FAS MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
MODEL: FAS FAS SPECIFICATIONS ES-1481 Rev.11 Page 1/4 http://www.m-system.co.jp/ Space-saving Plug-in Signal Conditioners F-UNIT DC ALARM Functions & Features
- Providing relay contact closures at preset DC input levels
- Single or dual (Hi/Lo) trip
- Multi-turn screwdriver setpoint adjustments
- Enclosed relays
- Relays can be powered 110 V DC
- High-density mounting Typical Applications
- Annunciator
- Various alarm applications 26 (1.02) 100 (3.94) mm (inch) 137 (5.39) MODEL: FAS–[1][2]–[3][4]
ORDERING INFORMATION
- Code number: FAS-[1][2]-[3][4] Specify a code from below for each of [1] through [4]. (e.g. FAS-62-L/Q)
- Special input range (For code 0) Use Ordering Information Sheet (No. ESU-1033) to specify output code 0 specifications.
- Specify the specification for option code /Q (e.g. /C01/S01) [1] INPUT Current A: 4 – 20 mA DC (Input resistance 250 Ω) D: 0 – 20 mA DC (Input resistance 50 Ω) G: 0 – 1 mA DC (Input resistance 1000 Ω) H: 10 – 50 mA DC (Input resistance 100 Ω) Voltage 3: 0 – 1 V DC (Input resistance 1 MΩ min.) 4: 0 – 10 V DC (Input resistance 1 MΩ min.) 5: 0 – 5 V DC (Input resistance 1 MΩ min.) 6: 1 – 5 V DC (Input resistance 1 MΩ min.) 0: Specify voltage (See INPUT SPECIFICATIONS) [2] OUTPUT 1: Single (SPDT); Hi in power failure 2: Single (SPDT); Lo in power failure 5: Hi/Lo (N.O.); OFF in power failure 6: Hi/Lo (N.C.); OFF in power failure 0: Specify [3] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) L: 170 – 264 V AC (Operational voltage range 170 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals (torque 0.8 N·m) Screw terminal: Nickel-plated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Setpoint adjustments: Multi-turn screwdriver adjustments (front); -5 – +105 % independently Hysteresis (deadband): Approx. 1 % Front LEDs: Red LED turns on when the coil is energized. Power ON timer: Relays de-energized for approx. 2 seconds after power is turned on. INPUT SPECIFICATIONS ■ DC Current: Shunt resistor attached to the input terminals (0.5 W) ■ DC Voltage: 0 – 300 V DC Minimum span: 1 V
MODEL: FAS FAS SPECIFICATIONS ES-1481 Rev.11 Page 2/4 http://www.m-system.co.jp/ Offset: Max. 1.5 times span Input resistance: ≥ 1 MΩ OUTPUT SPECIFICATIONS ■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 380 V AC or 125 V DC Maximum switching power: 120 VA or 30 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 x 107 cycles For maximum relay life with inductive loads, external protection is recommended. Alarm Trip Operation Terminal No. in parentheses Trip Operation in Power Failure
- Output Code 1 : Terminals 3 – 5 turn ON
- Output Code 2 : Terminals 3 – 6 turn ON
- Output Code 5, 6 : both relays turn OFF 0 50 100 ▲ Input (%) Lo Setpoint Hi Setpoint Hi Output (3–5)ON Lo Output (3–6)ON 0 50 100 ▲ Input (%) Lo Setpoint Hi Setpoint Hi Output (3–5)ON Lo Output (3–6)ON
- Output Code : 5
- Output Code : 6 0 50 100 Input (%) ▲ Setpoint Output
- Output Code : 1, 2 (3–6)ON (3–5)ON INSTALLATION Power input
- AC: Approx. 4.5 VA
- DC: 24 V approx. 70 mA 110 V approx. 20 mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail; Standard Rack Mounting Frame BX-16H available Weight: 180 g (0.40 lb) PERFORMANCE in percentage of span Trip point repeatability: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength Power input code R:
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
500 V AC @ 1 minute (I/O to power)
Power input code K, L, P:
1500 V AC @ 1 minute (I/O to power)
MODEL: FAS FAS SPECIFICATIONS ES-1481 Rev.11 Page 3/4 http://www.m-system.co.jp/ EXTERNAL VIEW Single Alarm or Dual High Setpoint Adj. *Dual Low LED *Dual Low Setpoint Adj. Single or Dual High LED *Not provided for Single Alarm. EXTERNAL DIMENSIONS unit: mm (inch) 1 2 3 4 26 (1.02) 93 (3.66) (.59) 2–4.5 (.18) HOLE 15 (.59) deep 8–M3.5 SCREW 7.8 (.31) 107 (4.21) DIN RAIL 35mm wide [3.3 (.13)] CLAMP (top & bottom) 137 (5.39)
- When mounting, no extra space is needed between units. 26 (1.02) 100 (3.94) TERMINAL ASSIGNMENTS unit: mm (inch) 3 4 1 2 INPUT RESISTOR (model: REM) 19 (.75) Input shunt resistor attached for current input.
MODEL: FAS FAS SPECIFICATIONS ES-1481 Rev.11 Page 4/4 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Inductive Load (Coil) Varistor or Spark Quenching Circuit
- DC Powered Inductive Load (Coil) Diode, Varistor or CR Circuit ■Relay Protection
- AC Powered Ry Base Socket Comparator ADJ. *INPUT
1 Low Drift
- Input shunt resistor attached for current input. ** Relay status is determined by output codes. ■ SINGLE ALARM Base Socket Comparator HI ADJ. *INPUT
LO ADJ. OUTPUT6 Ry Ry HI LO ■ DUAL ALARM * Input shunt resistor attached for current input. ** Relay status is determined by output codes. U(+) V(–) POWER U(+) V(–) POWER LOAD U LOAD Specifications are subject to change without notice.