments.com 9020-0523 Rev. B / Page 3 of 4 FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood MA 02090 USA  Tel: 781-471-3000  Fax: 781-471-3099  www.firecontrolinstruments.com Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 2001 All Rights Reserved A B SBUS ON 1234 +24GND RIN G TIP 61 60T1 RI N G TIP RI N G TIP RI N G TIP 59 58P1 57 56 55 54 T2 P2 12 34Z1 AB CD 59 1 3 1 761 0 1 4 1 871 1 1 5 1 981 2 1 6 2 0 AA A ABB B BCC C CDD D D Z2 Z3 Z4 Z521 22 23 BE A R T HW GND +2 4 D C 26 27 AB 28 29 GNDPWR 30 31 32 33 34 + NAC4– + NAC3– 35 36 37 38 39 40 41 42 + NAC2– + NAC 1– + PR 43 44 45 46 47 48 49 NO COM NC NO COM NC NO COM NC FIRE C O NTRO L INSTRUM ENTS FIRE ALARM CONTROL MODE L FC-73 ALARM SUPERVISORY T RO UBLE SI LENC ED PO WER ACK SILENC E RESET DRILL T EST NAC 1 NAC 2 NAC 3 NAC 4 MAS T E R BO X ZONE 1 ZONE 2 ZO NE 3 ZO NE 4 ZO NE 5 ZO NE 6 ZO NE 7 ZO NE 8 ZO NE 9 ZO NE 1 0 ZO NE 1 1 ZO NE 1 2 ZO NE 1 4 ZO NE 1 6 ZO NE 1 7 ZO NE 1 8 ZO NE 1 9 ZO NE 2 0 ZO NE DIS CONNECT SWI TCH (T YPICAL) NAC DIS CONNECT SWI TCH (T YPICAL) ZONE INDICATING LEDs RED/ YELLO W= ALARM/ SUPERVISO RY O FF- NO RMAL YELLO W= ZO NE TRO UBLE (T YPICAL) NAC INDICAT ING LEDs GREEN= CIRCUIT ACT IVE YELLO W= C IRC UIT TRO UBLE TYPIC AL

www.firecontrolinstruments.com 9020-0523 Rev. B / Page 4 of 4 FIRE CONTROL INSTRUMENTS 16 Southwest Park, Westwood MA 02090 USA  Tel: 781-471-3000  Fax: 781-471-3099  www.firecontrolinstruments.com Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change withou t notice. © 2001 All Rights Reserved GENERAL SPECIFICATIONS Primary AC Voltage Total DC Voltage output Auxiliary Power output Smoke Detector output Battery Charging Voltage Battery Charging Current Minimum Telephone input sensitivity Minimum Telephone line voltage Low Battery Threshold Low AC Brown-out Threshold Dimensions Shipping Weight ENVIRONMENTAL SPECIFICATIONS Recommended Operating Temperature Range Recommended Operating Humidity Range INITIATING DEVICE CIRCUIT SPECIFICATIONS 10 Style B (Class B) or 5 Style D (Class A) IDCs expandable to 20 Style B, 10 Style D withh addition of ZDM- FC73 Maximum Voltage Maximum Circuit Resistance Maximum Alarm Current for all Zones Supervisory Current (per Zone) Alarm Current (per Zone) Supervised & Power-Limited NOTIFICATION APPLIANCE CIRCUIT SPECIFICATIONS 4 Style Y (Class B) or 2 Style Z (Class A) NACs rated 3.0 amp. each (Note: total current draw from NACS, smoke detector power, auxiliary power and main Control Panel not to exceed 6.0 amp.) Supervised & Power-Limited APPROVALS U.L. (Std 864) S1869 C.S.F.M. Pending

ORDERING INFORMATION

Part No. Model Description 150-00013 FC73-PCB FC-73 Main Board 150-00014 FC-73 Fire Alarm Control Panel 150-00015 ZDM-FC73 Zone Expander Module 150-00016 LCD-FC73 Remote Annunciator 150-00018 FC-5280 St atus Display Module 150-00023 FC-2190 Accessory Cabinet

120 Vrms @ 60 Hz, 3A

27.4 VDC @ 1A

27.4 VDC

0.75A max. (33 A/H batteries max.) 35 dB 3 V

20.4 VDC

98 VAC

16” W x 26.4” H x 4” D (40.64 x 67.06 x 10.16 cm) 28 lbs. 60° to 80° F (15° to 27° C), 32° to 120° F max. (0° to 49° C) not to exceed 85% @ 90°F (32° C), non-condensing

25.6 VDC

1.0 amp. 0.003 amp. 0.095 amp.