FAMCL-01 MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 3

Technical content

MODEL: FAMCL-01 FAMCL-01 SPECIFICATIONS ES-9031 Rev.4 Page 1/3 https://www.m-system.co.jp/ Remote I/O FAM Series CC-Link MASTER MODULE (Yokogawa Electric PLC use) (1.18) 102 (4.02) mm (inch) 118 (4.65) MODEL: FAMCL-01

ORDERING INFORMATION

  • Code number: FAMCL-01

RELATED PRODUCTS

  • Yokogawa Electric PLC: FA-M3V Recommended CPU module: F3SP71-4S, F3SP76-7S, F3SP22
  • Configurator software (model: FAMCLCFG) Configurator software downloadable at M-System’s web site. In order to use FAMCLCFG, YOKOGAWA Electric Corporation 'WideField3' (R.3.02 or later) is required. FAMCL -01 and a PC are connected through the CPU unit of FA-M3V. PACKAGE INCLUDES...
  • Terminating resistor 110Ω (0.5W): 2 pcs. GENERAL SPECIFICATIONS Connection CC-Link: Separable tension clamp terminal Cable connector: TFMC1,5 / 5–STF–3,5 (Phoenix Contact) (included in the package) Applicable wire size: 0.2 − 1.5 mm2; stripped length 10 mm Recommended solderless terminal
  • AI0,25−10YE 0.25 mm2 (Phoenix Contact)
  • AI0,34−10TQ 0.34 mm2 (Phoenix Contact)
  • AI0,5−10WH 0.5 mm2 (Phoenix Contact)
  • AI0,75−10GY 0.75 mm2 (Phoenix Contact)
  • A1−10 1.0 mm2 (Phoenix Contact)
  • A1,5−10 1.5 mm2 (Phoenix Contact) Internal bus: Via the Installation Base Internal Power: Via the Installation Base Max. installable module: 2 Installable unit: Main unit and sub unit Isolation: CC-Link or FG to internal bus or internal power Status indicator LEDs:
  • RDY, RUN, LRUN, SD, RD: Green LED
  • ERR, LERR: Red LED CC-Link COMMUNICATION CC-Link: Ver. 1.10/2.00 Master function: Master station (local station, standby master station not supported) Station address: 00 (Use with '00'. Works as '00' even set to other than '00'.) Supported slave station: Remote I/O station Remote device station (Ver. 1.10) Remote device station (Ver. 2.00) Intelligent device station, local station not supported Max. number of units connected: 64 (Remote I/O station) 42 (Remote device station) Max. number of link points: RX: 8192 (Data unit: bit) RY: 8192 (Data unit: bit) RWr: 2048 (Data unit: word) Rww: 2048 (Data unit: word) Protocol: CC-Link Ver. 1.10 conformed Network topology: Multi-drop Max. overall cable extension length: 100 m (10 Mbps), 160 m (5 Mbps), 400 m (2.5 Mbps), 900 m (625 kbps), 1200 m (156 kbps) Transmission media: CC-Link Ver. 1.10 compatible cable Operational station: Master station Operational mode: On-line mode Communication mode: Cyclic transmission Baud rate: 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps, set with rotary switch Slave station settings: With configurator software (model: FAMCLCFG) INSTALLATION Current consumption: 600 mA @ 5V DC Operating temperature: 0 to 55°C (32 to 131°F) Operating humidity: 10 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base Module (model: F3BUxx-0N or F3BU05-0D)

MODEL: FAMCL-01 FAMCL-01 SPECIFICATIONS ES-9031 Rev.4 Page 2/3 https://www.m-system.co.jp/ Weight: 150 g (0.33 lb) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (CC-Link or FG to internal bus or internal power) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EXTERNAL VIEW Station Address Setting Rotary SW Baud Rate Setting Rotary SW Status Indicator LED STATION No. ×10 B.RATE DA DB DG SHIELD SHIELD ■ FRONT VIEW Tension Clamp Terminal ■ STATUS INDICATOR LED ID STATUS COLOR FUNCTION RDY ON Green FA-M3 internal communication normal RUN ON Green In cyclic transmission, FAMCL internal communication normal Blinking Green Self diagnostics error ERR ON Red Communication error Blinking Slave station data link error LRUN ON Green Data link running LERR ON Red Data link intercommunication error SD ON Green Transmitting data RD ON Green Receiving data

MODEL: FAMCL-01 FAMCL-01 SPECIFICATIONS ES-9031 Rev.4 Page 3/3 https://www.m-system.co.jp/ COMMUNICATION CABLE WIRING DA DB DG SHIELD SHIELD FAMCL-01 Blue White Yellow DA DB DG SLD FG I/O Unit DA DB DG SLD FG I/O Unit TERMINATOR TERMINATOR EXTERNAL DIMENSIONS unit: mm [inch] 100 (3.94) 2 (.08) SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM INTERNAL BUSDA DB DG SHIELD SHIELD INDICATOR ROTARY SW TO OTHER CC-Link DEVICES Isolation INTERNAL POWER Comm. Circuit CONNECTOR Control Circuit * Grounded at the installation base Specifications are subject to change without notice.