Miniature circuit breaker (MCB), 6 A, 1p, characteristic: C Part no. FAZ-C6/1 Catalog No. 278555 Alternate Catalog No. FAZ-C6/1 EL-Nummer (Norway) 1695151 Similar to illustration Delivery program Basic function Miniature circuit-breakers Number of poles 1 pole Tripping characteristic C Application Switchgear for industrial and advanced commercial applications Rated current In A 6 Rated switching capacity acc. to IEC/EN 60947-2 Icu kA 15 Product range FAZ Technical data Electrical Standards IEC/EN 60947-2 IEC/EN 60898 Rated operational voltage Ue V Ue V AC 240/415 V DC 60 (per pole) Rated voltage according to UL Un V AC 277 Rated switching capacity acc. to IEC/EN 60947-2 Icu kA 15 Breaking capacity according to UL kA 10 (UL1077) Max operational voltage according to IEC/EN 60947-2 V AC 254 Rated switching capacity according to IEC/EN 60947-2 (max operational voltage) Icu kA 10 Rated service short-circuit breaking capacity according to IEC/EN 60947-2 (max operational voltage) Ics 7,5 kA Rated voltage according to IEC/EN 60898-1 Un V AC 240 Rated switching capacity according to IEC/EN 60898-1 Icn kA 10 Rated service short-circuit breaking capacity according to IEC/EN 60898-1 Ics 7,5 kA Operational switching capacity kA 7.5 Characteristic B, C, D, K, S, Z Max. back-up fuse A gL/gG 125 Selectivity Class 3 lifespan Lifespan Operations > 10000 Direction of incoming supply as required Mechanical Standard front dimension mm 45 Enclosure height mm 80 Mounting width per pole mm 17.5 Mounting IEC/EN 60715 top-hat rail Degree of Protection IP20, IP40 (when fitted) Terminals top and bottom Twin-purpose terminals Terminal protection Finger and back-of-hand proof to BGV A2 Terminal capacities mm2 mm2 1 x 25 mm2 2 x 10 04/06/2023 Eaton 278555 ED2022 V93.0 EN 1 / 3

Thickness of busbar material mm 0.8 … 2 Mounting position As required Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation In A 6 Heat dissipation per pole, current-dependent Pvid W 0 Equipment heat dissipation, current-dependent Pvid W 1.5 Static heat dissipation, non-current-dependent Pvs W 0 Heat dissipation capacity Pdiss W 0 Operating ambient temperature min. °C -40 Operating ambient temperature max. °C 75 linear, per +1 °C, results in a 0.5% reduction of current carrying capacity IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat

and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility.

10.9 Insulation properties

10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction

leaflet (IL) is observed. Technical data ETIM 8.0 Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042) Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) Built-in depth mm 70.5 Release characteristic C Number of poles (total) 1 Number of protected poles 1 Rated current A 6 Rated voltage V 230 Rated insulation voltage Ui V 440 Rated impulse withstand voltage Uimp kV 4 Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V kA 10 04/06/2023 Eaton 278555 ED2022 V93.0 EN 2 / 3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V kA 10 Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V kA 15 Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V kA 15 Frequency Hz 50 - 60 Current limiting class 3 Flush-mounted installation No Concurrently switching neutral conductor No Over voltage category 3 Pollution degree 2 Additional equipment possible Yes Width in number of modular spacings 1 Degree of protection (IP) IP20 Ambient temperature during operating °C -25 - 75 Connectable conductor cross section multi-wired mm² 1 - 25 Connectable conductor cross section solid-core mm² 1 - 25 Explosion-proof No 04/06/2023 Eaton Industries GmbH http://www.eaton.eu © 07/2022 by Eaton Industries GmbH Eaton 278555 ED2022 V93.0 EN