SS-PD GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- Air velocity rating from 100 to 4,000 feet per minute (0.5 to 20.32 m/sec.). Patented telescopic sampling tube. Easily accessible code wheels for addressing detector. Outside mounting tabs. Mounts to round or rectangular ducts from 1’ to 12’ (0.3 to 3.7 meters) wide. Transparent cover for conve- nient visual inspection. Listings Listings and approvals below apply to the SS-PD and SS- PDR Intelligent Low-Flow Photoelectric Duct Smoke Detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: file S1115. CSFM approved: file 3240-1288:167. MEA approved: file 384-02-E Vol. III. SS-PD and SS-PDR Intelligent Low-Flow Photoelectric Duct Smoke Detectors
Description
The Gamewell SS-PD and SS-PDR Intelligent Low-Flow Photoelectric Smoke Duct Detectors provide low- flow technology that enables duct smoke detection throughout a broad range of airflow environments in HVAC applications. The low-flow technology can detect smoke at air speed veloci- ties of 100 feet per minute (0.5 m/sec.) or greater, while continuing the same reliable performance to 4,000 feet per minute (20.32 m/sec.). The intelligent low-flow duct detectors sample air cur- rents passing through a duct and gives dependable performance for shutdown SS-PDR
Applications
Duct smoke detectors have specific limitations, they are: NOT a substitute for open area smoke detectors. NOT a substitute for early warning detection. NOT a replacement for a building’s regular fire detection system. Please call Gamewell for a copy of System Sensor’s application guide, Proper Use of Smoke Detectors in Duct Applications , (A05-1004-00). Installation Wiring: For signal wiring (the wiring between detectors or from detectors to auxil- iary devices), it is recommended that single conductor wire be no smaller than 18 AWG (0.75 mm²). The duct smoke detector terminals accommodate wire sizes up to 12 AWG (3.25 mm²). Flexible conduit is recommended for the last foot (30.48 cm) of conduit; solid conduit connections may be used if desired. Smoke detectors and alarm system control panels have specifications for Signal- ing Line Circuit (SLC) wiring. Consult the control panel specifications for wiring requirements before wiring the detector loop. The SS-PD and SS-PDR detectors are designed for ease of wiring; their housing provides a terminal strip with clamp- ing plates. LED Features: If programmed with the system control panel, two LEDs on each duct smoke detector light to provide local visible indication. SS-PD of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke an fire gases through the protected area. The SS-PD and SS-PDR provide a remote alarm output for use with auxiliary devices such as the RA400 remote LED annunciator, as well as remote test capa- bility with the RTS451 or RTS451KEY Remote Test Stations. The SS-PD is a photoelectric duct detector with Smart Scan TM protocol. The SS- PDR additionally incorporates a relay.
SS-PD and SS-PDR CS-2463 10/21/04Page 2 of 4 Specifications SS-PD Operating voltage range 15 to 32 VDC. Standby current 300 µA @ 24 VDC (one communi- cation every 5 seconds with LED blink enabled). Operating temperature range Relative Humidity range 10% to 93% (non-condensing). Duct air velocity 100 to 4,000 feet/min (0.5 to 20.32 m/s). Dimensions 14.750" (37 cm) length x 5.500" (14 cm) width x 2.750" (7 cm) deep. Options 1. RTS-451, RTS-451KEY, RA400Z. 2. PA400 (Review installation instruc- tions on power requirements) . SS-PDR Operating voltage range 20 to 30 VDC, 24 VAC/VDC, 120/
240 VAC auxiliary power (requires
a separate auxiliary source ). Standby current 300 µA @ 24 VDC (one communi- cation every 5 seconds with LED blink enabled). Operating temperature range Relative Humidity range 10% to 93% (non-condensing). Duct air velocity 100 to 4,000 feet/min (0.5 to 20.32 m/s). Dimensions 14.750" (37 cm) length x 5.500" (14 cm) width x 2.750" (7 cm) deep. Options 1. RTS-451, RTS-451KEY, RA400Z. 2. PA400 (Review installation instruc- tions on power requirements).
10 Amp @ 30 VDC
10 Amp @ 277 VAC (0.75 P ow er Factor) 240 VAC @ 249 VAC (0.4 P ow er Factor) 1/8 HP @ 120 VAC 1/4 HP @ 240 VAC Supervisory Contact (SPST)
2.0 Amp @ 30 VDC (resistive)
SS-PDR: Relay Contact Ratings Alarm Auxiliary Contacts * (DPDT) Minimum sw itching current of 100 mA @ 5 VDC. Power Supply Voltage 30-30VDC 24VAC, 50/60 Hz 120VAC, 50/60 Hz 220/240 VAC, 50/60 Hz Max. Standby Current
26 Ma 65 mA
Sec. 3 to 17 Sec. 3 to 17 Sec. 3 to 17 Sec Power Up Time 2 Sec. 2 Sec. 2 Sec. 2 Sec. SS-PD: Current Requirements (using no accessories ) The RA400Z The RTS451 The RTS451KEY Programming specifications requirements for intelligent system control panels: The number of devices that can have their LEDs programmed to illuminate is limited by the fea- tures of the panel and the indi- vidual devices. The actual num- ber of devices is determined by the control panel and its ability to supply LED cur- rent. Refer to the control panel installation manual for details. Product Line Information Model Description SS-PD Duct detector housing with Smart Scan™ photoelectric smoke detector. SS-PDR Duct detector housing with Smart Scan™ photoelectric smoke detector, DPDT relay. A5053GM Replacement photoelectric sensor board. A5067 Replacement power board (without relay). A5060 Replacement power board (with relay). ST-1.5 Metal sampling tube, duct widths 1' to 2' (see table at left for metric lengths) . ST-3 Metal sampling tube, duct widths 2' to 4'. ST-5 Metal sampling tube, duct widths 4' to 8'. ST-10 Metal sampling tube, duct widths 8' to 12'. RA400Z Remote annunciator alarm LED. RTS451 Remote test station. Mounts in single-gang box. Includes red alarm LED and magnet test switch. RTS451KEY Key-activated remote test station. F36-09-11 Replacement filters. M02-04-00 Replacement test magnet. S08-39-01 Replacement photo insect screen.
SS-PD and SS-PDR CS-2463 10/21/04 Page 3 of 4 Sample Wiring Diagrams *NOTE: Inlet tube is required and must be purchased separately. Order one inlet tube for each duct smoke detector ordered. htdiWtcuDedistuO* ebuTtelnI )m6906.0(teef2otpU5 .1-TS )m2912.1ot6906.0(teef4ot23 -TS )m4834.2ot2912.1(teef8ot45 -TS )m6756.3ot4834.2(teef21ot80 1-TS SS-PD Duct Smoke Detector using a UL Listed control panel SS-PD Detector Terminals On to other Detectors on the Loop SS-PD Please refer to manual I56-1978-002R for installation instructions. SS-PDR Please refer to manual I56-1979-003R for installation instructions. SS-PD Detector Terminals SS-PD Duct Smoke Detector with optional RA400Z SS-PD Duct Smoke Detector with RTS451/ RTS451KEY NOTE: For RTS451, Terminal 3 is not used. RTS451 does not have a Terminal For RTS451KEY, Terminals 3 and 6 are not used. 6821wir1.wmf 6821wir2.wmf 6821wir3.wmf
SS-PD and SS-PDR CS-2463 10/21/04Page 4 of 4 The Gamewell Company
12 Clintonville Road
Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell.com A Honeywell Company © 2004 Gamewell Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell.